Plan Review Details - Permit 21090496
Plan Review Stops For Permit 21090496
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-12-10 Cont ID  
Sent By cthroop Date 2021-12-10 Time 07:20 Rev Time 0.00
Received By cthroop Date 2021-12-09 Time 15:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-03 Cont ID  
Sent By cthroop Date 2021-11-03 Time 16:06 Rev Time 0.00
Received By cthroop Date 2021-11-03 Time 14:41 Sent To  
Notes
2021-11-03 16:12:41BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1.PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER FIGURE
 R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
  
 2.PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN
 PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX.
 DO NOT E-MAIL DOCUMENTS TO THE PLANS EXAMINER.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-10 Cont ID  
Sent By cthroop Date 2021-12-10 Time 07:20 Rev Time 0.00
Received By cthroop Date 2021-12-10 Time 07:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-07 Cont ID  
Sent By mpeterso Date 2021-12-07 Time 15:42 Rev Time 0.00
Received By mpeterso Date 2021-12-07 Time 15:41 Sent To  
Notes
2021-12-07 15:43:10PASSED ELECTRICAL REVIEW
 NEW SUBMITTALS CONTAIN ELECTRICAL RISER DIAGRAM AND
 PANEL SCHEDULE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By jleahy Date 2021-10-06 Time 16:28 Rev Time 0.00
Received By jleahy Date 2021-10-06 Time 16:28 Sent To  
Notes
2021-10-06 16:32:54ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED RISER DIAGRAM SHOWING LOCATION OF PANEL AND ALSO
 NEED A PANEL SCHEDULE.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-09-24 Cont ID  
Sent By lcrespo Date 2021-09-24 Time 16:11 Rev Time 0.00
Received By lcrespo Date 2021-09-24 Time 16:11 Sent To  
Notes
2021-09-24 16:11:5709/24/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-10-07 Cont ID  
Sent By fmittner Date 2021-10-07 Time 11:49 Rev Time 0.00
Received By fmittner Date 2021-10-07 Time 11:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-10 Cont ID  
Sent By cthroop Date 2021-12-10 Time 07:20 Rev Time 0.00
Received By cthroop Date 2021-11-09 Time 16:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-03 Cont ID  
Sent By cthroop Date 2021-11-03 Time 16:13 Rev Time 0.00
Received By cthroop Date 2021-09-14 Time 07:04 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-11-10 Cont ID  
Sent By medwards Date 2021-11-10 Time 09:31 Rev Time 0.00
Received By medwards Date 2021-11-10 Time 09:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By medwards Date 2021-09-20 Time 17:22 Rev Time 0.00
Received By medwards Date 2021-09-20 Time 17:22 Sent To  
Notes
2021-09-20 17:23:451) PLEASE SHOW THE ANCHORAGE OF THE CONDENSING UNIT
 WILL COMPLY WITH FBC RES M1307.2
  
 2) PLEASE SHOW THE CONDENSATE PIPE AND THE TERMINATION
 LOCATION. FBC RES M1411.3
  
 3) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-09-24 Cont ID  
Sent By lcrespo Date 2021-09-24 Time 16:09 Rev Time 0.00
Received By lcrespo Date 2021-09-24 Time 16:09 Sent To  
Notes
2021-09-24 16:12:3709/24/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-12-10 Cont ID  
Sent By cthroop Date 2021-12-10 Time 07:20 Rev Time 0.00
Received By cthroop Date 2021-12-09 Time 15:20 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-11-03 Cont ID  
Sent By cthroop Date 2021-11-03 Time 15:54 Rev Time 0.00
Received By cthroop Date 2021-11-03 Time 14:45 Sent To  
Notes
2021-11-03 16:06:20ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
  
 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX.
 DO NOT E-MAIL DOCUMENTS TO THE PLANS EXAMINER.
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-10 Cont ID  
Sent By medwards Date 2021-11-10 Time 09:30 Rev Time 0.00
Received By medwards Date 2021-11-10 Time 09:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-20 Cont ID  
Sent By medwards Date 2021-09-20 Time 17:27 Rev Time 0.00
Received By medwards Date 2021-09-20 Time 17:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-10-07 Cont ID  
Sent By llouie Date 2021-10-07 Time 11:50 Rev Time 0.00
Received By fmittner Date 2021-10-07 Time 11:50 Sent To  
Notes
***NONE***