Plan Review Details - Permit 21090450
Plan Review Stops For Permit 21090450
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-29 Cont ID  
Sent By pvalenti Date 2021-10-29 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2021-10-29 Time 16:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-09-29 Time   Rev Time 0.00
Received By   Date 2021-09-29 Time   Sent To  
Notes
2021-09-29 13:53:14SEE PLUMBING COMMENTS, FBC 107 FLOOR PLAN SHOWING
 NATURE AND LOCATION OF PROPOSED IMPROVEMENT REQUIRED.
 ALL WORK PROPOSED TO BE SHOWN.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-04 Cont ID  
Sent By pleduc Date 2021-10-04 Time   Rev Time 0.00
Received By pleduc Date 2021-10-04 Time 14:03 Sent To  
Notes
2021-10-04 14:04:24FIRE PROVISO:
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS
 ARE MAINTAINED & REPAIRED IF DAMAGED.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-29 Cont ID  
Sent By pvalenti Date 2021-10-29 Time 16:37 Rev Time 0.00
Received By pvalenti Date 2021-10-20 Time 05:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-04 Cont ID  
Sent By lcrespo Date 2021-10-04 Time 14:50 Rev Time 0.00
Received By lmarchan Date 2021-09-09 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By lcrespo Date 2021-10-20 Time 08:24 Rev Time 0.00
Received By lcrespo Date 2021-10-20 Time 08:23 Sent To  
Notes
2021-10-20 08:25:2110/20/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-13 Cont ID  
Sent By lcrespo Date 2021-09-13 Time 17:09 Rev Time 0.00
Received By lcrespo Date 2021-09-13 Time 17:09 Sent To  
Notes
2021-09-13 17:38:5409/13/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE A LAYOUT OF THE BATHROOM BEING
 CHANGED FROM A TUB TO A SHOWER AND HOW MANY BATHROOMS
 THERE TO DETERMINE THE FAIR HOUSING DESIGN OR
 GUIDELINES THAT WAS USED
 THIS NEEDS TO BE DETERMINED BY RESEARCHING WHEN THE
 BUILDING WAS BUILT AND REQUESTING PLANS FROM THIS
 CITY'S WEBSITE. THIS MAY INCUR A FEE AND TIME TO
 RETRIEVE ALL THIS INFORMATION AND DETERMINE IF THE
 LEVEL OF ACCESSIBILITY IS ALTERED. WE REQUIRE TO SHOW
 THE DIMENSION OF THE CLEAR FLOOR SPACE IN THE BATHROOM
 IN FRONT OF EACH FIXTURE IN THAT BATHROOM. THE RESEARCH
 WILL TELL IF IT'S AN A OR B TYPE BATHROOM.
  
 2. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR THE CHANGING OF AN FHA
 COMPLIANCE STRUCTURE. THE OWNER AND DESIGNER OF RECORD
 ACKNOWLEDGE THAT THE PROPOSED BATHROOM DESIGN DOES NOT
 MEET THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES. THE OWNER AGREES TO REVERT THE UNIT BACK TO
 COMPLIANCE AT THE TIME OF SALE IF SO, REQUESTED BY THE
 BUYER. THIS WILL BE IN A LETTER TYPE FORMAT SIGNED AND
 NOTARIZED BY THE OWNER. WE PROVIDE A SAMPLE LETTER AND
 IT MUST BE SUBMITTED TO THE BUILDING DEPARTMENT OF THE
 CITY OF WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN
 EMAIL TO [email protected] AND I WILL SEND A COPY OF THE
 FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  