Plan Review Details - Permit 21090446
Plan Review Stops For Permit 21090446
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By cpuell Date 2021-09-27 Time 10:02 Rev Time 0.00
Received By cpuell Date 2021-09-27 Time 10:02 Sent To  
Notes
2021-09-27 10:03:01ACCESORY STRUCTURE GIVEN THE ADDRESS OF 506 N ST

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-14 Cont ID  
Sent By cthroop Date 2021-12-14 Time 16:37 Rev Time 0.00
Received By cthroop Date 2021-12-14 Time 16:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-23 Cont ID  
Sent By cthroop Date 2021-11-23 Time 12:37 Rev Time 0.00
Received By cthroop Date 2021-11-22 Time 11:05 Sent To  
Notes
2021-11-23 12:38:16BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. RE-SUBMIT SITE DRAINAGE PLAN AND ANY OTHER PLAN THAT
 WILL HAVE THE REVISED FINISHED FLOOR ELEVATION.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-07 Cont ID  
Sent By cthroop Date 2021-11-07 Time 10:46 Rev Time 0.00
Received By cthroop Date 2021-11-07 Time 09:47 Sent To  
Notes
2021-11-07 10:47:05BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REMOVE ROOFING FROM DEFERRAL LETTER BY AOR. ROOFING
 CANNOT BE DEFERRED. ROOFING SHALL BE BY SEPERATE
 PERMIT. SEE PROVISO ON PLAN PAGE S-2.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 107.3.4.1 DEFERRED SUBMITTALS.
  
 2. REMOVE ROOFING FROM DEFERRED SUBMITTALS ON PLAN PAGE
 A.O. SEE ABOVE #1.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 107.3.4.1 DEFERRED SUBMITTALS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-27 Cont ID  
Sent By cthroop Date 2021-09-27 Time 10:24 Rev Time 0.00
Received By cthroop Date 2021-09-24 Time 15:25 Sent To  
Notes
2021-09-27 10:25:14PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 ACCESSORY STRUCTURE
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REF. PLAN PAGE A.0 FOR THE FOLLOWING COMMENTS:
 1A) CHANGE BUILDING CODE REFERENCE TO 7TH ED, 2020.
 1B) CHANGE NEC REFERENCE TO 2017 NEC.
  
 2. PROVIDE BUILDING DATA: CONDITIONED SPACE,
 UN-CONDITIONED SPACES.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. CANNOT VERIFY VALUE DUE TO LACK OF BUILDING DATA.
 (SEE ABOVE)
 CITY OF WPB CHPT109.3 BUILDING PERMIT VALUATIONS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 4. PROVIDE A SITE DRAINAGE PLAN SHOWING COMPLIANCE WITH
 FBC R401.3 DRAINAGE.
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
  
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10
 FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE
 DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING
 FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
  
 5. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE
 ALTERNATIVE.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 6. REF. PLAN PAGE A-3 FOR THE FOLLOWING COMMENT;
 THE TEXT FOR THE INSTALLATION INSTRUCTIONS FOR THE
 GABLE END SHEATHING AND WOOD BEAM HAS TEXT OVERRIDDEN.
 CANNOT READ TEXT. PLEASE CORRECT.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 7. REF. PLAN PAGE S-4 FOR THE FOLLOWING COMMENT:
 PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER DESIGN
 PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 8. PROVIDE THE ICC-ES REPORT FOR THE SPRAY APPLIED
 INSULATION. DESIGNER SHALL SELECT SYSTEM TO BE
 INSTALLED.
 FBC 107.3.4 FAC RULE 9N-3 REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 9. PROVIDE PRODUCT APPROVALS FOR OVERHEAD DOOR.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-29 Cont ID  
Sent By fgiaquin Date 2021-09-29 Time 09:27 Rev Time 0.00
Received By fgiaquin Date 2021-09-29 Time 09:27 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-09-21 Cont ID  
Sent By fmittner Date 2021-09-21 Time 10:16 Rev Time 0.00
Received By fmittner Date 2021-09-21 Time 10:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-14 Cont ID  
Sent By cthroop Date 2021-12-14 Time 16:37 Rev Time 0.00
Received By cthroop Date 2021-11-30 Time 11:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-23 Cont ID  
Sent By lmarchan Date 2021-11-23 Time 12:50 Rev Time 0.00
Received By lmarchan Date 2021-11-18 Time 15:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-29 Cont ID  
Sent By fgiaquin Date 2021-09-29 Time 09:28 Rev Time 0.00
Received By fgiaquin Date 2021-09-09 Time 10:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2021-11-23 Cont ID  
Sent By lmarchan Date 2021-11-23 Time 12:50 Rev Time 0.00
Received By lmarchan Date 2021-11-23 Time 12:50 Sent To  
Notes
2021-11-23 12:50:51APPROVED UNDER 21080641

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-12-02 Cont ID  
Sent By medwards Date 2021-12-02 Time 13:39 Rev Time 0.00
Received By medwards Date 2021-12-02 Time 13:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-22 Cont ID  
Sent By cthroop Date 2021-11-22 Time 11:08 Rev Time 0.00
Received By cthroop Date 2021-11-22 Time 11:05 Sent To  
Notes
2021-11-22 11:09:17SEE MECH. COMMENTS UNDER 21080641 BY ME. CT

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-09-27 Cont ID  
Sent By cthroop Date 2021-09-27 Time 10:13 Rev Time 0.00
Received By cthroop Date 2021-09-24 Time 15:25 Sent To  
Notes
2021-09-27 10:14:36SEE MECHANICAL REVIEW COMMENTS UNDER MAIN DWELLING UNIT
 21080641 BY ME. CT

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By cthroop Date 2021-09-27 Time 14:16 Rev Time 0.00
Received By cthroop Date 2021-09-27 Time 14:16 Sent To  
Notes
2021-09-27 14:17:15LC APPROVED UNDER PERMIT 21080641. 504 N ST. CT

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2021-11-22 Cont ID  
Sent By cthroop Date 2021-11-22 Time 11:05 Rev Time 0.00
Received By cthroop Date 2021-11-22 Time 11:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-09-27 Cont ID  
Sent By cthroop Date 2021-09-27 Time 10:14 Rev Time 0.00
Received By cthroop Date 2021-09-24 Time 15:25 Sent To  
Notes
2021-09-27 10:15:45PRODUCT APPROVALS SUBMITTED FOR REVIEW ON 11/17/2021.
 SEE 2ND ROOFING REVIEW. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-12-14 Cont ID  
Sent By cthroop Date 2021-12-14 Time 16:37 Rev Time 0.00
Received By cthroop Date 2021-12-14 Time 16:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-22 Cont ID  
Sent By cthroop Date 2021-11-22 Time 11:09 Rev Time 0.00
Received By cthroop Date 2021-11-22 Time 11:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-07 Cont ID  
Sent By cthroop Date 2021-11-07 Time 10:09 Rev Time 0.00
Received By cthroop Date 2021-11-07 Time 10:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By cthroop Date 2021-09-27 Time 10:12 Rev Time 0.00
Received By cthroop Date 2021-09-24 Time 15:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-11-08 Cont ID  
Sent By amhamilt Date 2021-11-08 Time 14:43 Rev Time 0.00
Received By amhamilt Date 2021-11-08 Time 14:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-21 Cont ID  
Sent By fmittner Date 2021-09-21 Time 10:16 Rev Time 0.00
Received By fmittner Date 2021-09-21 Time 10:16 Sent To  
Notes
2021-09-21 10:17:03NEEDS SEPARATE LANDSCAPE PLAN/PERMIT