Plan Review Details - Permit 21090432
Plan Review Stops For Permit 21090432
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 11:01 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 11:01 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-03-15 Cont ID  
Sent By rmcphers Date 2022-03-15 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 14:48 Sent To  
Notes
2022-03-15 14:48:46PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-10-19 Cont ID  
Sent By rmcphers Date 2021-10-19 Time 13:48 Rev Time 0.00
Received By rmcphers Date 2021-10-19 Time 13:48 Sent To  
Notes
2021-10-19 13:49:32PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 11:02 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-15 Cont ID  
Sent By rmcphers Date 2022-03-15 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 14:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-19 Cont ID  
Sent By rmcphers Date 2021-10-19 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 15:48 Sent To  
Notes
2021-10-19 14:16:28BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE ACCESSIBLE SEATING AT THE BAR -
 COUNTER HEIGHT, KNEE CLEARANCE, TOE CLEARANCE ETC. -
 FBC ACCESSIBILITY 226.2 (BUILDING OFFICIALS
 INTERPRETATION IS THAT ACCESSIBLE SEATING MUST BE
 PROVIDED AT THE BAR)
 2) EXTERIOR COOLER IS SUBJECT TO WIND LOADS FBC 1609 -
 PLEASE PROVIDE THE EXTERIOR COOLER DETAILS SHOWING WIND
 DESIGN CRITERIA, PANEL DESCRIPTIONS, ATTACHMENTS,
 FOUNDATIONS ETC.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-13 Cont ID  
Sent By jleahy Date 2021-10-13 Time 11:45 Rev Time 0.00
Received By jleahy Date 2021-10-13 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By   Date 2022-03-14 Time   Rev Time 0.00
Received By bdolan Date 2022-03-14 Time 12:36 Sent To  
Notes
2022-03-14 12:36:50ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-09-20 Cont ID  
Sent By   Date 2021-09-20 Time   Rev Time 0.00
Received By bdolan Date 2021-09-20 Time 11:33 Sent To  
Notes
2021-09-20 11:43:23ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 BY A FIRE ALARM CONTRACTOR. A SEPARATE SHOP DRAWING
 COMPLIANT WITH NFPA 72 IS REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-03-17 Cont ID  
Sent By jesmith Date 2022-03-17 Time 12:19 Rev Time 0.00
Received By jesmith Date 2022-03-17 Time 10:07 Sent To  
Notes
2022-03-17 12:18:5321090432 5107 S DIXIE HWY
  
 GAS COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR GAS
  
 CITY OF WEST PALM BEACH GAS PIPING AFFIDAVIT OR
 MANOMETER TEST DOCUMENT REQUIRED AT JOBSITE FOR FINAL
 GAS INSPECTION. CALL 561-805-6692 FOR FURTHER
 INFORMATION
  
 INSTALLATION MANUALS FOR ALL GAS EQUIPMENT SHALL BE
 ONSITE FOR GAS INSPECTION. A SEPARATE PERMIT IS
 REQUIRED FOR THE GAS
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-09-29 Cont ID  
Sent By pvalenti Date 2021-09-29 Time 06:12 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:35 Sent To  
Notes
2021-09-29 06:12:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090432 5107 S DIXIE HWY
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2020 FUEL GAS CODE SEC. 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1.
  
 2.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR GAS
 SHUT OFF VALVES AND APPLIANCE VALVES. VALVES SHALL
 COMPLY WITH FBC FG SECTION 409.1.1 AND TABLE 409.1.1.
  
 3.ACCORDING TO THE PLUMBING LEGEND ON P0.1, ON P3.1 GAS
 RISER, A GAS COCK AND A BALL VALVE ARE IN THE
 CONNECTION LINE TO THE BOIL KETTLE, GAS COCKS ARE IN
 CONNECTION LINES TO THE TANKLESS HEATERS, BUT ARE SHOWN
 AS BALL VALVES IN THE TANKLESS WATER HEATER DETAIL ON
 P4.1, AND A BALL VALVE AND GAS COCK ARE IN UPSTREAM
 SIDE OF THE GAS METER. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 4.RE: P4.1 DETAIL MEDIUM TO LOW PRESSURE GAS REGULATOR
 DETAIL; DISTRIBUTION DOWNSTREAM OF THE UTILITY COMPANY
 REGULATOR IS ALREADY .5 PSI. IS DELIVERY PRESSURE TO
 APPLIANCES TO BE REDUCED AGAIN? IF SO, PER WPB FBC
 107.2.1, INDICATE THE AFFECTED APPLIANCE(S), CLARIFY
 AND STATE THE REDUCED PRESSURE. INDICATE ANY ADDITIONAL
 TABLES USED IN SIZING. SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. 2020 FGC SEC.410.1.
 PROVIDE IF NOT, DELETE THE DETAIL; DELETE ANY
 REGULATORS IN THE RISER DIAGRAM AS WELL. IT IS NOTED
 THAT THE TANKLESS WATER HEATER DETAIL DOES NOT INDICATE
 ANY MP REGULATORS.
  
 5. PER WPB FBC 107.2.1, PROVIDE AN APPLIANCE CONNECTION
 DETAIL SHOWING VALVE, UNION(S) AND DIRT LEG.
  
 6. PER WPB FBC 107.2.1, PROVIDE A GAS PIPE HANGER AND
 WALL STAND-OFF DETAIL WITH A NOTE STATING, " GAS PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC FG 407.2."
  
 7. PER WPB FBC 107.2.1, PROVIDE A GAS EQUIPMENT
 SCHEDULE INDICATING LISTING THE BTU LOAD OF EACH
 APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM.
  
 8.PER WPB FBC 107.2.1, SUBMIT CALCULATIONS FOR
 COMBUSTION AIR FOR THE BOIL KETTLE AND THE AVAILABLE
 COMBUSTION AIR 9NOT TO BE CONFUSED WITH MAKE-UP AIR)
 PER THE 2020 FBC-FUEL GAS CODE SEC.304.1.
  
 9. PER WPB FBC 107.2.1, ON THE PLAN SUBMIT A DETAIL
 SHOWING THE TYPES, LOCATIONS, SIZE, TERMINATION POINTS,
 HEIGHT ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS
 VENT(S) PER 2020 FBC-FUEL GAS SECS. 502 THRU 505.
 DETAIL(S) SHALL ALSO COMPLY WITH MANUFACTURERS
 RECOMMENDATIONS (SEE NAVIEN COMMON VENT INSTALLATION
 GUIDE HTTPS://WWW.NAVIENINC.COM/DOWNLOADS/COMMON-VENT-I
 NSTALLATION-MANUAL-EN)
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090432 5107 S DIXIE HWY
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-28 Cont ID  
Sent By medwards Date 2022-06-28 Time 17:07 Rev Time 0.00
Received By medwards Date 2022-06-25 Time 07:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2022-05-22 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-17 Cont ID  
Sent By jesmith Date 2022-03-17 Time 12:35 Rev Time 0.00
Received By jesmith Date 2022-03-17 Time 12:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-19 Cont ID  
Sent By rmcphers Date 2021-10-19 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2021-09-14 Time 05:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-07-25 Cont ID  
Sent By lmarchan Date 2022-07-25 Time 10:12 Rev Time 0.00
Received By lmarchan Date 2022-07-08 Time 08:25 Sent To  
Notes
2022-07-25 10:12:25NO FEES DUE FOR THIS PERMIT. LEM
2022-07-08 08:26:2507/08/20022 EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-10-19 Cont ID  
Sent By rmcphers Date 2021-10-19 Time 14:18 Rev Time 0.00
Received By rmcphers Date 2021-10-19 Time 14:16 Sent To  
Notes
2021-10-19 14:18:21CHANGE OF OCCUPANCY CLASSIFICATION-
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-06-28 Cont ID  
Sent By medwards Date 2022-06-28 Time 17:07 Rev Time 0.00
Received By medwards Date 2022-06-28 Time 17:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 05:54 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 05:54 Sent To  
Notes
2022-05-27 05:57:05IT APPEARS THAT AHU-1 IS TAKING THE RETURN AIR FROM THE
 MEN'S RESTROOM. YOU CANNOT TAKE RETURN AIR FROM A
 BATHROOM. FMC 601.5-7
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-03-17 Cont ID  
Sent By medwards Date 2022-03-17 Time 08:41 Rev Time 0.00
Received By medwards Date 2022-03-17 Time 08:41 Sent To  
Notes
2022-03-17 08:42:092ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21090432
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW ON THE EQUIPMENT DRAWING WHERE THE GRAIN
 IS STORED IN THIS FACTORY AND WHERE IT IS MILLED?
  
 2) PLEASE ADD A NOTE TO THE DRAWINGS STATING THAT THE
 CHILLER WILL ALSO NEED TO HAVE A SEPARATE PERMIT.
  
 3) THE NAME OF THE CLIENT IS DIXIE GRILL AND BREWERY,
 IS THERE GOING TO BE FOOD SERVED AT THIS ESTABLISHMENT?
 IF SO, PLEASE SHOW THE COOKING EQUIPMENT ALONG WITH THE
 KITCHEN.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-09-23 Cont ID  
Sent By medwards Date 2021-09-23 Time 13:45 Rev Time 0.00
Received By medwards Date 2021-09-23 Time 13:45 Sent To  
Notes
2021-09-23 13:46:081ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090432
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE TENANT ADDRESS ON THE ENERGY
 CALCULATIONS.
  
 2) PLEASE ADD A NOTE ON THE DRAWINGS STATING THAT THE
 REFRIGERATION SYSTEM WILL REQUIRE A SEPARATE PERMIT
 APPLICATION, SUBMITTAL AND REVIEW AS IT WILL NOTE BE
 REVIEWED UNDER THIS PERMIT.
  
 3) SHEET M2.1: THE BATHROOM EXHAUST FANS, EF-1, MUST BE
 RATED AT 70 CFM EACH UNLESS THEY ARE DESIGNED TO
 OPERATE CONTINUOUSLY WHILE THE BUILDING IS OCCUPIED.
 FBC M TABLE 403.3.1.1 FOOTNOTE E.
  
 4) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS ACCORDING TO
 FBC M 403.3.1.1 AND TABLE 403.3.1.1 FOR EACH SPACE.
 PLEASE LABEL THE SPACE ACCORDING TO THE OCCUPANCY
 CLASSIFICATION YOU USE FROM TABLE 403.3.1.1.
  
 FBC M 403.3.1.1: THE OCCUPANT LOAD UTILIZED FOR DESIGN
 OF THE VENTILATION SYSTEM SHALL BE NOT LESS THAN THE
 NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM OCCUPANT
 LOAD RATE INDICATED IN TABLE 403.3.1.1. VENTILATION
 RATES FOR OCCUPANCIES NOT REPRESENTED IN TABLE
 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY
 CLASSIFICATION THAT IS MOST SIMILAR IN TERMS OF
 OCCUPANT DENSITY, ACTIVITIES AND BUILDING CONSTRUCTION;
 OR SHALL BE DETERMINED BY AN APPROVED ENGINEERING
 ANALYSIS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-03-17 Cont ID  
Sent By jesmith Date 2022-03-17 Time 11:52 Rev Time 0.00
Received By jesmith Date 2022-03-17 Time 10:08 Sent To  
Notes
2022-03-17 11:52:4121090432 5107 S DIXIE HWY
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO: HORIZONTAL PLUMBING PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FPC CODE TABLE 308.5. SEE DETAIL;
 P-4.2.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-01 Cont ID  
Sent By pvalenti Date 2021-10-01 Time 06:06 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:35 Sent To  
Notes
2021-10-01 06:07:28CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090432 5107 S DIXIE HWY
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.SEE A-150 DEMO PLAN, NOTE 11. PLEASE CLARIFY. WHAT IS
 MEANT BY CIRCULATION? IS THE CONCRETE BLOCKING BEING
 REMOVED TO PROVIDE A CIRCULATION PATH WHICH WOULD ALLOW
 PATRONS AND EMPLOYEES, TO FREELY MOVE FROM ONE SIDE OF
 THE WALL TO THE OTHER? PER WPB FBC 107.2.1, PROVIDE
 DIMENSIONED DETAIL OF OPENINGS AND SHOW THE ACCESSIBLE
 ROUTE/CIRCULATION PATH FROM THE SEATING AREA ADJACENT
 TO KITCHEN AREA TO THE ACCESSIBLE RESTROOMS. SHOW
 COMPLIANCE WITH FBC ACC SECTION 206 AND FBC PL 403.3.1.
  
 2.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION PER
 FBC ACC 604.4.
  
 3.PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP (NOT
 THE CENTER) OF THE GRIPPING SURFACE
  
 4.MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE LAVATORIES
 OR COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE 35 INCHES (890 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 5.PER WPB FBC 107.2.1, PROVIDE A NOTE STATING ?DRINKING
 WATER SHALL BE PROVIDED IN A FLAT BOTTOM CONTAINER FREE
 OF CHARGE AS ALLOWED BY FBC PL 410.4? OR PROVIDE A
 DRINKING FOUNTAIN THAT COMPLIES WITH FBC PL 410.3, FBC
 ACC 307 AND FBC 602.
  
 6.PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR GAS
 TANKLESS WATER HEATER. THE INSTALLATION MANUAL SHALL BE
 ONSITE AT THE TIME OF INSPECTION.
  
 7.PER WPB FBC 107.2.1, SPECIFY THE PRESSURE RELIEF
 VALVE ON THE HOT WATER PIPING OUT OF THE TANKLESS WATER
 HEATER OR REQUIRE FURNISHING OF NAVIEN OPTION (INCLUDE
 PART NUMBER) FOR RELIEF VALVE IN THE WATER HEATER
 DETAIL NOTES.
 ?6.A) PER WPB FBC 107.2.1 PROVIDE SIZE, ROUTING AND
 TERMINATION POINT OF THE WATER HEATER RELIEF VALVES
 DISCHARGE PIPING. COMPLY WITH FBC PL 504.6.1 THROUGH
 504.6.14. PLEASE NOTE, THE PIPING MAY NOT DISCHARGE TO
 THE MOP SINK PER FBC PL 504.6.5.
  
 8.A-601 SHOWS A CONCRETE SLAB REPAIR DETAIL; P-4.1
 SHOWS A TRAP PRIMER DETAIL WITH WHAT APPEARS TO BE
 WOODEN JOIST SYSTEM. PER WPB FBC 107.2.1, PLEASE
 CLARIFY.
  
 9.PER WPB FBC 107.2.1, PROVIDE DETAIL SHOWING HOW
 RESEAL WATER FOR MULTIPLE FLOOR DRAIN TRAPS FROM ONE
 DEVICE WILL BE PROPERLY DISTRIBUTED TO ALLOW EACH TRAP
 TO BE RESEALED IN ACCORDANCE WITH FBC PL 1002.4.1.3.
  
 10.RE: A-202; PER WPB FBC 107.2.1, PROVIDE ON THE
 FIXTURE/FURNITURE/EQUIPMENT SCHEDULE, ALL APPLICABLE
 PLUMBING WATER & DRAINAGE CONNECTIONS, SIZED, INDICATE
 INDIRECT OR DIRECT DRAIN CONNECTIONS, REQUIRED BACKFLOW
 PREVENTERS (WHERE REQUIRED, SPECIFY TYPE AND MODEL),
 AIR GAPS, PRESSURE REDUCERS (WHERE REQUIRED, SPECIFY
 TYPE AND MODEL)/GAS CONNECTION SIZE AND BTUS/ELECTRICAL
 CHARACTERISTICS. SOME APPEAR TO BE ADDRESSED ON P0.1
 SCHEDULE, OTHERS ARE NOT.
  
 11.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR WATER
 CONNECTION TO F-2 WATER FILTER, F-4 BOIL KETTLE AND
 F-15 MASH LAUDER TUN. INCLUDE REQUIRED BACKFLOW
 PREVENTERS (WHERE REQUIRED, SPECIFY TYPE AND MODEL),
 PRESSURE REDUCERS (WHERE REQUIRED, SPECIFY TYPE AND
 MODEL).
  
 12.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR EMERGENCY
 EYEWASH, INCLUDING MOUNTING HEIGHT AND ANCHORING
 DETAILS. PER WPB FBC SHOW COMPLIANCE WITH FBC ACC
 307.2, PROTRUDING OBJECTS. OBJECTS WITH LEADING EDGES
 MORE THAN 27 INCHES AND NOT MORE THAN 80 INCHES ABOVE
 THE FLOOR SHALL NOT PROTRUDE MORE THAN 4 INCHES
 HORIZONTALLY INTO THE CIRCULATION PATH.
  
 13.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 14. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR SUPPORT OF
 WALL MOUNTED WATER HEATERS
  
 15. PER WPB FBC 107.2.1, PROVIDE DRYWELL DETAIL.
  
 16. PER WPB FBC 107.2.1, PROVIDE REFERENCE SCHEMATIC(S)
 OF GLYCOL AND C02 SYSTEMS. PROVIDE DETAILS FOR MAKE-UP
 WATER IF APPLICABLE.
  
 17.P3.1 SANITARY ISOMETRIC FOR RESTROOMS. PER FBC PL
 914.2, PROVIDE A CIRCUIT VENT CONNECTION DOWNSTREAM OF
 THE MOST UPSTREAM WATER CLOSET NOT DOWNSTREAM OF THE
 UPSTREAM LAVATORY. IN LIEU OF THAT, THE ENTIRE LENGTH
 OF THE VENT SECTION OF THE HORIZONTAL BRANCH DRAIN
 SHALL BE SIZED FOR THE TOTAL DRAINAGE DISCHARGE TO THE
 BRANCH PER 914.3. PLEASE NOTE THAT PER 914.5, FIXTURES,
 OTHER THAN THE CIRCUIT-VENTED FIXTURES, ARE PERMITTED
 TO DISCHARGE TO THE HORIZONTAL BRANCH DRAIN. SUCH
 FIXTURES SHALL BE LOCATED ON THE SAME FLOOR AS THE
 CIRCUIT-VENTED FIXTURES AND SHALL BE EITHER
 INDIVIDUALLY OR COMMON VENTED.
 ?17.A)PER 914.4, PROVIDE A RELIEF VENT DOWNSTREAM OF
 THE LAST TWO WATER CLOSETS ON THE CIRCUIT VENTED
 BRANCH.
  
 18. P3.1 SANITARY ISOMETRIC FOR MOP SINK AND EMERGENCY
 EYEWASH: PER WPB FBC 107.2.1, PROVIDE NOTE STATING ?MOP
 SINK COMMON VENTED BY EYEWASH PER FBC PL 911.3?
  
 19. P3.1 SANITARY ISOMETRIC FOR BREWERY/BAR FLOOR
 DRAINS: PER WPB FBC 107.2.1, PROVIDE NOTE STATING
 ?BREWERY/BAR FLOOR DRAINS AND FLOOR SINKS VENTED BY
 COMBINATION WASTE AND VENT IN ACCORDANCE WITH FBC PL
 SECTION 915.?
  
 20. BREWERY FLOOR DRAINS ARE TRENCH DRAINS. PER WPB FBC
 107.2.1, PROVIDE SPEC AND ADD TO SCHEDULE.
  
 21. IT IS NOTED THAT THE HOT WATER TO THE PUBLIC
 BATHROOMS HAS AN ISOLATION VALVE IN THE LINE. THIS IS A
 RECIRCULATED LINE WHICH WILL NOT FUNCTION IF THE
 ISOLATION VALVE IS CLOSED. PLEASE NOTE THAT THE
 REQUIREMENT FOR A FULL OPEN VALVE AS NOTED IN FBC PL
 606.1(5) IS NOT APPLICABLE AS WPB BUILDING FOLLOWS THE
 INTERPRETATION OF IBC PLUMBING COMMENTARY 606.1(5)
 WHICH STATES A WATER PIPE EXTENDING VERTICALLY THROUGH
 ONE OR MORE FLOORS AND CONVEYING WATER VERTICALLY
 DOWNWARD IS CONSIDERED A DOWN-FEED. VALVES AT THE TOP
 OF DOWN-FEEDS ARE HELPFUL FOR SERVICING MULTI-STORY
 BUILDING SO THAT ONLY SMALL AREAS OF THE BUILDING WILL
 BE WITHOUT WATER TO FACILITATE REPAIRS IN ONE AREA.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090432 5107 S DIXIE HWY
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-06-28 Cont ID  
Sent By medwards Date 2022-06-28 Time 17:07 Rev Time 0.00
Received By medwards Date 2022-06-28 Time 17:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 11:02 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 11:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-15 Cont ID  
Sent By rmcphers Date 2022-03-15 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2022-03-15 Time 14:57 Sent To  
Notes
2022-03-17 11:54:42SIGNATURES FOR PLUMBING AND GAS PLANS ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-19 Cont ID  
Sent By rmcphers Date 2021-10-19 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2021-10-19 Time 14:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By rthermid Date 2021-09-27 Time   Rev Time  
Received By rthermid Date 2021-09-27 Time   Sent To I
Notes
***NONE***