| 2021-09-13 15:07:19 | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1) ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE |
| | REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS |
| | APPLICABLE BELOW PER EACH DOOR/ENTRY/EXIT. |
| | |
| | |
| | 7.2.1.5.6 DOOR HARDWARE RELEASE OF ELECTRICALLY LOCKED |
| | EGRESS |
| | DOOR ASSEMBLIES. DOOR ASSEMBLIES IN THE MEANS OF EGRESS |
| | SHALL BE |
| | PERMITTED TO BE EQUIPPED WITH APPROVED ELECTRICAL |
| | LOCKING SYSTEMS |
| | RELEASED BY THE OPERATION OF DOOR HARDWARE PROVIDED |
| | THAT ALL OF THE FOLLOWING |
| | CONDITIONS ARE MET: |
| | (1) THE HARDWARE FOR EGRESS-SIDE OCCUPANT RELEASE OF |
| | THE ELECTRICAL |
| | LOCK IS AFFIXED TO THE DOOR LEAF. |
| | (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| | THAT IS READILY |
| | OPERATED IN THE DIRECTION OF EGRESS UNDER ALL LIGHTING |
| | CONDITIONS. |
| | (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| | HAND IN THE |
| | DIRECTION OF EGRESS. |
| | (4) OPERATION OF THE HARDWARE DIRECTLY INTERRUPTS THE |
| | POWER SUPPLY TO |
| | THE ELECTRIC LOCK AND UNLOCKS THE DOOR ASSEMBLY IN THE |
| | DIRECTION |
| | OF EGRESS. |
| | (5)* LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| | AUTOMATICALLY ELECTRICALLY |
| | UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| | (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| | ACCORDANCE WITH |
| | ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |