| 2021-11-01 10:01:46 | COMMENTS FOR PERMIT # 21090324 |
| | 1) DRAWING DOES NOT INCLUDE ELECTRICAL LOAD |
| | CALCULATIONS NEC 215.5 |
| | 2) DRAWING DOES NOT DELINEATE GROUNDING |
| | ELECTRODE/CONDUCTOR SYSTEM. |
| | SHOW ALL PRESENT GROUNDING ELECTRODES TO BE BONDED AS |
| | REQUIRED. NEC 250.50 |
| | 3) DRAWING DOES NOT SHOW IF THIS IS AN UNDERGROUND OR |
| | OVERHEAD SERVICE NEC 215.5 |
| | 4) DRAWING DOES NOT SHOW GROUND CONDUCTOR TO INTERIOR |
| | PANEL. NEC 215.5 |
| | 5) DRAWING DOES NOT DETAIL IF SMOKE DETECTORS ARE |
| | EXISTING. SMOKE DETECTORS SHALL BE INSTALLED WHERE |
| | PROVIDED IN THE FLORIDA BUILDING CODE RESIDENTIAL 2020 |
| | R314.2.2 AND FLORIDA BUILDING CODE EXISTING BUILDING |
| | 703.2 |
| | 6) DETAIL ELECTRICAL WIRING POWERING NEW AIR CONDITION |
| | UNITS |
| | 7) INSTALL ELECTRICAL WIRING FOR NEW AIR CONDITIONERS |
| | AS REQUIRED. NEC 430, NEC 210.63AND OTHER APPLICABLE |
| | CODES |
| | 8) PERMIT APPLICATION OMITS WIRING OF NEW AIR |
| | CONDITIONERS. IS THIS IN THE SCOPE OF WORK? |
| | 9) DO THE WIRES FEEDING THE INTERIOR SUBPANEL NEED TO |
| | BE SIZED HIGHER? THESE FEEDERS DO NOT CARRY THE ENTIRE |
| | LOAD AS THERE ARE BRANCH CIRCUIT OCPDS CONTAINED IN THE |
| | METER MAIN. |
| | THE OUTDOOR METER MAIN DOES NOT CONTAIN FEEDER WIRES |
| | ONLY BUS BARS. HOW WOULD YOU APPLY NEC 310.15 (B) (7) |
| | IF IT IS AN UNDERGROUND SERVICE? WOULD WE USE THE |
| | AMPACITY OF THE BUS? |
| | ARE FPL, UNDERGROUND, SERVICE LATERAL, FEEDER |
| | CONDUCTORS, INTO A METER ENCLOSURE, CONSIDERED ?SERVICE |
| | ENTRANCE CONDUCTORS? THEN SHOULD NEC 310.15 (B) (7) |
| | APPLY AND ALLOW SIZING, OF DOWNSTREAM FEEDER CONDUCTORS |
| | ACCORDINGLY. FPL SERVICE LATERAL WIRES COULD HAVE A |
| | LOWER AMPACITY AS WOULD BE REQUIRED FOR OVERHEAD |
| | ENTRANCE CONDUCTORS. |
| | |
| | |
| | MICHAEL PETERSON |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES DEPT. |
| | 561-805-6746 |
| | |