Plan Review Details - Permit 21090295
Plan Review Stops For Permit 21090295
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-30 Cont ID  
Sent By cthroop Date 2021-10-30 Time 11:25 Rev Time 0.00
Received By cthroop Date 2021-10-30 Time 11:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-10-09 Cont ID  
Sent By cthroop Date 2021-10-09 Time 06:32 Rev Time 0.00
Received By cthroop Date 2021-10-08 Time 13:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-28 Cont ID  
Sent By ppetty Date 2021-10-28 Time 10:51 Rev Time 0.00
Received By ppetty Date 2021-10-28 Time 10:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-28 Cont ID  
Sent By ppetty Date 2021-09-28 Time 11:45 Rev Time 0.00
Received By ppetty Date 2021-09-28 Time 11:03 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-10-28 Cont ID  
Sent By amhamilt Date 2021-10-28 Time 11:28 Rev Time 0.00
Received By amhamilt Date 2021-10-28 Time 11:28 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-09-30 Cont ID  
Sent By ajones Date 2021-09-30 Time 15:13 Rev Time 0.00
Received By ajones Date 2021-09-30 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-01 Cont ID  
Sent By lcrespo Date 2021-11-01 Time 08:52 Rev Time 0.00
Received By lcrespo Date 2021-10-25 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-09 Cont ID  
Sent By cthroop Date 2021-10-09 Time 06:33 Rev Time 0.00
Received By cthroop Date 2021-09-09 Time 11:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-01 Cont ID  
Sent By lcrespo Date 2021-11-01 Time 08:59 Rev Time 0.00
Received By lcrespo Date 2021-11-01 Time 08:52 Sent To  
Notes
2021-11-01 09:00:2211/01/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING/POOL)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By lcrespo Date 2021-09-20 Time 08:08 Rev Time 0.00
Received By lcrespo Date 2021-09-20 Time 07:58 Sent To  
Notes
2021-09-20 08:08:5909/20/21 1ST POOL PLUMBING REVIEW**DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD
 CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW COMPONENTS. IT
 REQUIRES THAT THE MAXIMUM SYSTEM FLOW RATE DOES NOT
 EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION
 OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH
 CALCULATIONS MUST INCLUDE ALL THE SYSTEM COMPONENTS,
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP PER THE ANSI/APSP/ICC 7 - 2015 SECS.
 4.4.9, 4.4.9.1 MAXIMUM SYSTEM FLOW RATE?UNSECURED
 CONTROL SYSTEMS.
  
 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR
 THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 3. WOULD YOU PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAIN, THE PUMP, FILTER AND
 CHLORINATOR PER THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. ON SHEET 3.0 UNDER PLUMBING NOTES NUMBER SIX IT
 REFERS TO THE 2017 FBC P. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-30 Cont ID  
Sent By cthroop Date 2021-10-30 Time 11:25 Rev Time 0.00
Received By cthroop Date 2021-10-30 Time 11:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-09 Cont ID  
Sent By cthroop Date 2021-10-09 Time 06:32 Rev Time 0.00
Received By cthroop Date 2021-10-08 Time 13:46 Sent To  
Notes
2021-10-09 06:33:30SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-10-28 Cont ID  
Sent By amhamilt Date 2021-10-28 Time 11:30 Rev Time 0.00
Received By amhamilt Date 2021-10-28 Time 11:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By rthermid Date 2021-09-27 Time   Rev Time  
Received By rthermid Date 2021-09-27 Time   Sent To I
Notes
***NONE***