Plan Review Details - Permit 21090259
Plan Review Stops For Permit 21090259
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By cthroop Date 2022-05-26 Time 15:57 Rev Time 0.00
Received By cthroop Date 2022-05-26 Time 15:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By cthroop Date 2021-11-15 Time 13:24 Rev Time 0.00
Received By cthroop Date 2021-11-15 Time 07:43 Sent To  
Notes
2021-11-15 13:31:10BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: A SEPERATE ROOFING PERMIT IS REQUIRED. SEE
 PROVISO PAGE A-2.
  
 1. DEMENSIONS ARE MISSING FORM FLOOR PLANS ON PAGE A-2.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER WIND
 PRESSURE CALCULATIONS FOR ZONES 1, 2 AND 3 ON PAGE S-2.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 3. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND EXT DOORS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 DEFERRAL OPTION:
  
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX. DO NOT
 E-MAIL DOCUMENTS TO THE PLANS EXAMINER.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-04 Cont ID  
Sent By mpeterso Date 2022-05-04 Time 14:15 Rev Time 0.00
Received By mpeterso Date 2022-05-04 Time 14:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-18 Cont ID  
Sent By jleahy Date 2021-10-18 Time 15:57 Rev Time 0.00
Received By jleahy Date 2021-10-18 Time 15:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-06-14 Cont ID  
Sent By ccole Date 2022-06-14 Time 11:29 Rev Time 0.00
Received By ccole Date 2022-06-14 Time 11:10 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-06-02 Cont ID  
Sent By ccole Date 2022-06-02 Time 17:05 Rev Time 0.00
Received By ccole Date 2022-06-02 Time 16:44 Sent To  
Notes
2022-06-02 17:07:433RD REVIEW FBC-2020 RES. GAS
 PERMIT- 21090259
 6/2/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #3 FROM THE 1ST
 AND 2ND REVIEWS COPIED BELOW WAS NOT ADDRESSED. PLEASE
 COMPLY.
  
 3) FAILED. P2: PROVIDE COMBUSTION AIR CALCULATIONS AND
 INDICATE HOW THE AIR WILL BE PROVIDED- SECTION G2407.1
 FBC RES. PLEASE NOTE IF USING INDOOR COMBUSTION AIR FOR
 THE 160000 BTU RANGE, THE MINIMUM REQUIRED VOLUME SHALL
 BE 50 CUBIC FEET PER 1,000 BTU/H OF THE APPLIANCE INPUT
 RATING- 8000 CU.FT. REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-04-20 Cont ID  
Sent By ccole Date 2022-04-20 Time 14:24 Rev Time 0.00
Received By ccole Date 2022-04-20 Time 12:45 Sent To  
Notes
2022-04-20 14:51:562ND REVIEW FBC-2020 RES. GAS
 PERMIT- 21090259
 4/20/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #3 FROM THE 1ST
 REVIEW COPIED BELOW WAS NOT ADDRESSED. PLEASE COMPLY.
  
 3) P2: PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE
 HOW THE AIR WILL BE PROVIDED- SECTION G2407.1 FBC RES.
  
 NEW COMMENT
  
 1) THE RISER INDICATES THE RANGE AT 166,000 BTU BUT THE
 PLAN INDICATES 120,000 BTU. PLEASE CORRECT- SEC.
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By ccole Date 2021-10-06 Time 15:56 Rev Time 0.00
Received By ccole Date 2021-10-06 Time 14:36 Sent To  
Notes
2021-10-06 15:57:221ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21090259
 10/6/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE NEW TANKLESS WATER HEATER-
 SECTION G2448.1 FBC RES.
  
 2) P2: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER IN COMPLIANCE WITH TABLE C404.2 FBC EC.
  
 3) P2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW RANGE
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 G2447.1 FBC RES. PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 G2407.1 FBC RES.
  
 4) P2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW DRYER
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 G2447.1 FBC RES. INDICATE HOW MAKEUP AIR WILL BE
 PROVIDED IN ACCORDANCE WITH G2407.1 & G2439.5 FBC RES.
  
 5) P2: LIST THE MAKES AND MODELS OF REGULATORS TO BE
 INSTALLED ON THE SYSTEM AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS MARKED UP TO SHOW THE SELECTED MODELS,
 AND INPUT AND OUT PIPE SIZES AND PRESSURES- SECTION
 G2421.2 FBC RES. PLEASE REVIEW APPLIANCE MANUFACTURER?S
 SPECIFICATIONS FOR REQUIRED GAS INPUT PRESSURES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By amhamilt Date 2022-05-10 Time 14:56 Rev Time 0.00
Received By amhamilt Date 2022-05-10 Time 14:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By amhamilt Date 2021-10-25 Time 11:39 Rev Time 0.00
Received By amhamilt Date 2021-10-25 Time 11:39 Sent To  
Notes
2021-10-25 11:41:11THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 THE PROPERTY IS IN A HISTORIC DISTRICT AND ANY EXTERIOR
 MODIFICATIONS OR ADDITIONS REQUIRE APPROVAL FROM THE
 HISTORIC PRESERVATION DIVISION. PLEASE EMAIL
 [email protected] FOR A CERTIFICATE OF APPROPRIATENESS
 APPLICATION.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 561.822.1428
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-21 Cont ID  
Sent By medwards Date 2022-06-21 Time 15:03 Rev Time 0.00
Received By medwards Date 2022-06-13 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-06-02 Time   Rev Time 0.00
Received By lmarchan Date 2022-05-31 Time 13:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-26 Cont ID  
Sent By cthroop Date 2022-05-26 Time 15:57 Rev Time 0.00
Received By cthroop Date 2022-04-14 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-15 Cont ID  
Sent By cthroop Date 2021-11-15 Time 13:25 Rev Time 0.00
Received By cthroop Date 2021-09-20 Time 16:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By lmarchan Date 2022-06-27 Time 16:47 Rev Time 0.00
Received By lmarchan Date 2022-06-23 Time 09:20 Sent To  
Notes
2022-06-27 16:47:19RECEIPT MU-2022-29367 - $0.00 NO FEES DUE. LEM
2022-06-23 09:21:026/23/22 EMAILED IMPACT FOR REVIEW-AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By cthroop Date 2021-11-15 Time 08:27 Rev Time 0.00
Received By cthroop Date 2021-11-15 Time 08:26 Sent To  
Notes
2021-11-15 08:27:49IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-06-21 Cont ID  
Sent By medwards Date 2022-06-21 Time 15:03 Rev Time 0.00
Received By medwards Date 2022-06-21 Time 15:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By medwards Date 2022-04-26 Time 16:16 Rev Time 0.00
Received By medwards Date 2022-04-26 Time 16:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By medwards Date 2021-09-27 Time 16:50 Rev Time 0.00
Received By medwards Date 2021-09-27 Time 16:50 Sent To  
Notes
2021-09-27 16:51:56APPROVED WITH PROVISO:
  
 THE POWDER ROOM MUST ALSO HAVE A BATH EXHAUST FAN
 DUCTED TO THE OUTDOORS. FBC RES R303.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-06-14 Cont ID  
Sent By ccole Date 2022-06-14 Time 11:29 Rev Time 0.00
Received By ccole Date 2022-06-14 Time 11:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-06-02 Cont ID  
Sent By ccole Date 2022-06-02 Time 17:07 Rev Time 0.00
Received By ccole Date 2022-06-02 Time 16:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-20 Cont ID  
Sent By ccole Date 2022-04-20 Time 14:24 Rev Time 0.00
Received By ccole Date 2022-04-20 Time 12:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By ccole Date 2021-10-06 Time 14:35 Rev Time 0.00
Received By ccole Date 2021-10-06 Time 14:22 Sent To  
Notes
2021-10-06 14:36:191ST REVIEW FBC-2020 RES.
 PERMIT- 21090259
 10/6/2021
  
 CODES IN EFFECT:
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: PROVIDE A SANITARY DRAINAGE AND VENT
 ISOMETRIC DRAWING- SECTION 107.3.5.3 WPB.
  
 2) P1: PROVIDE HOT WATER PIPE SPECIFICATIONS- TABLE
 C403.2.10 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-11-15 Cont ID  
Sent By cthroop Date 2021-11-15 Time 08:52 Rev Time 0.00
Received By cthroop Date 2021-11-15 Time 07:43 Sent To  
Notes
2021-11-15 08:52:59ROOFING PROVISO ON PAGE A-2: A SEPERATE ROOFING PERMIT
 IS REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-21 Cont ID  
Sent By medwards Date 2022-06-21 Time 15:03 Rev Time 0.00
Received By medwards Date 2022-06-21 Time 15:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-26 Cont ID  
Sent By cthroop Date 2022-05-26 Time 15:57 Rev Time 0.00
Received By cthroop Date 2022-05-26 Time 15:07 Sent To  
Notes
2022-04-26 16:18:39DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-26 Cont ID  
Sent By mpeterso Date 2021-10-26 Time 11:55 Rev Time 0.00
Received By mpeterso Date 2021-10-26 Time 11:55 Sent To  
Notes
2021-10-26 12:00:11REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED

Review Stop Z ZONING
Rev No 2 Status P Date 2022-05-10 Cont ID  
Sent By amhamilt Date 2022-05-10 Time 14:49 Rev Time 0.00
Received By amhamilt Date 2022-05-10 Time 14:49 Sent To  
Notes
2022-05-10 14:57:34DRIVEWAY TO BE APPROVED UNDER SEPARATE PERMIT
  
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By amhamilt Date 2021-10-27 Time 16:38 Rev Time 0.00
Received By amhamilt Date 2021-10-27 Time 16:38 Sent To  
Notes
2021-10-27 16:38:56THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S):
  
 SEE HISTORIC NOTES
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 561.822.1428
 [email protected]
  