| 2021-10-29 12:56:19 | 10/29/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE NOW, |
| | AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET G-0, THERE IS A LIST OF DRAWINGS MISSING; |
| | L-S1, A3-103, AND S, M, E, P ARE NOT LISTED. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 2. ON SHEET G-1; |
| | |
| | A. UNDER CODES STANDARDS, THERE IS NO SAFE HARBOR |
| | MENTIONED FOR FHA. ARE YOU USING THE DESIGN MANUAL OR |
| | THE GUIDELINES? WOULD YOU PLEASE CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE PROVIDE THE EDITION USED IN THE |
| | 2020 CODES MENTIONED PER THE WPB AMENDMENTS TO FBC |
| | 102.3 APPLICATION OF REFERENCES. |
| | |
| | 3. ON SHEET G-2; |
| | |
| | A. UNDER GOVERNING CODES, THERE IS NO SAFE HARBOR |
| | MENTIONED FOR FHA. ARE YOU USING THE DESIGN MANUAL OR |
| | THE GUIDELINES? WOULD YOU PLEASE CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | B. WOULD YOU PLEASE PROVIDE THE EDITION USED IN THE |
| | GOVERNING CODES MENTIONED PER THE WPB AMENDMENTS TO FBC |
| | 102.3 APPLICATION OF REFERENCES. |
| | |
| | 4. ON SHEET LS-01; |
| | |
| | A. WOULD YOU PLEASE PROVIDE THE TABLE USED AND THE |
| | NUMBER OF OCCUPANTS IN THE PLUMBING FIXTURE COUNT FOR |
| | THE LOBBY, RETAIL AREA, AND COMMERCIAL SPACE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 5. ON SHEET A1-1.02; |
| | |
| | A. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA, |
| | EITHER A OR B WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 6. ON SHEET A1-1.03; |
| | |
| | A. WOULD YOU PLEASE PROVIDE THE TABLE USED FOR THE |
| | STORMWATER PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE CORRECT THE SCUPPER DETAIL NOTE; IT |
| | SAYS A6 BUT IS A7-107 DETAIL 10. |
| | |
| | C. WOULD YOU PLEASE PROVIDE THE SQUARE FOOTAGE BEING |
| | DRAINED TO DETERMINE THE GPM AND SHOW THE SIZE OF THE |
| | ROOF DRAIN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 7. ON SHEET A1-201; |
| | |
| | A. PLAN NOTES SAY REFER TO SHEET A0-0.00 AND NO SUCH |
| | PAGE. WOULD YOU PLEASE PROVIDE THE CORRECT PAGE NUMBER |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? THIS IS A |
| | TYPICAL COMMENT FOR OTHER PAGES |
| | |
| | B. GENERAL NOTES REFERS TO THE CITY OF MIAMI BEACH. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 8. ON SHEET A1-301, 302, AND 303; |
| | |
| | A. PLAN NOTES SAY REFER TO SHEET A0-0.00 AND NO SUCH |
| | PAGE. WOULD YOU PLEASE PROVIDE THE CORRECT PAGE NUMBER |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. GENERAL NOTES REFERS TO THE CITY OF MIAMI BEACH. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA, |
| | EITHER A OR B WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | FHA ON THE SINK, IN FRONT OF THE REFRIGERATOR, TUB, |
| | LAV, AND TOILET. WOULD YOU PLEASE SHOW PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | 9. ON SHEET A4-102; |
| | |
| | A. THE ELEVATOR SHOWS A PIT, AND IN THE PIT, WILL THERE |
| | BE A PUMP TO PUMP OUT WATER? IF SO, WOULD YOU PLEASE |
| | PROVIDE DETAIL THAT HAS A PUMP DETAIL AND SHOW AN |
| | INDIRECT WASTE ON FLAT AND ISOMETRIC DRAWINGS? WOULD |
| | YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 10. ON SHEET A4.103; |
| | |
| | A. IN SOME APPLICATIONS OF A TRASH SHOOT, THERE IS A |
| | SANITIZING DISPENSER ON THE TOP FLOOR. IF ONE WILL BE |
| | PROVIDED WOULD YOU, PLEASE SHOW A DETAIL ALONG WITH |
| | SHUTOFF AND AN ATMOSPHERIC VACUUM BREAKER THAT COMPLIES |
| | WITH THE 2020 FBC P 608.14.6ATMOSPHERIC-TYPE VACUUM |
| | BREAKERS. |
| | |
| | B. IT MOTIONS A HOSE BIBB IN THE GENERAL NOTES. WOULD |
| | YOU PLEASE SHOW THE ISOMETRIC AND THE LOCATION AND GIVE |
| | THE DETAILED SECTION SHEET PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | 11. ON SHEET A1-501; |
| | |
| | A. WOULD YOU PLEASE LABEL THE UNIT TYPE THAT ARE FHA, |
| | EITHER A OR B PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE |
| | FHA ON THE SINK, IN FRONT OF THE REFRIGERATOR, TUB, |
| | LAV, AND TOILET PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | E. THE FAIR HOUSING ACT PROVIDES TWO SETS OF |
| | SPECIFICATIONS TO DESIGN BATHROOMS THAT ARE USABLE BY |
| | PEOPLE WITH DISABILITIES. THOUGH THERE ARE OTHER |
| | DIFFERENCES, SPECIFICATION B BATHROOMS OFFER GREATER |
| | ACCESS TO THE TUB THAN SPECIFICATION A BATHROOMS. |
| | |
| | IF THE SPECIFICATION A DESIGN IS SELECTED, ALL |
| | BATHROOMS IN THE UNIT MUST COMPLY WITH THE |
| | SPECIFICATION A STANDARD (SECTION 7.14). THIS INCLUDES |
| | ACCESS TO ALL FIXTURES IN EACH SPECIFICATION A BATHROOM |
| | (E.G., TWO LAVATORIES IN ONE BATHROOM WOULD BOTH NEED |
| | TO MEET FHA REGULATIONS). |
| | |
| | IF THE SPECIFICATION B DESIGN IS SELECTED, ONLY ONE |
| | BATHROOM IN THE UNIT, AND ONLY ONE OF EACH TYPE OF |
| | FIXTURE WITHIN THE BATHROOM, MUST COMPLY WITH |
| | SPECIFICATION B STANDARDS (SECTION 7.15). ALL OTHER |
| | BATHROOMS IN THE UNIT MUST MEET THE USABLE BATHROOM |
| | REQUIREMENTS (SECTION 7.11), EXEMPTING MANEUVERING |
| | CLEARANCES, AND CLEAR FLOOR SPACE REQUIREMENTS AT |
| | FIXTURES. THE TOP FIXTURE RIM IS A MAXIMUM OF 34 INCHES |
| | AFF, WITH THE APRON AT LEAST 27 INCHES AFF. IN |
| | INSTANCES WHERE REMOVABLE CABINETRY IS PROVIDED, PIPES |
| | ARE COVERED FOR PROTECTION; INSULATION AROUND PIPES, OR |
| | ADDING A FIXED, ONE-PIECE PROTECTION PANEL. |
| | |
| | F. FOR ALL BATHROOM DIMENSIONS OF THE FIXTURES SHALL |
| | COMPLY WITH THE 2020 FBC SEC. P 405.3.1 WATER CLOSETS |
| | AND LAVATORIES. THE FHA HAS SOME DIMENSIONS THAT MAY BE |
| | DIFFERENT. SHOW THE DEPTH OF THE NEW VANITY. THE VANITY |
| | SHALL BE A MAXIMUM OF 24 INCHES DEEP PER THE FAIR |
| | HOUSING ACT. ADDITIONAL REINFORCEMENT MAY BE REQUIRED |
| | IN THE WALLS AROUND THE TUB TO ALLOW FOR THE FUTURE |
| | INSTALLATION OF GRAB BARS PER THE FAIR HOUSING ACT. |
| | |
| | G. SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE TUB OR |
| | SHOWER IN ACCORDANCE WITH THE FAIR HOUSING ACT. |
| | |
| | 12. ON SHEET A5-1.02; |
| | |
| | A. UNDER NOTE, IT REFERS TO THE FBC 2014 R 307.2, WHICH |
| | IS THE WRONG CODE YEAR, AND OTHER COMMENTS ABOUT THE |
| | SHOWER THAT HAS NOTHING TO DO WITH THIS DRAWING. WOULD |
| | YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | B. UNDER INTERIOR FISHES, THERE ARE SHOWER GLASS |
| | COMMENTS THAT DON'T PERTAIN TO THIS DRAWING. WOULD YOU |
| | PLEASE REMOVE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. THESE RESTROOMS ARE TO COMPLY WITH THE 2020 FBC |
| | ACCESSIBILITY CODE. PLEASE PROVIDE THIS INFORMATION ON |
| | THIS PAGE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | D. WOULD YOU PLEASE GIVE DIMENSIONS FOR FIXTURE |
| | CLEARANCES PER FLORIDA BUILDING CODE AND FLORIDA |
| | ACCESSIBILITY CODE FOR TOILET AND LAV. |
| | |
| | E. PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| | DIMENSIONS FOR THE LAVATORY PER THE 2020 FBC ACC SEC. |
| | 606.2 CLEAR FLOOR SPACE. THE LAV NEEDS TO SHOW THE |
| | DIMENSIONS OF THE CLEAR FLOOR SPACE OF 30? X 48? PER |
| | THE 2020 FBC SEC. ACC 305.3. |
| | |
| | F. THE BOTTOM ON THE LAV SHALL BE A MINIMUM OF 27" KNEE |
| | CLEARANCE PER THE 2020 FBC SEC. 306.3. |
| | |
| | G. WOULD YOU PLEASE SHOW THE WATER CLOSET FLUSH CONTROL |
| | LOCATION PER THE 2020 FBC SEC. 604.6 FLUSH CONTROLS. |
| | |
| | H. WOULD YOU PLEASE SHOW THE FLUSH CONTROLS SHALL BE |
| | LOCATED ON THE OPEN SIDE OF THE WATER CLOSET PER THE |
| | 2020 ACC SEC. 604.6 FLUSH CONTROLS. |
| | |
| | J. THE WATER CLOSET IN THE ACCESSIBLE RESTROOM SHALL BE |
| | TO THE CENTERLINE OF THE WATER CLOSET 16 INCHES MINIMUM |
| | TO 18 INCHES MAXIMUM FROM THE SIDE WALL PER THE 2020 |
| | FBC ACC. SEC. 604.2 LOCATION. |
| | |
| | K. THE GRAB BARS ARE NOT SHOWN. WOULD YOU PLEASE SHOW |
| | THEM MEASURED TO THE TOP OF THE GRIPPING SURFACE PER |
| | THE 2020 FBC ACC SEC. 609.4. |
| | |
| | L. WOULD YOU PLEASE SHOW THE GRAB BARS, WHICH SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION PER THE 2020 FBC ACC |
| | SEC. 609.4. |
| | |
| | L. WOULD YOU PLEASE SHOW THE HORIZONTAL GRAB BARS WHICH |
| | NEED TO BE MEASURED TO THE CENTER OF THE BAR PER THE |
| | 2020 FBC ACC SEC. 604.5.1 SIDE WALL AND 604.5.2 REAR |
| | WALL. |
| | |
| | M. WOULD YOU PLEASE SHOW THE HORIZONTAL GRAB BARS ON |
| | THE REAR TO BE MEASURED TO THE CENTER OF THE WATER |
| | CLOSET TO 12 INCHES TO THE WALL AND 24 INCHES TO THE |
| | OPEN SIDE PER THE 604.5.1 SIDE WALL AND 604.5.2 REAR |
| | WALL. |
| | |
| | N. WOULD YOU PLEASE PROVIDE CABINET DETAIL SHOWING THE |
| | SINK AND OR LAVS HEIGHT OF 34 INCHES MAXIMUM PER THE |
| | 2020 FBC ACC SEC. 606.3. |
| | |
| | O. WOULD YOU PLEASE SHOW THE CLEAR FLOOR SPACE SHALL BE |
| | 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE |
| | SIDEWALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR |
| | FROM THE REAR WALL PER THE 2020 FBC ACC. SEC. 604.3.1. |
| | |
| | P. THE DOORS ARE SWINGING IN THE CLEAR FLOOR SPACE OF |
| | THE LAVS. WOULD YOU PLEASE SHOW THE TURNING SPACE |
| | DIAMETER- SPACE OF 60 INCHES DIAMETER MINIMUM AND |
| | INSIDE OF THAT THE 30 INCHES BY 60 INCHES PER THE 2020 |
| | FBC ACC SEC. 304.3. YOU CAN ALSO HAVE THE DOOR SWING |
| | OUT AND NOT SHOW THIS. |
| | |
| | Q. WOULD YOU PLEASE SHOW THE TOILET PAPER DISPENSERS |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF |
| | DISPENSER PER THE 2020 FBC ACC SEC. 604.7. |
| | |
| | R. WOULD YOU PLEASE PROVIDE A NOTE OR SHOW THE LAVATORY |
| | WATER SUPPLY AND DRAINPIPES UNDERSIDE THAT SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | S. WOULD YOU PLEASE SHOW THE TOILET SEAT TO BE 17 |
| | INCHES TO 19 INCHES MAXIMUM MEASURED TO THE TOP OF THE |
| | SEAT PER THE 2020 FBC ACC SEC. 604.4 SEATS. |
| | |
| | T. WOULD YOU PLEASE SHOW THE REFLECTIVE PART OF THE |
| | MIRROR NEEDS TO BE THE 40" TO THE REFLECTIVE SIDE PER |
| | THE 2020 FBC ACC SEC. 603.3. |
| | |
| | U. WOULD YOU PLEASE PROVIDE A NOTE THAT THE SEATS OF |
| | WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER 2020 FBC P |
| | 425.3 WATER CLOSET SEATS |
| | |
| | 13. ON SHEET A5-103; |
| | |
| | A. DETAIL ONE SHOWS A U SHAPE, AND A 60-INCH TURNING |
| | CIRCLE IS REQUIRED. WOULD YOU PLEASE AND PER THE FHA |
| | PAGE 7.9. |
| | |
| | 14. ON SHEET A5-104; |
| | |
| | A. THE DETAIL FOR THE GRAB BARS IS NOT REQUIRED AS THEY |
| | DO NOT NEED TO BE INSTALLED FOR COMPLIES, AND ONLY THE |
| | BACKING NEEDS TO BE SHOWN. WOULD YOU PLEASE DELETE TO |
| | PREVENT FIELD CONFUSION PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE SHOW THE WATER CLOSET DIMENSIONS |
| | THAT COMPLY WITH THE DESIGNED BATHROOMS AS PER PAGE |
| | 7.43 OF THE FHA DESIGN MANUAL. |
| | |
| | C. WOULD YOU PLEASE SHOW THE HEIGHT OF THE LAV IN THE |
| | SPECIFICATION TYPE "B" WILL BE THE USE OF 34 INCHES IN |
| | THE BATHROOMS AS PER FHA DESIGN MANUAL PAGE 7.52. |
| | |
| | 15. ON SHEET A7-1.09; |
| | |
| | A. THE FIRE PENETRATIONS FOR CAJ 2392, WL 12, AND WL |
| | 2128 FROM HILTI HAVE VERY LIGHT VERBIAGE. WOULD YOU |
| | PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | 16. ON SHEET P-1.0; |
| | |
| | A. WOULD YOU PLEASE SHOW THE ADA FIXTURES SCHEDULE FOR |
| | THE ACCESSIBLE RESTROOM PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. UNDER PLUMBING FIXTURES FOR COMMENT ONE, IT REFERS |
| | TO MIAMI DADE COUNTY AMENDMENTS. WE HAVE OUR |
| | AMENDMENTS, AND A COPY CAN BE FURNISHED BY CONTACTING |
| | ME IF YOU LIKE. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN THOSE SAME COMMENTS, TWO AND THREE ARE NOT THE |
| | CORRECT CODE REFERENCES, AND WOULD YOU PLEASE GIVE THE |
| | WHOLE YEAR AND EDTION YOU REFER TO PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION? ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. UNDER PLUMBING GENERAL NOTES, NUMBER 16 REFERS TO |
| | STACKS WITH A CLEANOUT AT THE BASE OF STACK OR VENT AND |
| | IN THE NEW CODE CYCLE THAT WAS ELIMINATED. THAT MAY BE |
| | AN RFI IN THE FIELD. THE INSPECTOR MAY ASK TO BE |
| | INSTALLED IN DRAWING, WHICH MOST PLUMBING CONTRACTORS |
| | DO NOT DO ANYMORE. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | E. ON THOSE SAME NOTES FOR NUMBER 19, IT SAYS |
| | UNDERGROUND PIPING TO BE HUNG FROM THE SLAB. YOU MAY |
| | KEEP THAT BUT NOT REQUIRED BY OUR CODE. IF SO, WOULD |
| | YOU PROVIDE DETAIL ON HOW DISTANCE AND MATERIALS ARE |
| | BEING USED PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. ON NUMBER 23, THE ANTI-SCALDING THE 110, I PRESUME, |
| | IS THE TEMPERATURE WHICH IN THE CODE IS 120 PER THE |
| | 2020 FBC SEC. P 412.3INDIVIDUAL SHOWER VALVES. WOULD |
| | YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE FBC |
| | SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | G. WOULD YOU PLEASE PROVIDE DETAIL FOR THE TANKLESS AND |
| | SPECIFICATIONS IN THE UNITS AND THE COMMERCIAL PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 17. ON SHEET P-2.0; |
| | |
| | A. THE WATER ISOMETRIC SHOWS THE WATER FOR BOTH IN ONE |
| | SERVICE LINE FOR HOT WATER AND THE COLD PER THE 2020 |
| | FBC SEC. P 606.1 (6) LOCATION OF FULL-OPEN VALVES. |
| | WOULD YOU SEPARATE THEM AS THEY ARE INDIVIDUAL UNITS, |
| | AND BUILD-OUT MAY CAUSE ISSUES IN THE FUTURE? PLEASE |
| | SHOW ITS OWN WATER SERVICE AND HOT TANKLESS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE SHOW SHUT-OFF VALVES FOR ALL RISERS |
| | WITH ACCESS PANELS IN THE GARAGE AREA PER THE 2020 FBC |
| | SEC? P 606.1 (4) LOCATION OF FULL-OPEN VALVES. |
| | |
| | C. WOULD YOU PLEASE SHOW ON THE ISOMETRIC A TRAP PRIMER |
| | AND ITS SOURCE PER THE 2020 FBC SEC. 1002.4.1 TRAP SEAL |
| | PROTECTION. |
| | |
| | D. WOULD YOU PLEASE SHOW THE CLEANOUT ON THE BUILDING |
| | DRAIN PER THE 2020 FBC SEC. P 708.1.3BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION. |
| | |
| | E. WOULD YOU PLEASE SHOW A BACKFLOW DEVICE NEXT TO THE |
| | METER AND PUT A SEPARATE PERMIT REQUIRED FOR THE |
| | BACKFLOW DEVICE PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 18. ON SHEET P-2.2; |
| | |
| | A. CORRECTION NEEDS TO BE MADE TO THE PLUMBING LAYOUT. |
| | PLEASE REFER TO COMMENT 20 TO MATCH SANITARY RISER PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. WASHING MACHINE VALES SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE UNIT PER THE 2020 FBC SEC. P 606.3. |
| | ACCESSIBLE SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL |
| | OF AN ACCESS PANEL OR SIMILAR REMOVABLE OBSTRUCTION. |
| | |
| | 19. ON SHEET P-3.0; |
| | |
| | A. IN THE GENERAL SANITARY RISER, WOULD YOU PLEASE SHOW |
| | A CLEANOUT ON EACH ENTRANCE TO THE BUILDING (COMMERCIAL |
| | SPACE AND UNITS). THE FOUR-INCH CLEAN-OUT-UP MAY NEED |
| | TO BE MOVED BEFORE THE WYE AND ADD ONE DOWNSTREAM OF |
| | THE WYE PER THE 2020 FBC SEC. 708.1.3BUILDING DRAIN AND |
| | BUILDING SEWER JUNCTION. |
| | |
| | B. IN THE GENERAL WATER RISER, THERE IS ONE METER, BUT |
| | IT GOES UP AND FEEDS TWO UNITS SHOULD THEY BE IN THE |
| | UNITS AND BE TWO INSTEAD OF ONE. WOULD YOU PLEASE |
| | CLARIFY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN THAT SAME RIDER, THE COLD LINE TO THE COMMERCIAL |
| | SPACE IS MISSING A DIMENSION BEFORE IT TEES OFF FROM |
| | THE 1 1/4 LINE. WOULD YOU PLEASE ADD THE SIZE PER THE |
| | WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | D. THERE IS NO ISOMETRIC FOR THE CONDENSATE LINES WITH |
| | A P-TRAP AND UNDER 2020 FBC M307.2.4 AND P1002.1. EACH |
| | TRAP SHALL BE VENTED TO PERMIT THE ADMISSION OR |
| | EMISSION OF AIR SO THAT THE SEAL OF ANY FIXTURE TRAP |
| | SHALL NOT BE SUBJECTED TO A PRESSURE DIFFERENTIAL OF |
| | MORE THAN 1 INCH OF WATER COLUMN PER THE 2020 FBC |
| | SECTION 901.2 TRAP SEAL PROTECTION. THE CONDENSATE LINE |
| | SHOULD SHOW A VENT TERMINATION AND LOCATION, AND THEY |
| | CANNOT TERMINATE IN A WALL AS IT HAS NO NEGATIVE OR |
| | POSITIVE PRESSURE TO HAVE A DIFFERENTIAL OF ONE-INCH |
| | WATER COLUMN. WOULD YOU PLEASE PROVIDE DETAIL OF HOW |
| | THEY WILL BE VENTED PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. IF |
| | TERMINATION IN PLENUM, IT MUST BE CPVC THAT HAS THE |
| | REQUIRED SMOKE INDEX. |
| | |
| | E. CONDENSATE IS NOT PERMITTED TO DISCHARGE INTO THE |
| | CITY'S SANITARY SYSTEM PER CITY ORDINANCE CHAPTER 90, |
| | ARTICLE III, SEC.90-126 (B)(5). THEY SHALL DISPOSE OF |
| | IN A SAFE LOCATION OR A DRY WELL. IF A DRY WELL WILL BE |
| | USED, WOULD YOU PLEASE PROVIDE DETAILS OF THE DRY WELL |
| | FOR THE CONDENSATE LINE PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | E. WOULD YOU PLEASE SHOW STORM LINES ON THE LAYOUT AND |
| | ISOMETRIC WITH ITS SIZE AND LOCATION OF TERMINATION PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | F. HOSE BIBB NOT SHOWN FOR THE TRASH SHOOT, AND IF ANY |
| | OTHER HOSE BIBB IS REQUIRED FOR THE COMMON AREAS, WOULD |
| | YOU PLEASE SHOW A SHUT-OFF VALVE PER THE 2020 FBC SEC. |
| | P 606.2 (2) LOCATION OF SHUTOFF VALVES. |
| | |
| | 20. ON SHEET P-3.01; |
| | |
| | A. ON ALL SANITARY RISERS, THE FIXTURE DRAIN FOR THE |
| | STANDPIPE SERVING AN AUTOMATIC CLOTHES WASHER SHALL |
| | CONNECT TO A 3-INCH OR LARGER DIAMETER FIXTURE BRANCH |
| | OR STACK PER THE 2020 FBC SEC. R 406.2 WASTE |
| | CONNECTION. |
| | |
| | B. IN THE SAME RISERS, BATHROOM GROUPS ( D, C AND E) |
| | HAVE THE TOILET AND THE SHOWER NOT VENTED. THE VENT |
| | NEEDS TO GO BETWEEN THE TOILET AND THE SHOWER OR USE A |
| | DOUBLE WYE PATTERN AS EACH TRAP SHALL BE VENTED PER THE |
| | 2020 FBC SEC. 910.1 INDIVIDUAL VENTS PERMITTED. |
| | |
| | C. THE ISOMETRIC DOES NOT SHOW VALVES TO SHUT OFF EACH |
| | UNIT IN SOME UNIT TYPE WITH THE CONNECTION IS UNCLEAR. |
| | WOULD YOU PLEASE CORRECT PER THE WPB AMENDMENTS TO THE |
| | FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |