Plan Review Details - Permit 21090106
Plan Review Stops For Permit 21090106
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-09-02 Cont ID  
Sent By cpuell Date 2021-09-02 Time 14:41 Rev Time 0.00
Received By cpuell Date 2021-09-02 Time 14:41 Sent To  
Notes
2021-09-02 14:42:162 BLDGS ON PROPERTY WORK CORRECTLY IDENTIFIED ON WEST
 BUILDING WITH THE ADDRESS OF 706 SUNSET RD

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-12-08 Cont ID  
Sent By cthroop Date 2021-12-08 Time 06:53 Rev Time 0.00
Received By cthroop Date 2021-12-06 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-10 Cont ID  
Sent By cthroop Date 2021-11-10 Time 16:46 Rev Time 0.00
Received By cthroop Date 2021-11-10 Time 09:06 Sent To  
Notes
2021-11-10 16:51:40BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY
 APPLIED INSULATION. PRODUCT DATA SHEET SUBMITTED FOR
 REVIEW DOES NOT PROVIDE INSTALLATION INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. PROVIDE COPY OF BOUNDRY LINE SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE PRODUCT APPROVALS FOR WINDOWS AND DOORS.
 PERMIT 18040144 HAS BEEN REVOKED AND DOES NOT APPLY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By cthroop Date 2021-09-30 Time 09:42 Rev Time 0.00
Received By cthroop Date 2021-09-29 Time 13:13 Sent To  
Notes
2021-09-30 10:09:37BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: VALUE HAS BEEN ADJUSTED TO $157,691.00 BASED ON
 THE ICC BUILDING VALUATION DATA.
  
  
 1. PROVIDE A SITE PLAN W/BOUNDRY LINE SURVEY
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE
 SITE,... AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE AND INCLUDED BOUNDARY LINE SURVEY.
  
  
 2. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 3. REF. PLAN PAGES A-3 AND A-5 FOR THE FOLLOWING
 COMMENT:
 ROOF SCUPPER DOWNSPOUT APPREARS TO DISCHARGE BEHIND BBQ
 CABINET. PROVIDE DETAIL SHOWING LOCATION OF DOWNSPOUT
 DISCHARGE AWAY FROM STRUCTURE.
 R318.5PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES, IRRIGATION/SPRINKLER SYSTEM RISERS
 FOR SPRAY HEADS, AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 4. PROVIDE PRODUCT APPROVALS FOR WINDOWS, EXT. DOORS
 AND OHD.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 DEFERRAL OPTION:
 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 5. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY
 APPLIED INSULATION. DESIGNER SHALL SELECT SYSTEM TO BE
 INSTALLED.
 FBC 107.3.4; FAC RULE 9N-3 REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-30 Cont ID  
Sent By cthroop Date 2021-09-30 Time 09:29 Rev Time 0.00
Received By cthroop Date 2021-09-30 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-09-30 Cont ID  
Sent By cthroop Date 2021-09-30 Time 09:29 Rev Time 0.00
Received By cthroop Date 2021-09-30 Time 06:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-11-17 Cont ID  
Sent By ccole Date 2021-11-17 Time 08:41 Rev Time 0.00
Received By ccole Date 2021-11-16 Time 16:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By ccole Date 2021-09-24 Time 11:55 Rev Time 0.00
Received By ccole Date 2021-09-24 Time 08:06 Sent To  
Notes
2021-09-24 11:55:361ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21090106
 9/24/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P3: PLEASE ADD THE LOW PRESSURE GAS PIPING
 SIZING TABLES FOR THE SCHEDULE 40 METALLIC AND THE
 CSST- SECTION G2413.4 FBC RES.
  
 2) P3: THE RISER SHOWS A FLOOR PENETRATION THAT APPEARS
 TO BE IN THE YARD AREA OF THE PROPERTY BASED ON THE
 FLOOR PLAN- PLEASE CORRECT OR CLARIFY WHAT FLOOR IS
 BEING PENETRATED- SECTION 107.2.1 WPB.
  
 3) P3: SHOW GAS TIGHT CAPS AT ALL FUTURE APPLIANCE
 TERMINATIONS- G2415.15 FBC RES.
  
 4) P3: INDICATE THE MAKES AND MODELS OF THE REGULATORS
 AND SUBMIT MARKED UP OR HIGHLIGHTED SPECS SHOWING THE
 SELECTED MODELS, THE INLET AND OUTLET PIPE SIZES AND
 PRESSURES- SECTION G2421.1 & G2421.2 FBC RES.
  
 5) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 RANGE AND PROVIDE COMBUSTION AIR CALCULATIONS- SECTIONS
 G2407.1 & G2447.1 FBC RES.'
  
 6) P3 & P4: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER AND SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL- SECTION G2448.1 FBC RES. PROVIDE
 AN INSTALLATION DETAIL ON THE PLAN INDICATING THE
 REQUIRED CLEARANCES TO BUILDING OPENINGS, GRADE, AND
 OVERHEAD CONSTRUCTION, AND PROVIDE CONDENSATE DISPOSAL
 DETAILS- SECTION G2448.1 FBC RES.
  
 7) P3: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUAL FOR THE BBQ- SECTION G2447.1 FBC
 RES. PLEASE NOTE THAT MANY OF THE MANUFACTURER?S
 INSTALLATION GUIDELINES PROHIBIT INSTALLATION OF A BBQ
 GRILL UNDER OVERHEAD CONSTRUCTION AND HAVE RECOMMENDED
 CLEARANCES TO COMBUSTIBLES ETC. PROVIDE PLAN AND
 ELEVATION VIEWS OF THE GRILL SHOWING ALL REQUIRED
 CLEARANCES IN ACCORDANCE WITH THE MANUFACTURER'S
 GUIDELINES. PLEASE NOTE THAT AN EXHAUST HOOD AND DUCT
 MAY BE REQUIRED PER THE MANUFACTURER- G2447.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2021-12-06 Cont ID  
Sent By fmittner Date 2021-12-06 Time 11:08 Rev Time 0.00
Received By fmittner Date 2021-12-06 Time 11:08 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-10-04 Cont ID  
Sent By fmittner Date 2021-10-04 Time 15:44 Rev Time 0.00
Received By fmittner Date 2021-10-04 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-08 Cont ID  
Sent By cthroop Date 2021-12-08 Time 06:54 Rev Time 0.00
Received By cthroop Date 2021-11-30 Time 10:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-22 Cont ID  
Sent By jgomez Date 2021-11-22 Time 14:19 Rev Time 0.00
Received By jgomez Date 2021-11-08 Time 07:16 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-05 Cont ID  
Sent By lmarchan Date 2021-10-05 Time 10:10 Rev Time 0.00
Received By lmarchan Date 2021-09-02 Time 12:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2021-11-30 Cont ID  
Sent By lmarchan Date 2021-11-30 Time 09:47 Rev Time 0.00
Received By lmarchan Date 2021-11-22 Time 11:06 Sent To  
Notes
2021-11-23 16:00:14RECEIPT MU-2021-055430 - $22.46 PAID
  
2021-11-22 11:06:2611/22/21 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By cthroop Date 2021-09-30 Time 05:58 Rev Time 0.00
Received By cthroop Date 2021-09-30 Time 05:58 Sent To  
Notes
2021-09-30 05:59:23IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-09-03 Cont ID  
Sent By medwards Date 2021-09-03 Time 09:45 Rev Time 0.00
Received By medwards Date 2021-09-03 Time 09:45 Sent To  
Notes
2021-09-03 09:47:25APPROVED WITH PROVOSO:
 PLEASE HAVE THE INSTALLATION INSTRUCTIONS FOR THE
 OUTDOOR BBQ ON SITE AT ROUGH IN INSPECTIONS. THE
 INSTRUCTION MANUAL MAY REQUIRE A HOOD ABOVE THE BBQ.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-16 Cont ID  
Sent By ccole Date 2021-11-16 Time 17:23 Rev Time 0.00
Received By ccole Date 2021-11-16 Time 16:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By ccole Date 2021-09-24 Time 10:33 Rev Time 0.00
Received By ccole Date 2021-09-24 Time 08:06 Sent To  
Notes
2021-09-24 10:34:311ST REVIEW FBC-2020 RES. PLUMING
 PERMIT- 21090106
 9/24/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P2: THE LOCATION OF THE RPZ BACKFLOW PREVENTER IS
 NOT IN COMPLIANCE WITH THE WPB UTILITIES CROSS
 CONNECTION MANUAL. THE DEVICE SHALL BE INSTALLED
 IMMEDIATELY BEYOND THE WATER METER. PLEASE REVISE THE
 PLAN AND NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 INSTALLATION OF THE BACKFLOW PREVENTER.
  
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 2) P-4: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW WATER
 HEATER INDICATING THE MAKE AND MODEL AND EFFICIENCY
 RATING- TABLE C404.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-09-30 Cont ID  
Sent By cthroop Date 2021-09-30 Time 09:36 Rev Time 0.00
Received By cthroop Date 2021-09-29 Time 13:13 Sent To  
Notes
2021-09-30 09:37:17PROVISO ON PLAN PAGE S-6. A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-12-08 Cont ID  
Sent By cthroop Date 2021-12-08 Time 06:53 Rev Time 0.00
Received By cthroop Date 2021-12-06 Time 08:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-22 Cont ID  
Sent By mpeterso Date 2021-11-22 Time 11:11 Rev Time 0.00
Received By mpeterso Date 2021-11-22 Time 11:11 Sent To  
Notes
2021-11-22 11:12:14REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-02 Cont ID  
Sent By rmcphers Date 2021-09-02 Time 13:47 Rev Time 0.00
Received By rmcphers Date 2021-09-02 Time 13:47 Sent To  
Notes
2021-09-02 13:49:50ORIGINAL SIGNED AND SEALED DRAWINGS AND MECHANICAL
 DOCUMENT TO STORAGE

Review Stop Z ZONING
Rev No 2 Status P Date 2021-11-18 Cont ID  
Sent By fmittner Date 2021-11-18 Time 09:34 Rev Time 0.00
Received By fmittner Date 2021-11-18 Time 09:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-10-04 Cont ID  
Sent By awooten Date 2021-10-04 Time 15:44 Rev Time 0.00
Received By fmittner Date 2021-10-04 Time 15:44 Sent To HIST
Notes
***NONE***