Plan Review Details - Permit 21090053
Plan Review Stops For Permit 21090053
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-02-25 Cont ID  
Sent By cpuell Date 2022-02-25 Time 11:15 Rev Time 0.00
Received By cpuell Date 2022-02-25 Time 11:15 Sent To  
Notes
2022-02-25 11:16:08PARCEL 623 AVON RD, 623 AVON RD # 1 MAIN BLDG AND 623
 AVON RD # 2 REAR BLDG

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-02-08 Cont ID  
Sent By cpuell Date 2022-02-08 Time 15:31 Rev Time 0.00
Received By cpuell Date 2022-02-08 Time 15:31 Sent To  
Notes
2022-02-08 15:32:30RESPOSE LETTER STATED THAT THE OWNER HAD CONTACTED
 ADDRESSING BUT THEY HAVE NOT. PLEASE HAVE OWNER CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By cpuell Date 2021-09-30 Time 14:27 Rev Time 0.00
Received By cpuell Date 2021-09-30 Time 14:27 Sent To  
Notes
2021-09-30 14:29:04PLEASE COORDINATE WITH [email protected] FOR THE HABITABLE
 SPACE AKA NEW GUEST COTTAGE, TO BE GIVEN AN ADDRESS.
 ALL ACCESSORY RESIDENTIAL/COMMERCIAL UNITS AND OR OTHER
 HABITABLE STRUCTURES WILL BE ISSUED A UNIQUE SECONDARY
 ADDRESS NUMBER PER CITY'S ADDRESSING POLICY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-11 Cont ID  
Sent By cthroop Date 2022-03-11 Time 13:17 Rev Time 0.00
Received By cthroop Date 2022-03-11 Time 12:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-05 Cont ID  
Sent By cthroop Date 2021-11-05 Time 08:55 Rev Time 0.00
Received By cthroop Date 2021-11-05 Time 06:48 Sent To  
Notes
2021-11-05 09:08:02BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: A SEPERATE PERMIT IS REQUIRED FOR THE
 CABANA/GARAGE STRUCTURE.
  
 1. CORRECT GOVERNING CODES ON PAGE A1 TO 2020FBC 7TH
 ED.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE A COPY OF THE BOUNDRY LINE SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. PROVIDE SETBACK DEMENSIONS TO SITE PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 4. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 5. PLACE EXT. WALL INSULATION TYPE AND R VALUE ON PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 6. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3
 STORIES.
 FBC EC-R101.5.1.1.2 BUILDING THERMAL ENVELOPE
 ALTERNATIVE.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 7. PROVIDE A ROOF FRAMING PLAN.
 7A) .PROVIDE DESIGN PRESSURES FOR NEW ROOFING PER
 FIGURE R301.2(7) COMPONENT AND CLADDING PRESSURE ZONES
 R301.2.1.1WIND DESIGN REQUIRED.
 7B) .PROVIDE ROOF SHEATHING FASTENER SCHEDULE PER
 DESIGN PRESSURES.
 TABLE R301.2.1.2 WINDBORNE DEBRIS PROTECTION FASTENING
 SCHEDULE FOR WOOD STRUCTURAL PANELS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 PLEASE UPLOAD YOUR DOCUMENTS TO PROJECT DOX. DO NOT
 E-MAIL DOCUMENTS TO THE PLANS EXAMINER.
  
 PLAN REVIEW COMMENTS:
 YOU CAN CHECK THE STATUS OF YOUR SUBMITTAL AND VIEW THE
 PLAN REVIEW COMMENTS BY FOLLOWING THE INSTRUCTIONS
 BELOW:
 COPY AND PASTE THE FOLLOWING LINK INTO ANY INTERNET
 BROWSER.
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 OPEN THE ONESTOPSHOP WEB-SITE FOR PERMIT STATUS
  
 ? ENTER IN THE PERMIT NUMBER ? SELECT SEARCH
 ? LEFT CLICK ON PERMIT NUMBER
 ? UNDER PERMIT INFORMATION SELECT PLAN REVIEWS TAB
 ? ANY OPEN REVIEW STOP MEANS THAT REVIEW IS STILL
 PENDING.
 ? CLICK ON THE LATEST REVIEW NAME AND NUMBER TO REVIEW
 COMMENTS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By fgiaquin Date 2022-02-23 Time 19:48 Rev Time 0.00
Received By fgiaquin Date 2022-02-23 Time 18:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-07 Cont ID  
Sent By fgiaquin Date 2021-10-07 Time 21:31 Rev Time 0.00
Received By fgiaquin Date 2021-10-07 Time 20:19 Sent To  
Notes
2021-10-07 20:52:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. MINIMUM GEC SIZE FOR COLD WATER PIPE IS #4 CU NOT
 NUMBER #6. PROVIDE CORRECTION. NEC 250.66
  
 2. 100AMP PANEL FOR COTTAGE DOES NOT SHOW MAIN BREAKER.
 MAIN BREAKER REQUIRED FOR SEPARATE STRUCTURE BECAUSE
 THERE ARE MORE THAN 6 THROWS OF THE HAND. NEC 225.32 &
 225.33
  
 3. SEPARATE PERMIT IS REQUIRED FOR COTTAGE STRUCTURE.
 FBC 105.1
  
 4. NOTE ON PLAN STATES AIC RATING WILL BE SUPPLIED BY
 FINAL INSPECTION. THIS IS NOT PERMITTED. AIC RATING
 WILL BE REQUIRED BEFORE PERMIT ISSUANCE. PROVIDE
 CORRECTION
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 5. A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE DETAILS ON PLAN OF
 GROUNDING ELECTRODE SYSTEM AND WIRING. NEC 250.32; FBC
 RE E3607.3
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-02-23 Cont ID  
Sent By amhamilt Date 2022-02-23 Time 16:03 Rev Time 0.00
Received By amhamilt Date 2022-02-23 Time 16:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 13:18 Rev Time 0.00
Received By medwards Date 2022-03-18 Time 08:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-11 Cont ID  
Sent By cthroop Date 2022-03-11 Time 13:18 Rev Time 0.00
Received By cthroop Date 2022-02-08 Time 07:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-05 Cont ID  
Sent By cthroop Date 2021-11-05 Time 09:08 Rev Time 0.00
Received By cthroop Date 2021-09-13 Time 14:03 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-03-23 Cont ID  
Sent By lmarchan Date 2022-03-23 Time 12:44 Rev Time 0.00
Received By lmarchan Date 2022-03-11 Time 13:29 Sent To  
Notes
2022-03-23 12:44:55RECEIPT MU-20220-012236 - $546.52 PAID
2022-03-11 13:30:303/11/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-11-05 Cont ID  
Sent By cthroop Date 2021-11-05 Time 07:26 Rev Time 0.00
Received By cthroop Date 2021-11-05 Time 07:26 Sent To  
Notes
2021-11-05 07:27:25IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 13:17 Rev Time 0.00
Received By medwards Date 2022-03-28 Time 13:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-17 Cont ID  
Sent By medwards Date 2022-02-17 Time 11:18 Rev Time 0.00
Received By medwards Date 2022-02-17 Time 11:07 Sent To  
Notes
2022-02-17 11:19:321ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090053
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS REVIEW IS FOR THE MAIN HOUSE ONLY. COTTAGE PERMIT
 NUMBER IS 22010888. THE CABANA WOULD BE CONSIDERED A
 HABITABLE SPACE AND MUST BE CONDITIONED. PLEASE SUBMIT
 MECHANICAL DRAWINGS FOR THIS CABANA. THE ELECTRICAL
 SHEET CALLS FOR A MINI SPLIT, IF THIS IS TO BE USED FOR
 THE CABANA PLEASE PROVIDE THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS ALONG WITH THE MECHANICAL DRAWING.
  
 1) THE SQUARE FOOTAGE SUBMITTED FOR THE MAIN HOUSE IN
 THE ENERGY CALCULATIONS AND THE MECHANICAL EQUIPMENT
 SIZING CALCULATIONS DO NOT MATCH. PLEASE CORRECT THIS.
  
 2) PLEASE PROVIDE DUCT SIZES ON DUCTS FROM AHU TO FIRST
 FLOOR AND DUCT FROM AHU TO TRANSFER BOX ABOVE THE
 MASTER BATH. FBC 107.2.1
  
 3) PLEASE PROVIDE A DETAIL OF THE ANCHORING OF THE
 CONDENSING UNIT. FBC RES M1307.2
  
 4) PLEASE SHOW THE CONDENSATE PIPING MATERIAL, SIZE AND
 TERMINATION LOCATION. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-09-23 Cont ID  
Sent By medwards Date 2021-09-23 Time 09:13 Rev Time 0.00
Received By medwards Date 2021-09-23 Time 09:13 Sent To  
Notes
2021-09-23 09:14:051ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090053
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A MECHANICAL DRAWING SHOWING ALL OF
 THE MECHANICAL WORK BEING COMPLETED UNDER THIS PROJECT
 BOTH FOR THE MAIN HOUSE AND THE NEW GUEST COTTAGE. FBC
 107.2.1
  
 2) PLEASE PROVIDE A MECHANICAL EQUIPMENT SIZING
 CALCULATION FOR THE NEW KITCHEN ADDITION AND FOR THE
 NEW GUEST COTTAGE. FBC EC R403.7.1
  
 3) PLEASE PROVIDE THE ENERGY CALCULATIONS FOR THE NEW
 KITCHEN ADDITION AND FOR THE NEW GUEST COTTAGE. FBC EC
 R101.5.1.1.2
  
 4) PLEASE PROVIDE THE CFM?S OF THE NEW KITCHEN HOOD.
 FBC RES M1503.4
  
 5) A SEPARATE PERMIT WILL BE REQUIRED FOR EACH
 STRUCTURE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By ccole Date 2022-02-15 Time 11:32 Rev Time 0.00
Received By ccole Date 2022-02-15 Time 11:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-30 Cont ID  
Sent By ccole Date 2021-09-30 Time 14:19 Rev Time 0.00
Received By ccole Date 2021-09-30 Time 12:31 Sent To  
Notes
2021-09-30 14:19:581ST REVIEW FBC-2020 RES.
 PERMIT- 21090053
 9/30/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET EP-1: BASED ON THE RISER DIAGRAM IT APPEARS
 THAT THE WATER CLOSET IN THE MASTER BATH IS NOT BEING
 VENTED PROPERLY. IF YOU ARE WET VENTING THE FIXTURE,
 THE DRAIN SHALL CONNECT HORIZONTALLY TO THE BRANCH
 DRAIN IN THE DIRECTION OF FLOW- SECTION P3108.1 FBC
 RES.
  
 2) EP-1: IT APPEARS THE WASHING MACHINE ON THE 2ND
 FLOOR IS PART OF A STACKABLE WASHER/DRYER COMBO UNIT.
 PLEASE SHOW THE LOCATIONS OF THE SHUT OFF VALVES FOR
 THE WASHING MACHINE TO VERIFY THEY WILL IN AN
 ACCESSIBLE LOCATION- P2903.9.3 FBC RES.
  
 3) EP-1: PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED
 FOR THE NEW GUEST COTTAGE- A COMPLETE REVIEW OF THE
 PLUMBING AT THE COTTAGE WILL NOT BE REVIEWED AT THIS
 TIME. PLEASE NOTE HOWEVER THAT THE CURRENT RISER
 DRAWING SHOWS A NON-COMPLIANT WET VENT FOR THE COTTAGE
 FIXTURE DRAINS- NOT MORE THAN ONE WET VENTED FIXTURE
 SHALL DISCHARGE UPSTREAM OF THE DRY VENTED FIXTURE
 DRAIN CONNECTION.
  
 4) EP-1: IN ACCORDANCE WITH SECTION 7C OF THE WPB
 UTILITIES MANUAL FOR CROSS-CONNECTION CONTROL A
 BACKFLOW ASSEMBLY SHALL BE INSTALLED ON THE POTABLE
 WATER SERVICE TO THE MULTI- FAMILY PROPERTY.
 PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-11-05 Cont ID  
Sent By cthroop Date 2021-11-05 Time 08:53 Rev Time 0.00
Received By cthroop Date 2021-11-05 Time 06:48 Sent To  
Notes
2021-11-05 08:53:59PROVISO ON PLAN PAGE A5: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-28 Cont ID  
Sent By medwards Date 2022-03-28 Time 13:17 Rev Time 0.00
Received By medwards Date 2022-03-28 Time 13:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-11 Cont ID  
Sent By cthroop Date 2022-03-11 Time 13:17 Rev Time 0.00
Received By cthroop Date 2022-03-11 Time 12:23 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-21 Cont ID  
Sent By mpeterso Date 2021-10-21 Time 13:24 Rev Time 0.00
Received By mpeterso Date 2021-10-21 Time 13:24 Sent To  
Notes
2021-10-21 13:27:44SIGNATURE REVIEW APPROVED WITH DIGITAL SIGNATES AND
 SEALS

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By llouie Date 2022-02-16 Time   Rev Time 0.00
Received By llouie Date 2022-02-15 Time   Sent To  
Notes
2022-02-16 10:08:19* FOR INTERIOR IMPROVEMENTS AND SMALL ADDITION TO THE
 MAIN HOUSE ONLY.
  
 * SEPARATE PERMIT SUBMITTED FOR REAR STRUCTURE
 IMPROVEMENTS (REFERENCE: PERMIT #22010888).
  
 * HISTORIC STOP ADDED.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-10-05 Cont ID  
Sent By llouie Date 2021-10-05 Time   Rev Time  
Received By llouie Date 2021-10-05 Time   Sent To  
Notes
2021-10-05 09:14:01** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) UPDATED SIGNED AND SEALED SURVEY OF THE PROPERTY IS
 REQUIRED. PLEASE NOTE IN ORDER TO PERMIT THE PROPOSED
 GUEST COTTAGE BY-RIGHT, THE PROPERTY MUST HAVE THE
 FOLLOWING LOT DIMENSIONS: MINIMUM LOT SIZE = 6,000 SQ.
 FT. AND MINIMUM LOT WIDTH = 60 FT. [ZLDR S.94-71, TABLE
 III-1]
  
 2.) SITE PLAN SHOWING THE BUILDING SETBACKS OF THE
 PROPOSED ADDITION(S) IS REQUIRED. ANY EXPANSION OF THE
 BUILDING MUST COMPLY WITH THE SETBACK REQUIREMENTS OF
 SEC. 94-74 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS).
  
 3.) NOTATE HEIGHT OF THE BUILDING(S) IN THE ELEVATION
 SHEETS.
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF14
  