| 2021-09-20 08:22:46 | 09/20/21 1ST POOL PLUMBING REVIEW**DENIED** WITH |
| | COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. WOULD YOU PLEASE SUBMIT TOTAL DYNAMIC HEAD |
| | CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW. THE MAXIMUM |
| | FLOW OF THE PUMP FROM ITS PUMP CURVE IS NO LONGER |
| | ALLOWED TO BE USED IN DETERMINING THE MAXIMUM SYSTEM |
| | FLOW RATE PER ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, |
| | 4.4.9.1. THE 2013 EDITION ADDRESSES THE FLOW RATE IN |
| | GALLONS PER MINUTE (GPM). IT REQUIRES THAT THE MAXIMUM |
| | SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM |
| | FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN |
| | COVER). THE TDH CALCULATIONS MUST INCLUDE ALL THE |
| | SYSTEM COMPONENTS INCLUDING SUCTION AND RETURN PIPING, |
| | FITTINGS, VALVES, HEATER, FILTER, AND CHLORINATOR. ALL |
| | SYSTEM COMPONENTS EXCEPT THE PUMP. |
| | |
| | |
| | 2. INDICATE ON THE PUMP CURVE WHICH CURVE KEY IS FOR |
| | THE PUMP BEING INSTALLED ON THIS SYSTEM PER THE WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 3. WOULD YOU PLEASE SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE MAIN DRAIN, THE PUMP, HEATER, |
| | FILTER AND CHLORINATOR PER THE WPB AMENDMENTS TO FBC |
| | SEC. 107.2.1. |
| | |
| | 4. HEATED SWIMMING POOLS AND IN GROUND PERMANENTLY |
| | INSTALLED SPAS SHALL BE EQUIPPED WITH A VAPOR-RETARDANT |
| | COVER ON OR AT THE WATER SURFACE OR A LIQUID COVER OR |
| | OTHER MEANS PROVEN TO REDUCE HEAT LOSS PER THE 2020 |
| | FBC- ENERGY- SEC. R 403.10.3. |
| | |
| | 5. A CONTAINMENT REDUCED PRINCIPAL ZONE BACKFLOW DEVICE |
| | WILL BE REQUIRED AT THE WATER METER BY A LICENSED |
| | CONTRACTOR WITH A SEPARATE PERMIT AND CERTIFIED BY THE |
| | CITY OF WEST PALM BEACH UTILITY DEPARTMENT PER THE |
| | CROSS CONNECTION CONTROL MANUAL PAGE 11 (C). THIS IS |
| | DUE TO THE AUTOFILL ON THE POOL, WHICH WILL REQUIRE A |
| | BACKFLOW DEVICE (P.V.B. ISOLATION), AND IT WILL BE |
| | REQUIRED TO BE CERTIFIED BY A LICENSED BACKFLOW |
| | CONTRACTOR. A REPORT MUST BE FILLED OUT FOR THE P.V.B. |
| | AND WILL NEED TO BE WITH THE PERMIT AT THE FINAL. THE |
| | INSPECTOR WILL TAKE THE CERTIFICATION FOR CITY RECORDS. |
| | THESE TWO BACKFLOWS CAN BE COMBINED IN THE SAME PERMIT. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |