Plan Review Details - Permit 21090018
Plan Review Stops For Permit 21090018
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-10-27 Cont ID  
Sent By ccole Date 2021-10-27 Time 11:52 Rev Time 0.00
Received By ccole Date 2021-10-27 Time 10:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-10-13 Cont ID  
Sent By ccole Date 2021-10-13 Time 14:40 Rev Time 0.00
Received By ccole Date 2021-10-13 Time 13:17 Sent To  
Notes
2021-10-13 14:41:572ND REVIEW FBC-2020 RES. BUILDING.
 PERMIT- 21090018
 10/13/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
 1) SHEET 10B: THE REVISED PLAN SHEET SHOWS GAS BEING
 SUPPLIED TO THE RANGE BY AN EXTERIOR TANK (SEE GAS
 PLAN) AND BY A NATURAL GAS METER (SEE GAS RISER).
 PLEASE CHOOSE ONE METHOD OR THE OTHER AND CORRECT THE
 NOTES AND DETAILS ON THE PLAN.
  
 2) 10B: PLEASE UPDATE THE 2014 CODE REFERENCES IN THE
 NOTES TO THE FBC 2017 FUEL GAS.
  
 3) COMMENTS 1, 2, 3, 4, & 5 FROM THE 1ST REVIEW PRINTED
 BELOW STILL EXIST. PLEASE PROVIDE A COMPLETE GAS RISER
 DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 &
 G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS-
 THE RISER SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURES AT THE 1ST AND 2ND STAGE
 REGULATORS.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) INDICATE THE GALLON SIZE OF THE TANK ON THE PLAN AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS VERIFYING IT HAS
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58. THE TANK IS ASSUMED TO CONTAIN
 LP GAS- HOWEVER IT IS LABELED "COMPRESSED GAS". PLEASE
 LABEL IT CORRECTLY ON THE PLAN- SECTION 107.2.1 WPB.
  
 3) PROVIDE A LP TANK INSTALLATION DETAIL SHOWING THE
 REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE STRUCTURAL
 SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATION WITH
 THE CONTAINER SUPPORTS- SECTION 6.6.3.1 NFPA 58. SHOW
 HOW THE TANK WILL BE ANCHORED TO RESIST WIND LOAD AND
 WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA 58.
  
 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 RANGE IN COMPLIANCE WITH SECTION G2447.1 FBC RES.
  
 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SECTION G2407.1.
  
 6) CLARIFY IF AN EXHAUST HOOD IS TO BE INSTALLED UNDER
 THIS PERMIT OR UNDER A SEPARATE AND PROVIDE DETAILS-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-09-17 Cont ID  
Sent By ccole Date 2021-09-17 Time 11:15 Rev Time 0.00
Received By ccole Date 2021-09-17 Time 11:15 Sent To  
Notes
2021-09-17 11:17:011ST REVIEW FBC-2020 RES. BUILDING.
 PERMIT- 21090018
 9/17/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 10B: PROVIDE A GAS RISER DRAWING- SECTION
 107.3.5.3 (13) WPB AND SECTION G2412.3 & G2412.4 FBC
 RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- THE RISER
 SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURES AT THE 1ST AND 2ND STAGE
 REGULATORS.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) INDICATE THE GALLON SIZE OF THE TANK ON THE PLAN AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS VERIFYING IT HAS
 BEEN DESIGNED, FABRICATED, TESTED AND MARKED (STAMPED)
 IN ACCORDANCE WITH THE REGULATIONS AS REQUIRED BY THE
 REGULATORY AGENCIES AND COMPLIANCE STANDARDS LISTED IN
 SECTION 5.2.1.1 NFPA 58. THE TANK IS ASSUMED TO CONTAIN
 LP GAS- HOWEVER IT IS LABELED ?COMPRESSED GAS?. PLEASE
 LABEL IT CORRECTLY ON THE PLAN- SECTION 107.2.1 WPB.
  
 3) PROVIDE A LP TANK INSTALLATION DETAIL SHOWING THE
 REQUIRED MASONRY OR OTHER NON-COMBUSTIBLE STRUCTURAL
 SUPPORTS LOCATED ON CONCRETE OR MASONRY FOUNDATION WITH
 THE CONTAINER SUPPORTS- SECTION 6.6.3.1 NFPA 58. SHOW
 HOW THE TANK WILL BE ANCHORED TO RESIST WIND LOAD AND
 WIND PRESSURES- SECTION 6.6.3.3 (D) NFPA 58.
  
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE NEW
 RANGE IN COMPLIANCE WITH SECTION G2447.1 FBC RES.
  
 5) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE THE AIR WILL BE PROVIDED- SECTION G2407.1.
  
 6) CLARIFY IF AN EXHAUIST HOOD IS TO BE INSTALLED UNDER
 THIS PERMIT OR UNDER A SEPARATE AND PROVIDE DETAILS-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 BUILDING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-01 Cont ID  
Sent By medwards Date 2021-11-01 Time 13:00 Rev Time 0.00
Received By medwards Date 2021-10-29 Time 09:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 07:02 Rev Time 0.00
Received By medwards Date 2021-10-21 Time 12:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-10-13 Time   Rev Time 0.00
Received By aoliver Date 2021-09-30 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-09-17 Time   Rev Time 0.00
Received By ccarvaja Date 2021-09-02 Time 10:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-11-01 Cont ID  
Sent By medwards Date 2021-11-01 Time 12:50 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 12:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 06:36 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 06:36 Sent To  
Notes
2021-10-28 07:00:55THE SUBMITTED HOOD SHOWS THE EXHAUST CFM'S IS 900.
 PLEASE SHOW THE HOOD EXHAUST DUCTWORK AND TERMINATION
 LOCATION ALONG WITH THE MAKEUP AIR AND DUCTWORK. FBC
 RES M1503.3
 THIS MECHANICAL WORK WILL REQUIRE A MECHANICAL
 SUBPERMIT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-10-27 Cont ID  
Sent By ccole Date 2021-10-27 Time 10:03 Rev Time 0.00
Received By ccole Date 2021-10-27 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-10-13 Cont ID  
Sent By ccole Date 2021-10-13 Time 14:52 Rev Time 0.00
Received By ccole Date 2021-10-13 Time 13:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-09-17 Cont ID  
Sent By ccole Date 2021-09-17 Time 11:17 Rev Time 0.00
Received By ccole Date 2021-09-17 Time 11:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-01 Cont ID  
Sent By medwards Date 2021-11-01 Time 13:00 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 13:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-13 Cont ID  
Sent By ccole Date 2021-10-13 Time 14:53 Rev Time 0.00
Received By ccole Date 2021-10-13 Time 14:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-17 Cont ID  
Sent By ccole Date 2021-09-17 Time 12:50 Rev Time 0.00
Received By ccole Date 2021-09-17 Time 12:50 Sent To  
Notes
***NONE***