| 2021-09-07 12:10:07 | 09/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THIS BUILDING WAS CONSTRUCTED UNDER THE FAIR HOUSING |
| | ACT. WOULD YOU PLEASE INDICATE ON PLANS WHICH DESIGN |
| | SPECIFICATION ( "A" OR "B" OF THE ACT) WAS USED IN THE |
| | ORIGINAL DESIGN OF THESE UNITS? TELL US WHICH USABLE |
| | BATHROOM IN THE DWELLING UNITS AND THE PROPOSED |
| | ALTERATION IN THE BATHROOM SHALL ALSO COMPLY WITH THE |
| | FAIR HOUSING ACT. THIS NEEDS TO BE DETERMINED BY |
| | RESEARCHING WHEN THE BUILDING WAS BUILT AND REQUESTING |
| | PLANS FROM THIS CITY?S WEBSITE. THIS MAY INCUR A FEE |
| | AND TIME TO RETRIEVE ALL THIS INFORMATION. IT IS UP TO |
| | THE ARCHITECT TO REQUEST THE INFORMATION AND DETERMINE |
| | IF THE LEVEL OF ACCESSIBILITY IS ALTERED. WE REQUIRE TO |
| | SHOW THE DIMENSION OF THE CLEAR FLOOR SPACE IN THE |
| | BATHROOM IN FRONT OF EACH FIXTURE IN THAT BATHROOM. THE |
| | RESEARCH WILL TELL IF IT'S AN A OR B TYPE BATHROOM. |
| | |
| | 2. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT |
| | PROVIDES AN OPTION FOR CHANGING AN FHA COMPLIANCE |
| | STRUCTURE. THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE |
| | THAT THE PROPOSED BATHROOM DESIGN DOES NOT MEET THE |
| | FAIR HOUSING ACCESSIBILITY GUIDELINES REQUIREMENTS. THE |
| | OWNER AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT |
| | THE TIME OF SALE IF SO, REQUESTED BY THE BUYER. THIS |
| | WILL BE IN A LETTER-TYPE FORMAT SIGNED AND NOTARIZED BY |
| | THE OWNER. WE PROVIDE A SAMPLE LETTER, AND IT MUST BE |
| | SUBMITTED TO THE BUILDING DEPARTMENT OF THE CITY OF |
| | WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO |
| | [email protected], AND I WILL SEND A COPY OF THE FAIR |
| | HOUSING AFFIDAVIT. |
| | |
| | 3. ON SHEET P-1; |
| | A. UNDER GENERAL PLUMBING NOTES, IT REFERS TO THE 2017 |
| | PLUMBING CODE. WOULD YOU PLEASE CORRECT PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | B. WOULD YOU PLEASE PROVIDE A PLUMBING ISOMETRIC RISER |
| | DIAGRAM FOR SANITARY AND PLUMBING PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) COMMERCIAL |
| | PLUMBING? |
| | |
| | C. THE WASHING MACHINE VALVES MUST BE ACCESSIBLE FOR |
| | SHUTTING OFF WITHOUT MOVING UNITS, 2020 FBC SEC. R |
| | 2903.9.3 FIXTURE VALVES AND ACCESS. ACCESSIBLE |
| | SIGNIFIES ACCESS THAT REQUIRES THE REMOVAL OF AN ACCESS |
| | PANEL OR SIMILAR REMOVABLE OBSTRUCTION. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |