Plan Review Details - Permit 21081484
Plan Review Stops For Permit 21081484
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By rmcdouga Date 2021-09-24 Time 10:24 Rev Time 0.00
Received By rmcdouga Date 2021-09-24 Time 09:23 Sent To  
Notes
2021-09-24 10:21:211ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THE
 EXPOSURE CATEGORY IS C AND THE VULT. WIND SPEED IS 170
 MPH. FBC-R301.1
 2) THE NEGATIVE UPLIFT PRESSURES IN THE ROOF PRESSURE
 CHART ON SHEET S.1 APPEAR TO BE LOW. FBC-R301.2.1
 3) THE RAFTER SPANS OF JUST UNDER 18 FEET FOR THE 2X10S
 AT 16" OC APPEARS TO BE EXCESSIVE BASED ON THE DEAD
 LOADS OF THE ROOF COVERING AND THE 7/8" STUCCO CEILING
 ALONG WITH THE LIVE LOADS. SUBMIT SIGNED AND SEALED
 CALCULATIONS FROM THE ENGINEER. FBC AMENDMENTS
 107.2.1.2
 4) THE DOUBLE 2X10 LOAD BEARING HEADERS THAT ARE
 SUPPORTING THE ROOF FRAMING ARE SPANNING MORE THAN 12
 FEET. SUBMIT SIGNED AND SEALED CALCULATIONS TO SHOW
 THEY ARE CAPABLE OF SUPPORTING THE LOADS. FBC
 AMENDMENTS 107.2.1.2
 5) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-29 Cont ID  
Sent By jleahy Date 2021-09-29 Time 13:42 Rev Time 0.00
Received By jleahy Date 2021-09-29 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-29 Cont ID  
Sent By jleahy Date 2021-09-29 Time 13:43 Rev Time 0.00
Received By jleahy Date 2021-09-03 Time 17:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-09-24 Cont ID  
Sent By rmcdouga Date 2021-09-24 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2021-09-24 Time 09:25 Sent To  
Notes
2021-09-24 10:25:37NO HABITABLE SPACE IS BEING ADDED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By rmcdouga Date 2021-09-24 Time 10:25 Rev Time 0.00
Received By rmcdouga Date 2021-09-24 Time 09:25 Sent To  
Notes
2021-09-24 10:27:27THE ENGINEER'S DIGITAL SIGNATURE ON THE PLANS COULD NOT
 BE VERIFIED. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO
 BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF
 THE SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By av Date 2021-09-24 Time 10:55 Rev Time 0.00
Received By ajones Date 2021-09-24 Time 10:55 Sent To  
Notes
2021-09-24 10:57:589/24/21- FAILED. PLEASE PROVIDE A SITE PLAN/SURVEY
 SHOWING THE SETBACK FOR THE COLUMNS FROM THE PROPERTY
 LINE.
  
 ANGELLA VANN, AICP
 561-822-1441
 [email protected]