| 2021-09-10 17:20:56 | RESIDENTIAL (R3) RE-ROOF, SECOND BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21081335 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- NEW MODIFIED BITUMEN FLORIDA PRODUCT APPROVAL |
| | FL16709-R8 SUBMITTED: |
| | A) BUILDING EXPOSURE: ACCORDING TO SEC. R301.2.1.4 |
| | FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE |
| | "D" NOT "C". REVISE AS REQUIRED. |
| | |
| | B) PAGE 25 OF 25 OF MODIFIED BITUMEN FLORIDA PRODUCT |
| | APPROVAL FL16709-R8 SUBMITTED INDICATES "N/A " FOR ROOF |
| | ZONE 3 FOR AN ULTIMATE WIND SPEED OF 170MPH IN BUILDING |
| | EXPOSURE D. |
| | "N/A" INDICATES THE SYSTEM CANNOT BE USED WITHIN THE |
| | PRESSURE ZONE. SEE MEANING OF "N/A" ON PAGE 22 OF 25 |
| | UNDER TABLE 7 HEADING. |
| | NEED TO USE ANOTHER PRODUCT APPROVAL OR PROVIDE SINGED |
| | AND SEALED RAS 117 CALCULATIONS FOR PRODUCT APPROVAL FL |
| | 2533-R5 AS REQUESTED ON THE FIRST REVIEW. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | ************************************** |
| | ORIGINAL REVIEW COMMENTS: |
| | |
| | PLAN REVIEW ROOFING |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/RPX306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | 2017 NEC |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE ENHANCED FASTENER CALCULATIONS PER |
| | LIMITATIONS NOTE 5.7.2 OF FL 2533-R5, PREPARED BY A |
| | QUALIFIED DESIGN PROFESSIONAL. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |