Plan Review Details - Permit 21081267
Plan Review Stops For Permit 21081267
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-12-01 Cont ID  
Sent By rmcdouga Date 2021-12-01 Time 10:40 Rev Time 0.00
Received By rmcdouga Date 2021-12-01 Time 10:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-29 Cont ID  
Sent By rmcdouga Date 2021-11-29 Time 10:04 Rev Time 0.00
Received By rmcdouga Date 2021-11-29 Time 10:04 Sent To  
Notes
2021-11-29 10:04:04PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [NOT RESOLVED. THE LETTER FROM THE FLORIDA
 DEPARTMENT OF HEALTH HAS THE ADDRESS OF THE POOL AS
 3580 VILLAGE BLVD. THE PLANS AND THE PERMIT APPLICATION
 HAVE AN ADDRESS OF 3590 VILLAGE BLVD.] SUBMIT A COPY OF
 THE RECEIPT FOR THE POOL OPERATING PERMIT FROM THE PALM
 BEACH COUNTY HEALTH DEPARTMENT. FS 514.03 APPROVAL
 NECESSARY TO CONSTRUCT, DEVELOP, OR MODIFY PUBLIC
 SWIMMING POOLS OR PUBLIC BATHING PLACES.
 (1) A PERSON OR PUBLIC BODY DESIRING TO CONSTRUCT,
 DEVELOP, OR MODIFY A PUBLIC SWIMMING POOL MUST SUBMIT
 AN APPLICATION, CONTAINING THE INFORMATION REQUIRED
 UNDER S. 514.031(1)(A)1.-6. TO THE DEPARTMENT FOR AN
 OPERATING PERMIT BEFORE FILING AN APPLICATION FOR A
 BUILDING PERMIT UNDER S. 553.79. A COPY OF THE FINAL
 INSPECTION REQUIRED UNDER S. 514.031(1)(A)5. SHALL BE
 SUBMITTED TO THE DEPARTMENT UPON RECEIPT BY THE
 APPLICANT. THE APPLICATION SHALL BE DEEMED INCOMPLETE
 PURSUANT TO S. 120.60 UNTIL SUCH COPY IS SUBMITTED TO
 THE DEPARTMENT.
  
 2) [RESOLVED.] THE PROJECT IS LOACTED IN A SPECIAL
 FLOOD HAZARD AREA (SFHA). THE FLOOD ZONE IS AE AND THE
 BFE IS 14' NAVD. THE CITY HAS A 2' FREE BOARD
 REQUIREMENT WHICH MAKES THE DFE 16' NAVD. THE POOL
 EQUIPMENT IS REQUIRED TO COMPLY WITH FBC 1612.4.2 AND
 ASCE 24-14.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-21 Cont ID  
Sent By rmcdouga Date 2021-09-21 Time 15:09 Rev Time 0.00
Received By rmcdouga Date 2021-09-21 Time 13:13 Sent To  
Notes
2021-09-21 15:07:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT A COPY OF THE RECEIPT FOR THE POOL OPERATING
 PERMIT FROM THE PALM BEACH COUNTY HEALTH DEPARTMENT. FS
 514.03 APPROVAL NECESSARY TO CONSTRUCT, DEVELOP, OR
 MODIFY PUBLIC SWIMMING POOLS OR PUBLIC BATHING PLACES.
 (1) A PERSON OR PUBLIC BODY DESIRING TO CONSTRUCT,
 DEVELOP, OR MODIFY A PUBLIC SWIMMING POOL MUST SUBMIT
 AN APPLICATION, CONTAINING THE INFORMATION REQUIRED
 UNDER S. 514.031(1)(A)1.-6. TO THE DEPARTMENT FOR AN
 OPERATING PERMIT BEFORE FILING AN APPLICATION FOR A
 BUILDING PERMIT UNDER S. 553.79. A COPY OF THE FINAL
 INSPECTION REQUIRED UNDER S. 514.031(1)(A)5. SHALL BE
 SUBMITTED TO THE DEPARTMENT UPON RECEIPT BY THE
 APPLICANT. THE APPLICATION SHALL BE DEEMED INCOMPLETE
 PURSUANT TO S. 120.60 UNTIL SUCH COPY IS SUBMITTED TO
 THE DEPARTMENT.
  
 2) THE PROJECT IS LOACTED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE FLOOD ZONE IS AE AND THE BFE IS 14'
 NAVD. THE CITY HAS A 2' FREE BOARD REQUIREMENT WHICH
 MAKES THE DFE 16' NAVD. THE POOL EQUIPMENT IS REQUIRED
 TO COMPLY WITH FBC 1612.4.2 AND ASCE 24-14.
  
 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-12-07 Cont ID  
Sent By mpeterso Date 2021-12-07 Time 13:21 Rev Time 0.00
Received By mpeterso Date 2021-12-07 Time 13:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-11-14 Cont ID  
Sent By jleahy Date 2021-11-14 Time 15:40 Rev Time 0.00
Received By jleahy Date 2021-11-14 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-24 Cont ID  
Sent By jleahy Date 2021-09-24 Time 16:37 Rev Time 0.00
Received By jleahy Date 2021-09-24 Time 14:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-07 Cont ID  
Sent By lmarchan Date 2021-12-07 Time 14:13 Rev Time 0.00
Received By lmarchan Date 2021-11-30 Time 13:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-29 Cont ID  
Sent By rmcdouga Date 2021-11-29 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2021-11-09 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-26 Cont ID  
Sent By lmarchan Date 2021-09-26 Time 08:10 Rev Time 0.00
Received By lmarchan Date 2021-09-01 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-12-03 Cont ID  
Sent By ccole Date 2021-12-03 Time 11:32 Rev Time 0.00
Received By ccole Date 2021-12-03 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-11-18 Cont ID  
Sent By ccole Date 2021-11-18 Time 16:34 Rev Time 0.00
Received By ccole Date 2021-11-18 Time 12:10 Sent To  
Notes
2021-11-18 16:36:172ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21081267
 11/18/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017
 FBC B- FLORIDA BUILDING CODE 6TH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 6TH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS FOR THE MAIN POOL- DENIED. FAILED
 COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW WITH
 ADDITIONAL NOTES IN CAP LETTERS.
  
 1) FAIILED. PLEASE PROVIDE A LIST OF REQUIRED SEPARATE
 PERMITS ON THE PLAN INCLUDING-
 ON SITE PLUMBING FOR WATER SUPPLY AND WASTE-WATER
 DISPOSAL.
 BACKFLOW PREVENTER FOR THE WATER SUPPLY TO THE POOL.
 AUTO FILL INSTALLATION.
 RESTROOM FACILITY AND PLUMBING AND FIXTURE
 INSTALLATIONS.
 POOL SHOWER AND HOSE BIB PLUMBING AND FIXTURE
 INSTALLATIONS.
 PAVILION AND EQUIPMENT ENCLOSURE CONSTRUCTION.
 POOL FENCE
 PAVER DECK
  
 5) FAILED. SHEET 1: THE DISCHARGE WATER FROM THE POOL
 SHALL NOT DRAIN INTO THE CITY SANITARY SYSTEM- SECTION
 454.1.6.5.15 & SEC. 90-126(5) WPB CODE OF ORDINANCES.
 PLEASE REVISE THE PLANS TO SHOW AN APPROVED PLACE OF
 DISPOSAL. THE DISCHARGE WATER IS ALSO SHOWN TO BE
 DRAINING INTO THE STORM DRAIN SYSTEM IN THE WASTE
 DETAIL ON SHEET 6. PLEASE NOTE THAT THE CITY OF WPB
 UTILITIES DEPT. PROHIBITS POOL WASTE-WATER FROM
 DRAINING INTO THE STORM DRAIN SYSTEM UNLESS THE WATER
 HAS BEEN DECHLORINATED. THE ENGINEER OF RECORD SHALL
 PROVIDE A PROCEDURE AND EQUIPMENT SPECIFICATIONS. IN
 RESPONSE ONE OF THE TWO RESPONSE NARRATIVES INDICATES
 ALL WATER TO BE DE-CHLORINATED AND ROUTED TO THE STORM.
 THE SECOND NARRATIVE INDICATES A DE-CHLORINATOR HAS
 BEEN PROVIDED.
  
 A) PLEASE SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 DE-CHLORINATOR.
  
 B) PLEASE CONTACT THE CHRIS JACKSON, ENVIRONMENTAL
 COMPLIANCE SPECIALIST III, PUBLIC UTILITIES DEPARTMENT,
 561-822-2062 OR [email protected] FOR FURTHER
 DIRECTION.
  
 C) PLEASE REMOVE ALL DETAILS AND NOTES FROM THE PLAN
 INDICATING POOL WASTE WATER DRAINING INTO THE SANITARY,
 AND ADD NOTES TO INDICATE ONLY DE-CHLORINATED WATER TO
 DRAIN INTO THE STORM SYSTEM- SEE SHEETS PPP-2, P0-1,
 P0-3, P0-6.
  
 13) FAILED. SHEET 2: PROVIDE TOTAL DYNAMIC HEAD
 CALCULATIONS AND THE PUMP CURVE FROM THE MANUFACTURER-
 SECTION 454.1.6.5.4 FBC B. TDH CALCS AND PUMP CURVE NOT
 PROVIDED.
  
 16) FAILED. SHEETS 4 & 6: PLEASE PROVIDE THE DIMENSIONS
 OF THE GUTTERS IN COMPLIANCE WITH SECTION
 454.1.6.5.3.1.1 FBC B. NOT PROVIDED.
  
 20) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS FROM THE FBC EC:
 FAILED. C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL
 HEATERS SHALL BE CONTROLLED BY A READILY ACCESSIBLE
 ON-OFF SWITCH THAT IS AN INTEGRAL PART OF THE HEATER,
 MOUNTED ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO
 AND WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF
 SUCH SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS. HEATER SPECS WERE NOT PROVIDED AND
 SWITCH LOCATION NOT SHOWN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-17 Cont ID  
Sent By ccole Date 2021-09-17 Time 08:34 Rev Time 0.00
Received By ccole Date 2021-09-16 Time 08:33 Sent To  
Notes
2021-09-17 08:37:401ST REVIEW FBC-2017 PLUMBING
 PERMIT- 21081267
 9/15/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017
 FBC B- FLORIDA BUILDING CODE 6TH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 6TH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS FOR THE MAIN POOL- DENIED.
  
 1) PLEASE NOTE THE FOLLOWING LIST OF ITEMS REQUIRING
 SEPARATE PERMITS AND PLAN SUBMITTALS:
 ON SITE PLUMBING FOR WATER SUPPLY AND WASTE-WATER
 DISPOSAL.
 BACKFLOW PREVENTER FOR THE WATER SUPPLY TO THE POOL.
 AUTO FILL INSTALLATION.
 RESTROOM FACILITY AND PLUMBING AND FIXTURE
 INSTALLATIONS.
 POOL SHOWER AND HOSE BIB PLUMBING AND FIXTURE
 INSTALLATIONS.
 PAVILION AND EQUIPMENT ENCLOSURE CONSTRUCTION.
 POOL FENCE
 PAVER DECK
  
 2) PLEASE NOTE THAT THE PERMIT APPLICANT IS RESPONSIBLE
 FOR OBTAINING AN OPERATIONAL PERMIT ISSUED BY THE PALM
 BEACH COUNTY DEPARTMENT OF HEALTH- SECTION 454.1.1 FBC
 B.
  
 3) SHEET 1 DESIGN CRITERIA: REFER TO 454.1.1 AND
 1612.4.2 FBC B.-THE POOL IS BEING CONSTRUCTED IN AN AE
 FLOOD ZONE. PLEASE ADD THE ASCE 24-2014 TO THE LIST OF
 CODES AND STANDARDS AND PROVIDE DETAILS AND NOTES ON
 THE PLAN INDICATING COMPLIANCE WITH SECTION 7.3
 PLUMBING SYSTEMS, 7.4 MECHANICAL, HEATING, HVAC
 SYSTEMS.
  
 SECTION 7.3.1: THE POOL PLUMBING PIPES SHALL BE BURIED
 TO A DEPTH SUFFICIENT TO PREVENT MOVEMENT, SEPARATION,
 OR LOSS DUE TO FLOODING AND EROSION UNDER DESIGN FLOOD
 CONDITIONS.
  
 SECTION 7.3.2: THE POOL PIPING EMERGING FROM
 UNDERGROUND SHALL BE DESIGNED, CONSTRUCTED, ANCHORED,
 AND PROTECTED TO WITHSTAND FLOOD-RELATED LOADS,
 INCLUDING THE EFFECTS OF BUOYANCY, HYDRODYNAMIC FORCES,
 AND DEBRIS IMPACT.
  
 SECTION 7.3.3: THE POOL PLUMBING SYSTEM AND COMPONENTS
 (POOL EQUIPMENT) SHALL BE ELEVATED AT A MINIMUM OF 1
 FT. ABOVE THE BFE + 1 FT. OR THE DFE WHICHEVER IS
 HIGHER PER TABLE 7-1. OPENINGS BELOW THE REQUIRED
 ELEVATION SHALL BE PROTECTED WITH AUTOMATIC BACKWATER
 VALVES OR OTHER AUTOMATIC BACKFLOW DEVICES.
  
 REFER TO SECTION 309.1 FBC P FOR ADDITIONAL
 REQUIREMENTS FOR PLUMBING PIPING AND EQUIPMENT
 INCLUDING THE SANITARY AND STORM DRAIN PIPING, POOL
 HEATER, PUMP, AND OTHER POOL EQUIPMENT. SUCH SYSTEMS
 ARE REQUIRED TO BE DESIGNED AND INSTALLED TO PREVENT
 WATER FROM ENTERING OR ACCUMULATING WITHIN THEIR
 COMPONENTS AND THE SYSTEMS ARE CONSTRUCTED TO RESIST
 HYDROSTATIC AND HYDRODYNAMIC LOADS AND STRESSES,
 INCLUDING THE EFFECTS OF BUOYANCY, DURING THE
 OCCURRENCE OF FLOODING UP TO SUCH AN ELEVATION.
  
 4) SHEET 2: INDICATE WHICH CODE STANDARD AND FORMULA
 WAS USED TO DETERMINE THE CALCULATED GPM FLOW OF 75 GPM
 PER LIVING UNIT- SECTION 107.2.1. PLEASE NOTE SECTION
 454.1.1 FBC B SPECIFIES ONE BATHER PER SEVEN LIVING
 UNITS FOR A NONTRANSIENT FACILITY, AND BATHING LOAD
 COMPUTED EITHER ON THE BASIS OF ONE PERSON PER 5 GPM OF
 RECIRCULATION FLOW, OR ONE PERSON PER EACH 20 SQ. FT.
  
 5) SHEET 1: THE DISCHARGE WATER FROM THE POOL SHALL NOT
 DRAIN INTO THE CITY SANITARY SYSTEM- SECTION
 454.1.6.5.15 & SEC. 90-126(5) WPB CODE OF ORDINANCES.
 PLEASE REVISE THE PLANS TO SHOW AN APPROVED PLACE OF
 DISPOSAL. THE DISCHARGE WATER IS ALSO SHOWN TO BE
 DRAINING INTO THE STORM DRAIN SYSTEM IN THE WASTE
 DETAIL ON SHEET 6. PLEASE NOTE THAT THE CITY OF WPB
 UTILITIES DEPT.
  
 PROHIBITS POOL WASTE WATER FROM DRAINING INTO THE STORM
 DRAIN SYSTEM UNLESS THE WATER HAS BEEN DECHLORINATED.
 THE ENGINEER OF RECORD SHALL PROVIDE A PROCEDURE AND
 EQUIPMENT SPECIFICATIONS.
  
 6) SHEET 1: PLEASE ADD A NOTE TO INDICATE THE POOL
 EQUIPMENT ENCLOSURE GATE WILL BE SELF- CLOSING AND
 SELF-LATCHING- 454.1.5.1.
  
 7) SHEET 1: THE WOMEN'S RESTROOM SHALL HAVE A RATIO OF
 THREE TO TWO WATER CLOSETS FOR WOMEN AS THE COMBINED
 TOTAL OF WATER CLOSETS AND URINALS PROVIDED FOR ME-
 454.1.6.1.1 FBC B.
  
 8) SHEET 1: SHOW THE REQUIRED FLOOR DRAINS IN THE
 RESTROOMS AND FLOOR SLOPE TO DRAINS- 454.1.6.1.3 FBC B.
  
 9) SHEET 1: A HOSE BIB WITH A VACUUM BREAKER SHALL BE
 PROVIDED WITHIN 25 FT. OF THE EACH RESTROOM FOR EASE OF
 CLEANING- 454.1.6.4. INDICATE VACUUM BREAKERS WILL BE
 INSTALLED AT ALL OTHER HOSE BIBS SHOWN ON THE PLAN -
 454.1.6.3.
  
 10) SHEET 2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE VAKPAK AP30 FILTRATION SYSTEM, PUMP, COLLECTOR
 TANK, SEPARATOR TANK, AND DISINFECTION EQUIPMENT
 INCLUDING CHLORINE FEEDERS AND CONTAINERS. THE SPECS
 SHALL INDICATE THE EQUIPMENT CONFORMS WITH REQUIRED
 STANDARDS NSF/ANSI STANDARD 50, CIRCULATION SYSTEM
 COMPONENTS AND RELATED MATERIALS FOR SWIMMING POOL,
 SPAS/HOT TUBS, DATED APRIL 2007- SECTIONS 454.1.6.5.1 &
 454.1.6.5.5.3 FBC B. THE SPECS SHALL INDICATE TYPE OF
 FILTERING MATERIAL TO BE PROVIDED. PLEASE NOTE THAT A
 PRECOAT OR COLLECTOR TANK SHALL BE PROVIDED FOR D-E
 TYPE SYSTEMS- 454.1.6.5.5.1.
  
 11) SHEET 2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE POOL HEATER, AND PROVIDE A PIPING DIAGRAM SHOWING
 THE LOCATION OF THE FIXED THERMOMETER, VALVES, PIPE
 SIZES AND MATERIAL SPECIFICATIONS- SECTION 454.1.6.5.14
 FBC B.
  
 12) SHEET 2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 THE MAIN DRAIN AND COVER SHOWING CONFORMANCE WITH THE
 ANSI/APSP 16 STANDARD- 454.1.6.5.10.2 FBC P. PROVIDE AN
 ENLARGED MAIN DRAIN DETAIL IN COMPLIANCE WITH SECTION
 454.1.6.5.10.2 FBC B.
  
 13) SHEET 2: PROVIDE TOTAL DYNAMIC HEAD CALCULATIONS
 AND THE PUMP CURVE FROM THE MANUFACTURER- SECTION
 454.1.6.5.4 FBC B.
  
 14) SHEETS 2, 3, & 5: PLEASE PROVIDE AN ENLARGED
 EQUIPMENT ROOM DRAWING THAT IDENTIFIES ALL EQUIPMENT IN
 THE ROOM/AREA THE CORRELATING NUMBERED EQUIPMENT
 SCHEDULE- SECTION 454.1.5 FBC B. INCLUDE A PLUMBING
 PIPING SCHEMATIC FOR THE EQUIPMENT IN THE ROOM.
  
 15) SHEETS 1 & 4: PLEASE SHOW THE ENTIRE POOL PIPING
 RUNS FROM THE POOL TO THE EQUIPMENT AREA AND VAKPAK-
 THE PLAN IS CUT OFF AT THE PAVILION- SECTION 454.1.6.5
 FBC B AND SECTION 107.2.1 WPB. PLEASE INCLUDE THE WATER
 SUPPLY RUN FROM THE POINT OF CONNECTION FROM THE MAIN
 TO THE TO THE VAKPAK WITH THE LOCATIONS OF TYPES OF
 VALVES AND BACKFLOW PREVENTER IDENTIFIED: AND THE
 DISCHARGE PIPING FROM THE VAKPAK TO THE DISPOSAL
 LOCATION- SECTION 107.2.1 WPB. PLEASE REFER TO COMMENT
 #5 ABOVE CONCERNING WASTE-WATER DISCHARGE.
  
 16) SHEETS 4 & 6: PLEASE PROVIDE THE DIMENSIONS OF THE
 GUTTERS IN COMPLIANCE WITH SECTION 454.1.6.5.3.1.1 FBC
 B.
  
 17) SHEETS 2 & 4: CLARIFY FLOW RATE INDICATORS WILL BE
 INSTALLED ON THE RETURN PIPING AND INCLUDE THEM IN THE
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECTION
 454.1.6.5.13 FBC B.
  
 18) SHEETS 1, 2 & 6: CLARIFY IF A TIME CLOCK WILL BE
 INSTALLED FOR THE RECIRCULATION SYSTEM AND INCLUDE IT
 IN THE SCHEDULE, AND PROVIDE INSTALLATION DETAILS-
 SECTION 454.1.6.5.2 FBC B.
  
 19) PROVIDE A WATER SUPPLY PIPING LAYOUT AND RISER
 DRAWING FOR INSTALLATION OF THE HOSE BIB AND POOL
 SHOWER- SECTION 602.2 FBC P AND 107.3.5.1.3 WPB. PLEASE
 PROVIDE EQUIPMENT SCHEDULES FOR THE FIXTURES ON THE
 PLAN- SECTIONS 412.3 & 608.16.4.2 FBC P. A) INDICATE
 HOW WATER FROM THE SHOWER WILL BE DRAINED TO AN
 APPROVED PLACE OF DISPOSAL- SECS. 90-126 & 203 WPB CODE
 OF ORDINANCES.
  
 20) PLEASE SHOW COMPLIANCE WITH THE FOLLOWING CODE
 SECTIONS FROM THE FBC EC:
  
 C404.9.1 HEATERS. THE ELECTRIC POWER TO ALL HEATERS
 SHALL BE CONTROLLED BY A READILY ACCESSIBLE ON-OFF
 SWITCH THAT IS AN INTEGRAL PART OF THE HEATER, MOUNTED
 ON THE EXTERIOR OF THE HEATER, OR EXTERNAL TO AND
 WITHIN 3 FEET (914 MM) OF THE HEATER. OPERATION OF SUCH
 SWITCH SHALL NOT CHANGE THE SETTING OF THE HEATER
 THERMOSTAT. SUCH SWITCHES SHALL BE IN ADDITION TO A
 CIRCUIT BREAKER FOR THE POWER TO THE HEATER. GAS-FIRED
 HEATERS SHALL NOT BE EQUIPPED WITH CONTINUOUSLY BURNING
 IGNITION PILOTS.
  
 C404.9.2 TIME SWITCHES. TIME SWITCHES OR OTHER CONTROL
 METHODS THAT CAN AUTOMATICALLY TURN OFF AND ON HEATERS
 AND PUMP MOTORS ACCORDING TO A PRESET SCHEDULE SHALL BE
 INSTALLED FOR HEATERS AND PUMP MOTORS. HEATERS AND PUMP
 MOTORS THAT HAVE BUILT-IN TIME SWITCHES SHALL BE IN
 COMPLIANCE WITH THIS SECTION.
 EXCEPTIONS:
 1. WHERE PUBLIC HEALTH STANDARDS REQUIRE 24-HOUR PUMP
 OPERATION.
 2. PUMPS THAT OPERATE SOLAR- AND WASTE-HEAT-RECOVERY
 POOL HEATING SYSTEMS.
  
 C404.9.3 COVERS. OUTDOOR HEATED SWIMMING POOLS AND
 OUTDOOR PERMANENT SPAS SHALL BE EQUIPPED WITH A
 VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-12-07 Cont ID  
Sent By lcrespo Date 2021-12-07 Time 15:48 Rev Time 0.00
Received By lcrespo Date 2021-12-07 Time 15:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-12-01 Cont ID  
Sent By rmcdouga Date 2021-12-01 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2021-12-01 Time 10:49 Sent To  
Notes
2021-12-01 11:04:43THE PAPER PLAN SHEETS THAT WERE SUBMITTED ARE COPIES OF
 SHEETS WITH DIGITAL SIGNATURES. THESE ARE SHEETS:
 CH-5.1, EPP-1, PPP-1 & PPP-2. PAPER DOCUMENTS ARE
 REQUIRED TO HAVE THE DESIGNER'S ORIGINAL HANDWRITTEN
 SIGNATURE. DIGITAL SIGNATURES ARE ONLY ACCEPTABLE FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & 61G1 OR FS 471 & 61G15
 SENT TO DENIED SIGNATURE BOX IN LIBRARY.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-29 Cont ID  
Sent By rmcdouga Date 2021-11-29 Time 10:05 Rev Time 0.00
Received By rmcdouga Date 2021-11-29 Time 10:04 Sent To  
Notes
2021-11-29 10:08:12THE REVISED DRAWINGS HAVE NOT BEEN DIGITALLY SIGNED BY
 THE ENGINEER. THE DIGITALLY SIGNED DRAWINGS IN THE
 SIGNATURE FILE DO NOT REFLECT THE CHANGES THAT WERE
 MADE TO ADDRESS THE REVIEW COMMENTS. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-21 Cont ID  
Sent By rmcdouga Date 2021-09-21 Time 14:04 Rev Time 0.00
Received By rmcdouga Date 2021-09-21 Time 14:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2021-12-07 Cont ID  
Sent By jroach Date 2021-12-07 Time 13:30 Rev Time 0.00
Received By jroach Date 2021-12-07 Time 13:30 Sent To  
Notes
2021-12-07 13:30:15THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE BROADSTONE LAKESIDE RESIDENTIAL PLANNED
 DEVELOPMENT SHALL BE SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 106-20,
 APPROVED ON JULY 27, 2020, AND AS MAY BE AMENDED.
  
 2. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED
 (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS
 OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE
 GRADE.
  
 3. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.
  
 4. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE
 POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT
 NOT ONTO ADJACENT PROPERTIES.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2021-11-22 Cont ID  
Sent By jroach Date 2021-11-22 Time 14:09 Rev Time 0.00
Received By jroach Date 2021-11-22 Time 14:09 Sent To  
Notes
2021-11-22 14:09:59THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE BROADSTONE LAKESIDE RESIDENTIAL PLANNED
 DEVELOPMENT SHALL BE SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 106-20,
 APPROVED ON JULY 27, 2020, AND AS MAY BE AMENDED.
  
 2. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED
 (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS
 OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE
 GRADE.
  
 3. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.
  
 4. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE
 POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT
 NOT ONTO ADJACENT PROPERTIES.
 _______________________________________________________
 _____________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 P: 561.822.1448 | E: [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-25 Cont ID  
Sent By jroach Date 2021-09-25 Time 14:53 Rev Time 0.00
Received By jroach Date 2021-09-25 Time 14:04 Sent To  
Notes
2021-09-25 14:53:30THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. THE BROADSTONE LAKESIDE RESIDENTIAL PLANNED
 DEVELOPMENT SHALL BE SUBJECT TO ALL DEVELOPMENT ORDER
 CONDITIONS, AS OUTLINED IN RESOLUTION NO. 106-20,
 APPROVED ON JULY 27, 2020, AND AS MAY BE AMENDED.
  
 2. ALL POOL EQUIPMENT SHALL BE A MINIMUM OF ONE (1)
 FOOT FROM THE SIDE PROPERTY LINE.
  
 3. POOL SHALL BE ENCLOSED BY A PERMANENT FENCE OR
 SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT ACCESS
 BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF THE
 RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED
 (?BABY FENCE? DOES NOT MEET THIS REQUIREMENT). BARRIERS
 OR FENCES SHALL BE AT LEAST 4 FEET IN HEIGHT ABOVE
 GRADE.
  
 4. ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE THROUGH
 A BUILDING OR THROUGH A SELF-CLOSING AND SELF-LATCHING
 GATE OR THROUGH A SCREEN ENCLOSURE DOOR WITH LATCHES
 PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF GATE.
  
 5. PATIO OR PAVED AREA ADJACENT TO OR SURROUNDING THE
 POOL SHALL BE DESIGNED TO DRAIN AWAY FROM THE POOL, BUT
 NOT ONTO ADJACENT PROPERTIES.
 _______________________________________________________