| Plan Review Stops For Permit 21081222 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
P |
Date |
2021-12-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-01 |
Time |
12:23 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-01 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2021-12-01 12:24:53 | PLANS FOR SUITE 600 AND 800 REMOVED. APPROVED | | | ADDRESSING REVIEW. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2021-11-04 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-11-04 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-11-04 |
Time |
12:31 |
Sent To |
|
|
| Notes |
| 2021-11-04 12:31:35 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2021-10-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-10-31 |
Time |
12:11 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-10-31 |
Time |
12:11 |
Sent To |
|
|
| Notes |
| 2021-10-31 12:12:20 | PLANS UPLOADED ARE FOR SUITES 600, 700 AND 800 HOWEVER | | | APPLICATION IS ONLY FOR SUITE 700. PLEASE LET ME KNOW | | | THE SCOPE OF WORK AND WHICH ADDRESSES ARE INVOLVED. IF | | | YOU YOU ARE DEMOING ALL THREE SUITES THREE PERMITS WILL | | | NEED TO BE APPLIED FOR. PLEASE EMAIL [email protected] OR | | | CALL 561-805--659 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-10-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-10-19 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-10-19 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2021-10-19 16:38:08 | PLANS UPLOADED ARE FOR SUITES 600, 700 AND 800 HOWEVER | | | APPLICATION IS ONLY FOR SUITE 700. PLEASE LET ME KNOW | | | THE SCOPE OF WORK AND WHICH ADDRESSES ARE INVOLVED. | | | PLEASE EMAIL [email protected] OR CALL 561-805--659 |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
5 |
Status |
P |
Date |
2022-02-18 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-02-18 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-02-18 |
Time |
08:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
4 |
Status |
F |
Date |
2021-12-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-12-13 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-12-13 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2021-12-13 10:20:41 | LETTER IS STILL MISSING THE REQUIRED TEXT LISTED BELOW | | | AND A SIGNATURE OF THE QUALIFIER. | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | ASBESTOS REVIEW DENIED: | | | | | | FAILED PLAN REVIEW, COMMERCIAL: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
F |
Date |
2021-12-02 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-12-02 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-12-02 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2021-12-02 13:13:32 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | ASBESTOS REVIEW DENIED: | | | | | | FAILED PLAN REVIEW, COMMERCIAL: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2021-10-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-10-29 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-10-29 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2021-10-29 08:42:55 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | ASBESTOS REVIEW DENIED: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-09-10 |
Time |
06:41 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-09-10 |
Time |
06:27 |
Sent To |
|
|
| Notes |
| 2021-09-10 06:43:39 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | ASBESTOS COMMENTS: | | | | | | FAILED PLAN REVIEW, COMMERCIAL: | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING | | | ASBESTOS REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD | | | BE IN PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND ?ASBESTOS? IN THE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2021-12-02 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-12-02 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-12-02 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-10-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-10-29 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-10-29 |
Time |
08:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-09-10 |
Time |
06:43 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-09-10 |
Time |
06:28 |
Sent To |
|
|
| Notes |
| 2021-09-10 07:11:27 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1, PROVIDE A SITE PLAN THAT INDICATES WHICH | | | WALLS/COLUMNS ARE BEARING AND/OR FIRE RATED MEMBERS AND | | | IF THESE WALLS/COLUMNS ARE BEING CHANGED OUT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-08-28 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-08-28 |
Time |
22:46 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-08-28 |
Time |
22:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2021-08-31 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-08-31 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
2021-08-31 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-11-09 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2021-11-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-11-01 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2021-11-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-12-13 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-12-13 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-12-10 |
Time |
10:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-12-02 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-12-02 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-11-04 |
Time |
12:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-11-02 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-11-02 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-10-07 |
Time |
09:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-09-10 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-08-24 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2021-10-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2021-10-21 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2021-10-21 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-09-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-09-10 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-09-10 |
Time |
07:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2021-12-02 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2021-12-02 |
Time |
13:08 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2021-12-02 |
Time |
13:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-10-08 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-10-08 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-10-08 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2021-10-08 15:37:54 | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS. A COPY OF A SIGNED | | | PLAN IS NOT CONSIDERED AN ORIGINAL.IT APPEARS THE | | | ENGINEER HAS A DIGITAL SIGNATURE PLEASE EMAIL THE | | | ORIGINAL DIGITALLY SIGNED DOCUMENT | | | | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-08-24 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-08-24 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-08-24 |
Time |
15:50 |
Sent To |
|
|
| Notes |
| 2021-08-24 15:51:49 | ORIGINAL SIGNED AND SEALED ENGINEER'S LETTERS SENT TO | | | STORAGE. |
|
|