Plan Review Details - Permit 21081166
Plan Review Stops For Permit 21081166
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2023-01-24 Cont ID  
Sent By ccole Date 2023-01-24 Time 16:47 Rev Time 0.00
Received By ccole Date 2023-01-24 Time 16:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2023-01-19 Cont ID  
Sent By ccole Date 2023-01-19 Time 08:34 Rev Time 0.00
Received By ccole Date 2023-01-19 Time 07:44 Sent To  
Notes
2023-01-19 08:35:02 
 2ND REVIEW FBC-2020 RES. GAS
 PERMIT- 21081166
 1/18/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SUBMIT THE CORRECT PERMIT APPLICATION FOR THE
 PROJECT AT 264 ALPINE RD. THE SUBMITTED APPLICATION ON
 FILE HAS INCORRECT OWNER???S NAME AND PROJECT ADDRESS-
 291 AUSTIN LN.- SEC. 107.2.1 WPB.
  
 2) PLEASE NOTE THE GAS FLOOR PLAN DRAWING IS NOT
 DIGITALLY SIGNED AND SEALED BY THE ENGINEER OF RECORD
 AS REQUIRED BY FL. STATUTE 471.025 & SEC. 61G15-23.005
 FAC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-12-22 Cont ID  
Sent By ccole Date 2022-12-22 Time 11:01 Rev Time 0.00
Received By ccole Date 2022-12-22 Time 08:34 Sent To  
Notes
2022-12-22 11:03:25 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 21081166
 12/22/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE REVIEW THE
 FOLLOWING COMMENTS AND IF YOU QUESTIONS, PLEASE CONTACT
 ME.
  
 1) THE SUBMITTED PERMIT APPLICATION FOR THE GAS PIPING
 AT 264 ALPINE RD. HAS INCORRECT PROJECT ADDRESS- 291
 AUSTIN LANE AND INCORRECT PRIMARY PERMIT- 21081542. THE
 PRIMARY PERMIT IS 21071257. PLEASE SUBMIT A NEW
 APPLICATION WITH CORRECT INFORMATION.
  
 2) GAS RISER- SEC. 107.2.1 & 107.3.5.3 WPB.
  
 A) THE SURVEY SHOWS A FUTURE GENERATOR. SHOW THE GAS
 LINE TO THE GENERATOR, LABEL THE LOCATION AS FUTURE
 GENERATOR AND PROVIDE A GAS-TIGHT CAP, SHOW THE BTU
 LOAD AND ADD IT TO THE TOTAL LOAD.
  
 B) A SEPARATE PERMIT IS REQUIRED FOR INSTALLATION OF
 THE POOL HEATER. PLEASE LABEL THE LOCATION AS FUTURE
 POOL HEATER AND SHOW A GAS-TIGHT CAP.
  
 C) THE SURVEY INDICATES THE BBQ AS FUTURE. PLEASE LABEL
 THE BBQ AS FUTURE AND SHOW A GAS-TIGHT CAP AT THE
 LOCATION.
  
 3) PROVIDE A FLOOR PLAN DRAWING SHOWING THE LOCATIONS
 OF ALL THE APPLIANCES. THE SUBMITTED SURVEY DOES NOT
 SHOW THE ROOM LOCATIONS AND ROOM DIMESNIONS WHERE THE
 RANGE AND DRYER WILL BE INSTALLED.
  
 A) INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO THE
 RANGE AND PROVIDE CALCULATIONS- SEC. G2407.1 FBC RES.
  
 B) INDICATE HOW COMBUSTION AIR OR MAKEUP AIR WILL BE
 PROVIDED TO THE DRYER AND PROVIDE CALCULATIONS- SECS.
 G2407.1 & G2439.5 FBC RES. FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By lcrespo Date 2021-09-01 Time 09:59 Rev Time 0.00
Received By lcrespo Date 2021-09-01 Time 09:58 Sent To  
Notes
2021-09-01 11:10:5209/01/21 1 ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE HAVE A SIGNATURE ON THE ISOMETRIC
 DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT IN
 ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE
 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.1 GENERAL.
  
 2. WOULD YOU PLEASE SHOW THE CORRESPONDING EHD NUMBER
 OF THE CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE
 SIZE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM; ADD THE FUTURE, PLEASE. REFER
 TO THE 2020 FBC RES. SEC. G2413.
  
 4. THIS IS A TWO-STORY HOME, AND THE LAYOUT OF THE GAS
 ON THE ISOMETRIC IS NOT UNDERSTANDABLE. WOULD YOU
 PLEASE PROVIDE A MORE COMPREHENSIVE GAS RISER DIAGRAM
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS?
  
 5. WOULD YOU PLEASE PROVIDE MANUFACTURES SPECIFICATIONS
 FOR ALL GAS EQUIPMENT FUTURE AND NEW PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 6. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE
 HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. GAS UNITS MAY REQUIRE CONDENSATE, AND THEY NEED TO
 BE 1' AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC
 R318.5. A NOTE ON ISO WILL BE OK.
  
 8. HOT WATER LINES NOT IN CONDITION SPACE NEED TO BE
 INSULATED WITH A MINIMUM R-3 PER THE 2020 FBC SEC. RE
 403.5.3. A NOTE ON ISO WILL BE OK.
  
 9. THIS TANK-LESS UNIT CALL FOR A 10.5 INCHES WATER
 COLUMN, AND THE SERVICE METER DISCHARGES IS A 12 INCH
 WATER COLUMN REQUIRING A REGULATOR FOR THIS UNIT AS PER
 THE MANUFACTURER'S SPECIFICATION. PLEASE SHOW THE
 REGULATOR ON ISO. REGULATORS INSTALLED ON THE EXTERIOR
 OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 10. WOULD YOU PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1 FOOT OF EITHER SIDE PER THE 2020 FBC RES?
 SEC G2421.2.
  
 11. WOULD YOU PLEASE SHOW THE SHUTOFF VALVE ON GAS
 ISOMERIC PER THE 2020 FBC FG SEC. 409.5 OR 2020 FBC
 RES. SEC. G2420.5.
  
 12. THE SHUT-OFF INSIDE SHALL BE ACCESSIBLE WITHOUT
 MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202)
 GD, ACCESS. A NOTE ON ISO WILL BE OK.
  
 13. SHOW DRIP LEG ON EQUIPMENT INSTALLED, EXCEPT FOR
 APPLIANCES, RANGE, DRYERS & OD GRILLS PER THE 2020 FBC
 FG 408.2 OR 2020 FBC RES. SEC. G2419.2.
  
 14. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2020
 FBC RES. SEC. G2407.1 AND G2439.4 (CLOTHES DRYERS).
  
 15. IF USING LOVERS FOR COMBUSTION AIR, PLEASE SHOW THE
 LOCATION OF THE LOUVERS THAT ARE BEING INSTALLED. THE
 LOUVERS CANNOT BE LOCATED ON AN EXTERIOR WALL THAT IS
 FIRE RATED AS THE FIRE RATING OF THE WALL MUST BE
 MAINTAINED PER THE WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 16. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE FBC
 RES. SEC. G2413.2 AND G2404.3.
  
 17. NEED A SHUTOFF VALVE AND HARD CAP FOR FUTURE RANGE
 SHOW ON GAS ISOMERIC SHUTOFF 2020 FBC RES. SEC.
 G2401.1.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-01-27 Cont ID  
Sent By mpeterso Date 2023-01-27 Time 13:58 Rev Time 0.00
Received By mpeterso Date 2023-01-23 Time 12:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2023-01-19 Time   Rev Time 0.00
Received By aoliver Date 2023-01-17 Time 07:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-12-22 Time   Rev Time 0.00
Received By aoliver Date 2022-12-22 Time 07:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-01 Cont ID  
Sent By lcrespo Date 2021-09-01 Time 11:12 Rev Time 0.00
Received By lcrespo Date 2021-08-25 Time 13:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status N Date 2023-01-24 Cont ID  
Sent By ccole Date 2023-01-24 Time 16:47 Rev Time 0.00
Received By ccole Date 2023-01-24 Time 16:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2023-01-19 Cont ID  
Sent By ccole Date 2023-01-19 Time 08:35 Rev Time 0.00
Received By ccole Date 2023-01-19 Time 07:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-12-22 Cont ID  
Sent By ccole Date 2022-12-22 Time 11:01 Rev Time 0.00
Received By ccole Date 2022-12-22 Time 08:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-09-01 Cont ID  
Sent By lcrespo Date 2021-09-01 Time 11:12 Rev Time 0.00
Received By lcrespo Date 2021-09-01 Time 11:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-01-27 Cont ID  
Sent By mpeterso Date 2023-01-27 Time 13:58 Rev Time 0.00
Received By mpeterso Date 2023-01-27 Time 13:54 Sent To  
Notes
2023-01-24 17:08:54ON HOLD, WORKING WITH THE CONTRACTOR TO GET THE DIG.
 SIGNED AND SEALED PLAN SENT TO ME.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2023-01-19 Cont ID  
Sent By ccole Date 2023-01-19 Time 08:36 Rev Time 0.00
Received By ccole Date 2023-01-19 Time 08:35 Sent To  
Notes
2023-01-19 08:39:23SIGNATURE REVIEW
 1/18/23
  
 1) THE GAS FLOOR PLAN SHEET IS NOT DIGITALLY SIGNED AND
 SEALED BY THE ENGINEER OF RECORD RICHARD BOYETTE AS
 REQUIRED BY FL. STATUTE 471.025, AND SEC. 61G15-23.005
 FAC.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
  
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  