Plan Review Details - Permit 21081144
Plan Review Stops For Permit 21081144
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2021-10-25 Cont ID  
Sent By rmcphers Date 2021-10-25 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2021-10-25 Time 14:56 Sent To  
Notes
2021-10-25 14:57:49NO BUILDING OR STRUCTURAL DRAWINGS AT THIS TIME.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2021-10-11 Cont ID  
Sent By fgiaquin Date 2021-10-11 Time 21:56 Rev Time 0.00
Received By fgiaquin Date 2021-10-11 Time 20:42 Sent To  
Notes
2021-10-11 21:56:33NO ELECTRICAL REVIEWED OR APPROVED. ELEC WORK FOR
 REFRIDGERATION SYSTEM TO BE DONE FROM MAIIN ELECTRICAL
 CONTRACTOR SUBCONTRACTOR

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 08:45 Rev Time 0.00
Received By medwards Date 2021-10-26 Time 11:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-25 Cont ID  
Sent By rmcphers Date 2021-10-25 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2021-10-04 Time 13:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 08:45 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 08:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-05 Cont ID  
Sent By medwards Date 2021-10-05 Time 15:03 Rev Time 0.00
Received By medwards Date 2021-10-05 Time 15:00 Sent To  
Notes
2021-10-05 15:12:001) PLEASE PROVIDE THE REQUIRED INFORMATION FOR
 ALLOWABLE REFRIGERANT QUANTITY BASED ON TYPE OF
 REFRIGERANT SYSTEM CLASSIFICATION AND OCCUPANCY FOR
 EACH SYSTEM. FBC M 1102.1- 3
  
 2) PLEASE ADD THE FOLLOWING NOTE TO THE DRAWINGS: FBC M
 1108.4 DECLARATION. A CERTIFICATE OF TEST SHALL BE
 PROVIDED FOR ALL SYSTEMS CONTAINING 55 POUNDS (25 KG)
 OR MORE OF REFRIGERANT. THE CERTIFICATE SHALL GIVE THE
 NAME OF THE REFRIGERANT AND
 THE FIELD TEST PRESSURE APPLIED TO THE HIGH SIDE AND
 THE LOW SIDE OF THE SYSTEM. THE CERTIFICATION OF TEST
 SHALL BE SIGNED BY THE INSTALLER AND SHALL BE MADE PART
 OF THE PUBLIC RECORD.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-28 Cont ID  
Sent By medwards Date 2021-10-28 Time 08:45 Rev Time 0.00
Received By medwards Date 2021-10-28 Time 08:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 11:44 Rev Time 0.00
Received By mpeterso Date 2021-10-25 Time 11:44 Sent To  
Notes
2021-10-25 11:44:36REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED