| 2021-09-07 08:00:06 | 2ND REVIEW FBC-2020 MECHANICAL |
| | PERMIT-21081124 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION |
| | FBC FG- FLORIDA FUEL GAS |
| | FBC EX- FLORIDA EXISTING BUILDING CODE |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE THE CALCULATIONS AND INFORMATION FOR |
| | THE REFRIGERATION SYSTEMS PER FBC M 1102 BELOW: |
| | |
| | SECTION 1102 |
| | SYSTEM REQUIREMENTS |
| | 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE |
| | REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS, |
| | LOCATION LIMITATIONS, AND FIELD PRESSURE TEST |
| | REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS: |
| | 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION, |
| | IN ACCORDANCE WITH SECTION 1103.3. |
| | |
| | 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN |
| | ACCORDANCE WITH SECTION 1103.1. |
| | |
| | 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF |
| | REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON |
| | TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND |
| | OCCUPANCY. |
| | |
| | 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN |
| | ACCORDANCE WITH SECTION 1104. |
| | |
| | 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND |
| | INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF |
| | CHAPTER 3. |
| | |
| | 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND |
| | APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH |
| | SECTION 1108. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |