Plan Review Details - Permit 21081124
Plan Review Stops For Permit 21081124
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-22 Cont ID  
Sent By mpeterso Date 2021-10-22 Time 13:24 Rev Time 0.00
Received By mpeterso Date 2021-10-22 Time 13:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-07 Cont ID  
Sent By medwards Date 2021-10-07 Time 07:41 Rev Time 0.00
Received By medwards Date 2021-10-06 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-07 Cont ID  
Sent By medwards Date 2021-09-07 Time 08:02 Rev Time 0.00
Received By medwards Date 2021-09-03 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 09:29 Rev Time 0.00
Received By medwards Date 2021-08-25 Time 13:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-10-07 Cont ID  
Sent By medwards Date 2021-10-07 Time 07:39 Rev Time 0.00
Received By medwards Date 2021-10-07 Time 07:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-09-07 Cont ID  
Sent By medwards Date 2021-09-07 Time 07:59 Rev Time 0.00
Received By medwards Date 2021-09-07 Time 07:59 Sent To  
Notes
2021-09-07 08:00:062ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21081124
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE CALCULATIONS AND INFORMATION FOR
 THE REFRIGERATION SYSTEMS PER FBC M 1102 BELOW:
  
 SECTION 1102
 SYSTEM REQUIREMENTS
 1102.1 GENERAL. THE SYSTEM CLASSIFICATION, ALLOWABLE
 REFRIGERANTS, MAXIMUM QUANTITY, ENCLOSURE REQUIREMENTS,
 LOCATION LIMITATIONS, AND FIELD PRESSURE TEST
 REQUIREMENTS SHALL BE DETERMINED AS FOLLOWS:
 1. DETERMINE THE REFRIGERATION SYSTEM'S CLASSIFICATION,
 IN ACCORDANCE WITH SECTION 1103.3.
  
 2. DETERMINE THE REFRIGERANT CLASSIFICATION IN
 ACCORDANCE WITH SECTION 1103.1.
  
 3. DETERMINE THE MAXIMUM ALLOWABLE QUANTITY OF
 REFRIGERANT IN ACCORDANCE WITH SECTION 1104, BASED ON
 TYPE OF REFRIGERANT, SYSTEM CLASSIFICATION AND
 OCCUPANCY.
  
 4. DETERMINE THE SYSTEM ENCLOSURE REQUIREMENTS IN
 ACCORDANCE WITH SECTION 1104.
  
 5. REFRIGERATION EQUIPMENT AND APPLIANCE LOCATION AND
 INSTALLATION SHALL BE SUBJECT TO THE LIMITATIONS OF
 CHAPTER 3.
  
 6. NON-FACTORY-TESTED, FIELD-ERECTED EQUIPMENT AND
 APPLIANCES SHALL BE PRESSURE TESTED IN ACCORDANCE WITH
 SECTION 1108.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 09:27 Rev Time 0.00
Received By medwards Date 2021-08-28 Time 09:27 Sent To  
Notes
2021-08-28 09:28:34PLEASE SUBMIT DRAWINGS FOR THIS REFRIGERATION SYSTEM.
 FBC 107.2.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-22 Cont ID  
Sent By mpeterso Date 2021-10-22 Time 13:23 Rev Time 0.00
Received By mpeterso Date 2021-10-22 Time 13:23 Sent To  
Notes
2021-10-22 13:23:44REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-07 Cont ID  
Sent By medwards Date 2021-09-07 Time 08:01 Rev Time 0.00
Received By medwards Date 2021-09-07 Time 08:01 Sent To  
Notes
2021-09-07 08:02:36PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 (INCLUDING THE SUPPORTING DOCUMENTS) IS REQUIRED TO BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE
 WITH THE PROPER THIRD PARTY VERIFICATION. PROVIDE
 CORRECTION. F.S.471, 481
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-08-28 Cont ID  
Sent By medwards Date 2021-08-28 Time 09:28 Rev Time 0.00
Received By medwards Date 2021-08-28 Time 09:28 Sent To  
Notes
2021-08-28 09:29:19NO DRAWINGS WERE SUBMITTED FOR THIS REFRIGERATION
 REVIEW. ME