Plan Review Details - Permit 21081110
Plan Review Stops For Permit 21081110
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-10-05 Cont ID  
Sent By jwitmer Date 2021-10-05 Time 13:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-09-21 Cont ID  
Sent By jwitmer Date 2021-09-21 Time 16:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-21 16:56:53WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21081110
 ADD: 7106 S. DIXIE HWY.
 CONT: CAMPBELL GENERAL CONTRACTING
 TEL: 772-486-3764
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. SEPT. 21ST/2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THE PERMIT APPLICATION DOES NOT
 INDICATE IF THIS STRUCTURE IS TO BE CONSIDERED
 TEMPORARY IN NATURE OR TO BE CONSIDERED A PERMANENT
 STRUCTURE. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 SECTION 108.1. THE BUILDING OFFICIAL IS AUTHORIZED TO
 ISSUE A PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY
 USES. SUCH PERMITS SHALL BE LIMITED AS TO TIME OF
 SERVICE BUT SHALL NOT BE PERMITTED FOR MORE THAN 6
 MONTHS. THE BUILDING OFFICIAL IS AUTHORIZED TO GRANT
 EXTENSIONS FOR DEMONSTRATED CAUSE. PLEASE PROVIDE WHAT
 THE USAGE WILL BE (OCCUPANCY TYPE).
  
 108.2 CONFORMANCE. TEMPORARY STRUCTURES AND USES SHALL
 CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, ACCESSIBILITY, LIGHT. VENTILATION AND
 SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO
 ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
  
 2) 2ND REQUEST. IF THE STRUCTURE IS GOING TO BE
 PERMANENT THEN THE STRUCTURE WILL NEED TO SHOW
 COMPLIANCE WITH 108.2 CONFORMANCE. PERMANENT STRUCTURES
 AND USES SHALL CONFORM TO THE STRUCTURAL STRENGTH, FIRE
 SAFETY, MEANS OF EGRESS, ACCESSIBILITY, LIGHT.
 VENTILATION AND SANITARY REQUIREMENTS OF THIS CODE AS
 NECESSARY TO ENSURE PUBLIC HEALTH, SAFETY AND GENERAL
 WELFARE.
  
 3) A STRUCTURAL ENGINEER WILL NEED TO ENGINEER AND OR
 CALCULATE ANCHORAGE OF THIS UNIT IN CONFORMANCE WITH
 THE 2020 FBC-BUILDING SECTION 1604.8 ANCHORAGE. THE
 SHEET S-2 NOTES:
  
  
 3A) NOTE 3 GROUND ANCHORS ARE TO HAVE A MINIMUM TENSION
 CAPACITY OF 2,250 LBS, CONTRACTOR TO MANUFACTURERS
 SPECS.
  
 3B) GALVANIZED WIRE ROPE IS TO HAVE A MINIMUM TENSION
 CAPACITY OF 2,250 LBS. THE DESIGNER OF RECORD HAS NOT
 INDICATED THE SIZE OF WIRE ROPE NOR THE TENSILE
 STRENGTH.
  
 3C) THE DESIGNER OF RECORD HAS NOT IDENTIFIED THE TYPE
 OF FASTENERS AT EACH END OF THE WIRE ROPE, NOR THE SIZE
 AND CAPACITY OF FASTENERS, ARE MULTIPLE FASTENERS
 REQUIRED AT EACH END?
  
 1ST REVIEW COMMENTS. BUILDINGS AND OTHER STRUCTURE, AND
 PORTIONS THEREOF, SHALL BE PROVIDED WITH ANCHORAGE IN
 ACCORDANCE WITH SECTIONS 1604.8.1 THROUGH 1604.8.3 AS
 APPLICABLE. PERMANENT BUILDINGS HAVE FOUNDATIONS, SEE
 1809.4 DEPTH AND WIDTH OF FOUNDATIONS.
  
 4) THE ENGINEER WILL HAVE TO ENGINEER THE ANCHORAGE TO
 THE PROPER WIND ZONE TO KEEP THE STRUCTURE FROM SLIDING
 AND OR TIPPING OVER. 2020 FBC-BUILDING CODE 1609.1.1
 DETERMINATION OF WIND LOADS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 17:41 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 17:39:59WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21081110
 ADD: 7106 S. DIXIE HWY.
 CONT: CAMPBELL GENERAL CONTRACTING
 TEL: 772-486-3764
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 01/2021
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION DOES NOT INDICATE IF THIS
 STRUCTURE IS TO BE CONSIDERED TEMPORARY IN NATURE OR TO
 BE CONSIDERED A PERMANENT STRUCTURE. 2020 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION SECTION 108.1. THE BUILDING OFFICIAL
 IS AUTHORIZED TO ISSUE A PERMIT FOR TEMPORARY
 STRUCTURES AND TEMPORARY USES. SUCH PERMITS SHALL BE
 LIMITED AS TO TIME OF SERVICE BUT SHALL NOT BE
 PERMITTED FOR MORE THAN 6 MONTHS. THE BUILDING OFFICIAL
 IS AUTHORIZED TO GRANT EXTENSIONS FOR DEMONSTRATED
 CAUSE.
  
 108.2 CONFORMANCE. TEMPORARY STRUCTURES AND USES SHALL
 CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, ACCESSIBILITY, LIGHT. VENTILATION AND
 SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO
 ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
  
 2) IF THE STRUCTURE IS GOING TO BE PERMANENT THEN THE
 STRUCTURE WILL NEED TO SHOW COMPLIANCE WITH 108.2
 CONFORMANCE. PERMANENT STRUCTURES AND USES SHALL
 CONFORM TO THE STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, ACCESSIBILITY, LIGHT. VENTILATION AND
 SANITARY REQUIREMENTS OF THIS CODE AS NECESSARY TO
 ENSURE PUBLIC HEALTH, SAFETY AND GENERAL WELFARE.
  
 3) A STRUCTURAL ENGINEER WILL NEED TO ENGINEER AND OR
 CALCULATE ANCHORAGE OF THIS UNIT IN CONFORMANCE WITH
 THE 2020
 FBC-BUILDING SECTION 1604.8 ANCHORAGE. BUILDINGS AND
 OTHER STRUCTURE, AND PORTIONS THEREOF, SHALL BE
 PROVIDED WITH ANCHORAGE IN ACCORDANCE WITH SECTIONS
 1604.8.1 THROUGH 1604.8.3 AS APPLICABLE. PERMANENT
 BUILDINGS HAVE FOUNDATIONS, SEE 1809.4 DEPTH AND WIDTH
 OF FOUNDATIONS.
  
 4) THE ENGINEER WILL HAVE TO ENGINEER THE ANCHORAGE TO
 THE PROPER WIND ZONE TO KEEP THE STRUCTURE FROM SLIDING
 AND OR TIPPING OVER. 2020 FBC-BUILDING CODE 1609.1.1
 DETERMINATION OF WIND LOADS.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-26 Cont ID  
Sent By   Date 2021-08-26 Time   Rev Time 0.00
Received By bdolan Date 2021-08-26 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-14 Cont ID  
Sent By lmarchan Date 2021-10-14 Time 10:54 Rev Time 0.00
Received By lmarchan Date 2021-09-30 Time 09:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-21 Cont ID  
Sent By jwitmer Date 2021-09-21 Time 16:58 Rev Time 0.00
Received By jwitmer Date 2021-09-16 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-09 Cont ID  
Sent By lmarchan Date 2021-09-09 Time 16:22 Rev Time 0.00
Received By lmarchan Date 2021-08-23 Time 09:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-10-05 Cont ID  
Sent By jwitmer Date 2021-10-05 Time 13:14 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-21 Cont ID  
Sent By jwitmer Date 2021-09-21 Time 16:58 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-21 16:58:16FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 DOCUMENT IN THE FILE FOLDER, SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED ON DIGITALLY SIGNED AND
 SEALED ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 17:40 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 17:41:07NO PAPERWORK WAS SUBMITTED TO REVIEW SIGNATURES.

Review Stop Z ZONING
Rev No 3 Status P Date 2021-10-14 Cont ID  
Sent By llouie Date 2021-10-14 Time   Rev Time 0.00
Received By llouie Date 2021-10-14 Time   Sent To  
Notes
2021-10-14 10:45:16ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) THE EXISTING FENCE SHALL BE PROVIDED WITH MATERIAL
 THAT WILL ALLOW FOR FULL SCREENING OF THE STORAGE
 CONTAINER FROM ADJACENT USES/PROPERTIES. (SEE MARKUP IN
 PERMIT PLAN)

Review Stop Z ZONING
Rev No 2 Status P Date 2021-09-16 Cont ID  
Sent By llouie Date 2021-09-16 Time   Rev Time 0.00
Received By llouie Date 2021-09-16 Time   Sent To  
Notes
2021-09-16 11:24:17ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) THE EXISTING FENCE SHALL BE PROVIDED MATERIAL THAT
 WILL ALLOW FOR FULL SCREENING OF THE STORAGE CONTAINER
 FROM ADJACENT USES/PROPERTIES (SEE MARKUP IN PERMIT
 PLAN).
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-09 Cont ID  
Sent By llouie Date 2021-09-09 Time   Rev Time  
Received By llouie Date 2021-09-09 Time   Sent To  
Notes
2021-09-09 15:31:06** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) SHOW SETBACK DIMENSIONS FROM THE PROPOSED CONTAINER
 TO THE PROPERTY LINE(S). [ZLDR S.94-144]
  
 2.) FULL SCREENING OF THE PROPOSED CONTAINER (FROM
 BREVARD AVENUE AND THE PROPERTIES TO THE NORTH AND
 SOUTH) IS REQUIRED. [ZLDR S.94-315]
  
 3.) HOW TALL IS THE PROPOSED CONTAINER? ARE THERE
 ELEVATIONAL DRAWINGS OF THE CONTAINER?
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: NC
  
  