Plan Review Details - Permit 21081037
Plan Review Stops For Permit 21081037
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-09-13 Cont ID  
Sent By pvalenti Date 2021-09-13 Time 16:50 Rev Time 0.00
Received By pvalenti Date 2021-09-13 Time 16:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-28 Cont ID  
Sent By jleahy Date 2021-09-28 Time 14:40 Rev Time 0.00
Received By jleahy Date 2021-09-28 Time 13:48 Sent To  
Notes
2021-09-28 14:40:11ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) 70 AMPERE TAP ON LOAD SIDE OF MAIN SHALL COMPLY WITH
 705.12
  
 705.12 (B) LOAD SIDE. THE OUTPUT OF AN INTERCONNECTED
 ELECTRIC POWER SOURCE SHALL BE PERMITTED TO BE
 CONNECTED TO THE LOAD
 SIDE OF THE SERVICE DISCONNECTING MEANS OF THE OTHER
 SOURCE(S) AT ANY DISTRIBUTION EQUIPMENT ON THE
 PREMISES. WHERE DISTRIBUTION
 EQUIPMENT, INCLUDING SWITCHGEAR, SWITCHBOARDS, OR
 PANELBOARDS, IS FED SIMULTANEOUSLY BY A PRIMARY
 SOURCE(S) OF
 ELECTRICITY AND ONE OR MORE OTHER POWER SOURCE(S), AND
 WHERE THIS DISTRIBUTION EQUIPMENT IS CAPABLE OF
 SUPPLYING MULTIPLE
 BRANCH CIRCUITS OR FEEDERS, OR BOTH, THE
 INTERCONNECTING PROVISIONS FOR OTHER POWER SOURCES
 SHALL COMPLY WITH 705.12(B)(1)
 THROUGH (B)(5).
  
 2) BOX BELOW 200A PANEL ON RISER? WHAT IS IT FOR?
  
 3) POLARIS TAPS IN METERMAIN COMBO? TAPPING WHAT?
  
 4) IS VALUE $5K OR $55K ?

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-28 Cont ID  
Sent By jleahy Date 2021-09-28 Time 14:40 Rev Time 0.00
Received By jleahy Date 2021-08-25 Time 14:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-13 Cont ID  
Sent By pvalenti Date 2021-09-13 Time 16:50 Rev Time 0.00
Received By pvalenti Date 2021-09-13 Time 16:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-20 Cont ID  
Sent By rthermid Date 2021-09-20 Time   Rev Time  
Received By rthermid Date 2021-09-20 Time   Sent To I
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved