Plan Review Details - Permit 21081012
Plan Review Stops For Permit 21081012
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2021-09-13 Cont ID  
Sent By shill Date 2021-09-13 Time 18:09 Rev Time 0.00
Received By shill Date 2021-09-13 Time 18:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-09-08 Cont ID  
Sent By jleahy Date 2021-09-08 Time 15:26 Rev Time 0.00
Received By jleahy Date 2021-09-08 Time 15:26 Sent To  
Notes
2021-09-08 15:28:07CHANGED PERMIT TYPE IN ORDER TO KEEP BALL ROLLING,
 CONTRACTOR IN PROCESS OF SUBMITTING A NEW APPLICATION.
 JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jleahy Date 2021-09-07 Time 14:42 Rev Time 0.00
Received By jleahy Date 2021-09-07 Time 14:38 Sent To  
Notes
2021-09-07 14:42:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SCOPE AND PLANS DO NOT MATCH.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-08 Cont ID  
Sent By pleduc Date 2021-09-08 Time   Rev Time 0.00
Received By pleduc Date 2021-09-08 Time 15:55 Sent To  
Notes
2021-09-08 15:56:36CONTACTED BY APPLICANT, APPLICATION CHANGED TO ACCESS
 CONTROL, AND TO EXPEDITE.
  
 PASSED 9/8/21
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-08-26 Cont ID  
Sent By pleduc Date 2021-08-26 Time   Rev Time 0.00
Received By pleduc Date 2021-08-26 Time 12:37 Sent To  
Notes
2021-08-26 12:42:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE APPLICATION INDICATES THE INSTALLATION OF A
 CELLULAR COMMUNICATION DEVICE. THE PLAN SHEETS INDICATE
 CARD READERS/ACCESS CONTROL.
  
 PLEASE REVIEW, CORRECT AND RESUBMIT
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-09-20 Time   Rev Time 0.00
Received By aoliver Date 2021-09-20 Time 14:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-20 Cont ID  
Sent By pvalenti Date 2021-09-20 Time 07:49 Rev Time 0.00
Received By pvalenti Date 2021-09-15 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-13 Cont ID  
Sent By shill Date 2021-09-13 Time 18:09 Rev Time 0.00
Received By shill Date 2021-08-25 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-08-30 Cont ID  
Sent By medwards Date 2021-08-30 Time 15:30 Rev Time 0.00
Received By medwards Date 2021-08-30 Time 15:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-09-20 Cont ID  
Sent By ccole Date 2021-09-20 Time 15:39 Rev Time 0.00
Received By ccole Date 2021-09-20 Time 15:38 Sent To  
Notes
2021-09-20 15:40:47 
 REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE- CLC.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-20 Cont ID  
Sent By pvalenti Date 2021-09-20 Time 07:47 Rev Time 0.00
Received By pvalenti Date 2021-09-20 Time 07:41 Sent To  
Notes
2021-09-20 07:49:38CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTI
  
 SIGNATURE REVIEW DENIED:
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By jleahy Date 2021-09-07 Time 14:40 Rev Time 0.00
Received By jleahy Date 2021-09-07 Time 14:38 Sent To  
Notes
2021-09-07 14:42:04ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS ARE FOR ACCESS CONTROL NOT WHAT PERMIT COPE IS
 FOR.