| 2021-10-05 13:15:00 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21081001 |
| | 10/5/2021 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE PROVIDE A POOL PLUMBING DEMOLITION PLAN |
| | SHOWING ALL COMPONENTS OF THE RECIRCULATION SYSTEM- |
| | PIPING AND EQUIPMENT- THAT ARE BEING REMOVED AND |
| | REPLACED. |
| | |
| | 2) M1 & M2: PROVIDE TDH CALCULATIONS AND THE PUMP CURVE |
| | FOR THE NEW PUMP- SECTION 454.1.6.5.4 FBC B. |
| | |
| | 3) M1 & M2: PROVIDE AN EQUIPMENT SCHEDULE FOR THE PUMP |
| | AND FILTER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- |
| | SECTIONS 454.1.6.5.4 & 454.1.6.5.5 FBC P. |
| | |
| | 4) M1 & M2: PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN |
| | FOR THE MAIN DRAIN AND COVER AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS SHOWING CONFORMANCE WITH THE ANSI/APSP |
| | 16 STANDARD- 454.1.6.5.10.2 FBC P. |
| | |
| | 5) M1 & M2: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | RECIRCULATION AND TREATMENT EQUIPMENT INCLUDING THE |
| | TANKS, CONTROLLERS, AND FEEDERS SHOWING THE EQUIPMENT |
| | CONFORMS WITH REQUIRED STANDARDS NSF/ANSI STANDARD 50, |
| | CIRCULATION SYSTEM COMPONENTS AND RELATED MATERIALS FOR |
| | SWIMMING POOL, SPAS/HOT TUBS, DATED APRIL 2007- SEC. |
| | 454.1.6.5.1 FBC B. |
| | |
| | 6) M1 & M2: PLEASE PROVIDE THE POOL DIMENSIONS, SQUARE |
| | FOOT AREA, AND THE POOL TURNOVER RATE- SEC. 454.1.6.5.3 |
| | FBC. |
| | |
| | 7) M1 & M2: PROVIDE DIMENSIONED GUTTER INSTALLATION |
| | DETAILS- SEC. 454.1.6.5.3.1- 454.1.6.5.3.1.3 FBC B. |
| | |
| | 8) M1 & M2: PROVIDE THE FLOW VELOCITY OF THE POOL INLET |
| | PIPING- SEC. 454.1.6.5.8 FBC B. |
| | |
| | 9) M1 & M2: PROVIDE A POOL INLET INSTALLATION DETAIL- |
| | SEC. 454.1.6.5.9 FBC B. |
| | |
| | 10) M2: SHOW THE SPACING MEASUREMENTS OF THE INLETS- |
| | SEC. 454.1.6.5.9.1 FBC B. |
| | |
| | 11) M21 & M2 VACUUM SYSTEM: PROVIDE EQUALIZER LINE AND |
| | VALVE INSTALLATION DETAILS- SEC. 454.1.6.5.12 FBC B. |
| | THE EQUALIZER VALVE SHALL BE A SPRING-LOADED VERTICAL |
| | CHECK VALVE THAT WILL NOT ALLOW DIRECT SUCTION ON THE |
| | EQUALIZER LINE. FLOAT VALVES ARE PROHIBITED. SHOW THE |
| | EQUALIZER LINE WILL BE INSTALLED AT LEAST 1 FOOT BELOW |
| | THE NORMAL POOL WATER LEVEL AND THE EQUALIZER LINE |
| | INLET WILL BE PROTECTED BY AN ANSI/APSP-16 COMPLIANT |
| | COVER/GRATE. |
| | |
| | 12) M1 & M2: PROVIDE A DIMENSIONED SECTION CUT OF THE |
| | POOL SHOWING THE LOCATION OF THE MAIN DRAIN WILL BE IN |
| | COMPLIANCE WITH SEC. 454.1.6.5.10 & 454.1.6.5.10.1 FBC |
| | B. |
| | |
| | 13) M2: SHOW THE LOCATIONS OF THE NEW FLOOR DRAINS AND |
| | PROVIDE A SANITARY DRAINAGE AND VENT ISOMETRIC DRAWING- |
| | SECTION 107.3.5.1.3 WPB AND SECTION 412.2 FBC P. |
| | |
| | 14) M2: PROVIDE TRAP SEAL PROTECTION FOR THE FLOOR |
| | DRAINS- SEC.1002.4 FBC P. |
| | |
| | 15) M2: INSTALLATION OF THE NEW FLOOR DRAINS MAY |
| | REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 16) M2: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| | SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| | SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| | APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | 17) M2: SHOW THE LOCATION OF THE HOSE BIB AND PROVIDE A |
| | WATER RISER- SEC. 107.3.5.1.3 WPB. PROVIDE AN EQUIPMENT |
| | SCHEDULE FOR THE HOSE BIB INDICATING MAKE AND MODEL, |
| | AND TYPE OF VACUUM BREAKER- SEC. 608.15.4.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |