Plan Review Details - Permit 21080941
Plan Review Stops For Permit 21080941
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By cthroop Date 2021-10-15 Time 08:24 Rev Time 0.00
Received By cthroop Date 2021-10-15 Time 06:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-24 Cont ID  
Sent By shill Date 2021-09-24 Time 17:10 Rev Time 0.00
Received By shill Date 2021-09-24 Time 17:10 Sent To  
Notes
2021-09-24 17:13:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PAGE 7 OF THE ENGINEERING CITES THE DESIGN CRITERIA
 OF FBC B 3105 WHICH REQUIRES THAT THE AWNING BE
 RETRACTED WHEN WINDS OVER 35MPH ARE ANTICIPATED, FABRIC
 TO BE REMOVED IN THE EVENT OF WINDS IN EXCESS OF 75
 MPH. HOW WILL THIS BE ACCOMPLISHED?
  
 FBC 107, PROVIDE THE FOLLOWING INFORMATION:
  
 PROVIDE INSTRUCTIONS ON FABRIC REMOVAL, INCLUDING TOOLS
 NECESSARY.
  
 WHO WILL BE RESPONSIBLE FOR REMOVING THE FABRIC?
  
 WILL THIS BE INCORPORATED INTO THE HOTEL O&M OR OTHER
 DOCUMENTS, HURRICANE PLAN?
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By jleahy Date 2021-10-15 Time 11:05 Rev Time 0.00
Received By jleahy Date 2021-10-15 Time 07:44 Sent To  
Notes
2021-10-15 11:06:05ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 ELECTRICAL PERMIT AND PLANS ARE REQUIRED FOR THIS
 PROJECT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 09:07 Rev Time 0.00
Received By jleahy Date 2021-09-27 Time 09:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-08 Cont ID  
Sent By pleduc Date 2021-10-08 Time   Rev Time 0.00
Received By pleduc Date 2021-10-08 Time 09:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-08-25 Cont ID  
Sent By pleduc Date 2021-08-25 Time   Rev Time 0.00
Received By pleduc Date 2021-08-25 Time 10:16 Sent To  
Notes
2021-08-25 11:04:11THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDCATIONS OF A COVERED STRUCTURE ON THE
 ROOF DECK OVER AN ASSEMBLY SEATING AREA.
  
 THERE ARE NO INDICATIONS OF REQUIRED FIRE SPRINKLER
 COVERAGE.
  
 FIRE SPRINKLER COVERAGE IS REQUIRED TO BE EXTENDED OVER
 THIS COVERED SEATING AREA.
  
 PLEASE REVIEW AND PROVIDE FOR FIRE SPRINKLER COVERAGE.
  
 AN APPLICABLE NOTE OF ACKNOWLEDGEMENT STATING "FIRE
 SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED" WILL BE
 ACCPETED.
  
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-15 Cont ID  
Sent By jleahy Date 2021-10-15 Time 11:06 Rev Time 0.00
Received By jleahy Date 2021-10-07 Time 16:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 11:21 Rev Time 0.00
Received By jleahy Date 2021-08-20 Time 13:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-15 Cont ID  
Sent By cthroop Date 2021-10-15 Time 08:32 Rev Time 0.00
Received By cthroop Date 2021-10-15 Time 06:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-24 Cont ID  
Sent By shill Date 2021-09-24 Time 17:32 Rev Time 0.00
Received By shill Date 2021-09-24 Time 17:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2021-10-12 Cont ID  
Sent By aaponte Date 2021-10-12 Time 09:53 Rev Time 0.00
Received By aaponte Date 2021-10-12 Time 09:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-09 Cont ID  
Sent By aaponte Date 2021-09-09 Time 16:15 Rev Time 0.00
Received By aaponte Date 2021-09-09 Time 16:15 Sent To  
Notes
2021-09-09 16:17:34PLEASE PROIVDE A 3D RENDERING ON THE PROPOSED CANOPY.
 IT IS HIGLY VISIBLE FROM THE STREET LEVEL AND IT WILL
 IMPACT THE EXTERIOR APPEARANCE OF THE BUILDING.
 PROPOSED CANOPY SHALL MAINTAIN THE OVERALL DESIGN OF
 THE BUILDING AND ROOF LINE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.