Plan Review Details - Permit 21080908
Plan Review Stops For Permit 21080908
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2022-01-06 Cont ID  
Sent By cpuell Date 2022-01-06 Time 10:13 Rev Time 0.00
Received By cpuell Date 2022-01-06 Time 10:13 Sent To  
Notes
2022-01-06 10:14:52GROUND FLOOR ADDRESSES ESTABLISHED, UNITS WILL BE
 ASSIGNED UNDER BUILDING PERMIT.

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2021-12-30 Cont ID  
Sent By cpuell Date 2021-12-30 Time 14:19 Rev Time 0.00
Received By cpuell Date 2021-12-30 Time 14:19 Sent To  
Notes
2021-12-30 14:21:05GROUND FLOOR ADDRESSES ESTABLISHED, ALL UNITS NEED TO
 BE ASSIGNED ADDRESSES, PLEASE CONTACT [email protected] OR
 CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-11-08 Cont ID  
Sent By cpuell Date 2021-11-08 Time 12:52 Rev Time 0.00
Received By cpuell Date 2021-11-08 Time 12:52 Sent To  
Notes
2021-11-08 12:54:12ADDRESS UPDATED:
  
 170 LAKEVIEW AVE ? RETAIL SPACE A
 180 LAKEVIEW AVE ? MAIN ENTRANCE (PRIMARY ADDRESS FOR
 PROJECT)
 190 LAKEVIEW AVE ? RETAIL SPACE B
 155 OKEECHOBEE BLVD ? OFFICE/READING ROOM
  
 RESIDENTIAL UNITS STILL NEED TO BE ADDRESSED. APPLICANT
 INFORMED THAT NEW SHEETS WOULD HAVE TO BE UPLOADED WITH
 THE CORRECT ADDRESS

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-10-31 Cont ID  
Sent By cpuell Date 2021-10-31 Time 12:16 Rev Time 0.00
Received By cpuell Date 2021-10-31 Time 12:16 Sent To  
Notes
2021-10-31 12:17:57ADDRESS WILL NEED TO BE ESTABLISHED FOR PROJECT AND
 RETAILS SPACES. PLEASE EMAIL A SITE PLAN SHOWING THE
 MAIN ENTRANCE TO THE BUILDING. PLEASE EMAIL TO
 [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 11:29 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 11:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-01 Cont ID  
Sent By rmcphers Date 2022-01-25 Time 14:47 Rev Time 0.00
Received By rmcphers Date 2022-01-25 Time 14:47 Sent To  
Notes
2022-01-25 14:48:32FOUNDATION ONLY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ENCLOSED BUILDING ENTRIES AND EXITS NEED TO BE
 RAISED TO THE DESIGN FLOOD ELEVATION - 2 FEET ABOVE THE
 BASE FLOOD ELEVATIONS. (PER BUILDING OFFICIAL)

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-07 Cont ID  
Sent By rmcphers Date 2022-01-07 Time 14:48 Rev Time 0.00
Received By rmcphers Date 2022-01-06 Time 16:28 Sent To  
Notes
2022-01-07 14:50:18FOUNDATION ONLY - AUDIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By rmcphers Date 2021-12-16 Time 16:21 Rev Time 0.00
Received By rmcphers Date 2021-12-16 Time 14:14 Sent To  
Notes
2021-12-16 16:21:33FOUNDATION ONLY - AUDIT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) EXTERIOR WALL AND OPENINGS - THE EXTERIOR WALL OF
 THE BUILDING ADJACENT TO THE EXISTING 2 STORY BUILDING
 SHOWS 12'9" SETBACK FROM PROPERTY LINE - PLEASE SHOW
 THE ALLOWABLE WALL OPENING CALCULATIONS PER FBC TABLE
 705.8
 DRAWING G-006 UNDER "FIRE AND SMOKE PROTECTION
 FEATURES" WALL FIRE SEPARATION DISTANCE CIRCLED IS
 INCORRECT. PLEASE CORRECT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-07 Cont ID  
Sent By jleahy Date 2022-01-07 Time 11:11 Rev Time 0.00
Received By jleahy Date 2022-01-07 Time 11:04 Sent To  
Notes
2022-01-07 11:12:14FOUNDATION PERMIT ONLY JLEAHY
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2021-11-08 Cont ID  
Sent By rrossano Date 2021-11-08 Time   Rev Time  
Received By rrossano Date 2021-11-08 Time   Sent To  
Notes
2021-11-08 11:29:22 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-11-03 Cont ID  
Sent By pleduc Date 2021-11-03 Time   Rev Time 0.00
Received By pleduc Date 2021-11-03 Time 09:56 Sent To  
Notes
2021-11-03 09:57:47FIRE PROVISO:
  
 SHEET A -101
  
 ***ENSURE FIRE PUMP ROOM HAS A FLOOR DRAIN TO SEWER
 SYSTEM.
  
 ***FIRE COMMAND ROOM WAS UNDER REVIEW TO BE MOVED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2021-11-03 Cont ID  
Sent By fmittner Date 2021-11-03 Time 16:56 Rev Time 0.00
Received By fmittner Date 2021-11-03 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-02-15 Cont ID  
Sent By shill Date 2022-02-15 Time 08:13 Rev Time 0.00
Received By shill Date 2022-02-11 Time 11:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-02-09 Cont ID  
Sent By aoliver Date 2022-02-09 Time 14:15 Rev Time 0.00
Received By aoliver Date 2022-02-03 Time 16:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-25 Cont ID  
Sent By rmcphers Date 2022-01-25 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2022-01-19 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-07 Cont ID  
Sent By rmcphers Date 2022-01-07 Time 14:56 Rev Time 0.00
Received By rmcphers Date 2021-12-29 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-17 Cont ID  
Sent By shill Date 2021-12-17 Time 07:02 Rev Time 0.00
Received By lcrespo Date 2021-11-24 Time 12:26 Sent To  
Notes
2021-12-03 19:16:54ROUTED TO BUILDING DIVISION AUDIT
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-29 Cont ID  
Sent By shill Date 2021-11-24 Time 12:26 Rev Time 0.00
Received By shill Date 2021-10-26 Time 07:49 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By lmarchan Date 2022-02-23 Time 16:42 Rev Time 0.00
Received By lmarchan Date 2022-01-26 Time 09:01 Sent To  
Notes
2022-02-23 13:30:25RECEIPT MU-2022-07094 - $747,548.73 PAID
2022-01-26 09:01:511/26/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By dbattles Date 2021-08-19 Time 10:43 Rev Time 0.00
Received By dbattles Date 2021-08-19 Time 10:43 Sent To  
Notes
2021-08-19 10:44:49109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status N Date 2022-01-25 Cont ID  
Sent By rmcphers Date 2022-01-25 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2022-01-25 Time 15:06 Sent To  
Notes
2022-01-25 15:07:52FLOOD ZONE = AE6
 PROPOSED LOWEST FLOOR ELEVATION = (9.60 NGVD) - 1.52
 PER SURVEY = 8.08 NAVD
  
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-01-07 Cont ID  
Sent By rmcphers Date 2022-01-07 Time 14:23 Rev Time 0.00
Received By rmcphers Date 2022-01-07 Time 14:03 Sent To  
Notes
2022-01-07 14:22:53FLOOD ZONE = AE6
 PROPOSED LOWEST FLOOR ELEVATION = (9.60 NGVD) - 1.52
 PER SURVEY = 8.08 NAVD
  
 CORRECTIONS NEEDED =
  
 1) THERE ARE ROOMS THAT ARE BELOW THE REQUIRED LOWEST
 FLOOR ELEVATION - SUCH AS RESTROOM 01-307 (NOT
 NUMBERED), IT POE 01-305, AND IT POE 01-308 (NOT SURE
 WHAT "IT POE" MEANS) - ONLY VEHICLE PARKING BUILDING
 ACCESS AND STORAGE CAN BE LOWER THAN THE LOWEST FLOOR
 ELEVATION - FBC SECTION 202 LOWEST FLOOR. THE LOWEST
 FLOOR OF THE LOWEST ENCLOSED AREA, INCLUDING BASEMENT,
 BUT EXCLUDING ANY UNFINISHED OR FLOOD-RESISTANT
 ENCLOSURE, USABLE SOLELY FOR VEHICLE PARKING, BUILDING
 ACCESS OR LIMITED STORAGE PROVIDED THAT SUCH ENCLOSURE
 IS NOT BUILT SO AS TO RENDER THE STRUCTURE IN VIOLATION
 OF SECTION 1612.
  
 ORDINANCE NO. 4729-17 SEC. 18-34 - TECHNICAL AMENDMENTS
 TO FLORIDA BUILDING CODE, BUILDING.(B) 1612.4.2
 ELEVATION REQUIREMENTS. THE MINIMUM ELEVATION
 REQUIREMENTS SHALL BE AS SPECIFIED IN ASCE 24 OR THE
 BASE FLOOD ELEVATION PLUS TWO FEET (610MM). WHICHEVER
 IS HIGHER.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By rmcphers Date 2021-12-16 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2021-12-16 Time 15:26 Sent To  
Notes
2021-12-16 15:52:18FLOOD ZONE = AE6
 PROPOSED LOWEST FLOOR ELEVATION = (9.60 NGVD) - 1.52
 PER SURVEY = 8.08 NAVD
  
 CORRECTIONS NEEDED =
  
 1) PLEASE SHOW THE LOWEST FLOOR ELEVATION ( NOT THE
 FINISHED FLOOR ELEVATION) - FBC SECTION 202 LOWEST
 FLOOR. THE LOWEST FLOOR OF THE LOWEST ENCLOSED AREA,
 INCLUDING BASEMENT, BUT EXCLUDING ANY UNFINISHED OR
 FLOOD-RESISTANT ENCLOSURE, USABLE SOLELY FOR VEHICLE
 PARKING, BUILDING ACCESS OR LIMITED STORAGE PROVIDED
 THAT SUCH ENCLOSURE IS NOT BUILT SO AS TO RENDER THE
 STRUCTURE IN VIOLATION OF SECTION 1612.
  
 2) PROVIDE AN ELEVATION CERTIFICATE - FBC 1612.5 FLOOD
 HAZARD DOCUMENTATION
  
 3) FLOOR PLAN SHOWS ENCLOSED SPACES BELOW THE REQUIRED
 LOWEST FLOOR ELEVATION (8.00 NAVD) WITHOUT FLOOD
 OPENINGS - FBC 1612.5 FLOOD HAZARD DOCUMENTATION
  
 FBC 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1.FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS OR COASTAL A ZONES:
  
 1.1.THE ELEVATION OF THE LOWEST FLOOR, INCLUDING THE
 BASEMENT, AS REQUIRED BY THE LOWEST FLOOR ELEVATION
 INSPECTION IN SECTION 110.3, BUILDING, 1.1 AND FOR THE
 FINAL INSPECTION IN SECTION 110.3, BUILDING, 5.1.
  
 1.2.FOR FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD
 ELEVATION WHERE PROVISIONS TO ALLOW FOR THE AUTOMATIC
 ENTRY AND EXIT OF FLOODWATERS DO NOT MEET THE MINIMUM
 REQUIREMENTS IN SECTION 2.7.2.1 OF ASCE 24,
 CONSTRUCTION DOCUMENTS SHALL INCLUDE A STATEMENT THAT
 THE DESIGN WILL PROVIDE FOR EQUALIZATION OF HYDROSTATIC
 FLOOD FORCES IN ACCORDANCE WITH SECTION 2.7.2.2 OF ASCE
 24.
  
 4) PLEASE SHOW THE FLOOR ELEVATION FOR ALL ENCLOSED
 ROOMS - SUCH AS TRANSFORMER ROOM, ETC..
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-03 Cont ID  
Sent By lcrespo Date 2022-01-03 Time 14:07 Rev Time 0.00
Received By lcrespo Date 2022-01-03 Time 14:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 16:51 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 06:36 Sent To  
Notes
2021-12-17 16:52:2012/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET P-200F;
  
 A. A 4" PIPE 32 DFU SHOWED IN A PRESSURIZATION WELL
 STAIR WITH A FIRE-RATED SYSTEM NEET TO HAVE A SHAFT AND
 STAIRWELL NOT LABELED. WOULD YOU PLEASE CLARIFY PER THE
 WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 B. GREASE INTERCEPTOR SIZE NEEDS TO MAX 750 GALLONS TO
 HAVE THE AMOUNT IN SERIES AND IT IS CALLED 1000
 GALLONS. UPON REQUEST, THERE IS A CITY DETAIL TO COMPLY
 WITH THESE INTERCEPTORS.
  
 C. GREASE INTERCEPTORS REQUIRE A SEPARATE PERMIT AND
 REVIEW BEFORE INSTALLATION PER THE WPB AMENDMENTS TO
 THE FBC SEC. 105.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 2. ON SHEET P300-F, IT SHOWS HUB DRAINS TRAPS WITH NO
 TRAP PRIMES AND NO VENT. WOULD YOU PLEASE CORRECT PER
 THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 6 Status P Date 2022-02-14 Cont ID  
Sent By jgomez Date 2022-02-14 Time 16:51 Rev Time 0.00
Received By jgomez Date 2022-02-14 Time 16:40 Sent To  
Notes
2022-02-14 16:52:10DRAWING A-101 REVISION (4) WAS CORRECTED. JG.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status F Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 11:30 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 11:30 Sent To  
Notes
2022-02-04 11:33:04PRIVATE PROVIDER - PLAN COMPLIANCE AFFIDAVIT - BUILDING
  
 1) DRAWING A-101 SHOWS THE REVISION (4) DATE
 INCORRECTLY - PLEASE CORRECT.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status P Date 2022-01-25 Cont ID  
Sent By rmcphers Date 2022-01-25 Time 15:05 Rev Time 0.00
Received By rmcphers Date 2022-01-25 Time 15:05 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2022-01-07 Cont ID  
Sent By rmcphers Date 2022-01-07 Time 12:38 Rev Time 0.00
Received By rmcphers Date 2022-01-07 Time 12:38 Sent To  
Notes
2022-01-07 12:49:11PRIVATE PROVIDER PLAN COMPLIANCE AFFIDAVIT "PLUMBING"
  
 CORRECTIONS NEEDED -
  
 1) P-400F - AFFIDAVIT SHOULD HAVE A PLAN DATE OF
 12-02-2021 (09-01-2021 IS SHOWN ON THE AFFIDAVIT)
  
 2) P-401F - AFFIDAVIT SHOULD HAVE A PLAN DATE OF
 12-02-2021 (09-01-2021 IS SHOWN ON THE AFFIDAVIT)
  
 3) P-402F - AFFIDAVIT SHOULD HAVE A PLAN DATE OF
 12-02-2021 (09-01-2021 IS SHOWN ON THE AFFIDAVIT)
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2021-12-03 Cont ID  
Sent By shill Date 2021-11-30 Time 19:14 Rev Time 0.00
Received By shill Date 2021-11-29 Time 19:14 Sent To  
Notes
2021-11-29 16:21:03THE AFFIDAVITS HAD A TYPO IN THE PERMIT # (TRANSPOSED),
 ADDRESS AND PARCEL ID HAD BEEN CHANGED, SO REQUESTED
 NEW AFFIDAVITS. RECEIVED AND UPLOADED.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By dbattles Date 2021-08-19 Time 13:54 Rev Time 0.00
Received By dbattles Date 2021-08-19 Time 13:54 Sent To  
Notes
2021-08-19 13:55:58PLEASE PROVIDE CERTIFICATE OF INSURANCE (COI)
 ALSO, PLEASE PROVIDE QUALIFICATIONS FOR REVIEWERS AND
 INSPECTORS WITH THEIR LICENSES.
  
 FOR PLAN REVIEW PROVIDE PRIVATE PROVIDER PLAN REVIEW
 COMPLIANCE AFFIDAVIT.
  
 UPLOAD ALL DOCUMENTS INTO THE SUPPORTING DOCUMENTS
 FOLDER.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-02-04 Cont ID  
Sent By rmcphers Date 2022-02-04 Time 11:29 Rev Time 0.00
Received By rmcphers Date 2022-02-04 Time 11:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-01-25 Cont ID  
Sent By rmcphers Date 2022-01-25 Time 15:05 Rev Time 0.00
Received By rmcphers Date 2022-01-25 Time 15:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-07 Cont ID  
Sent By rmcphers Date 2022-01-07 Time 14:47 Rev Time 0.00
Received By rmcphers Date 2022-01-07 Time 14:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-29 Cont ID  
Sent By mpeterso Date 2021-11-29 Time 13:16 Rev Time 0.00
Received By mpeterso Date 2021-11-29 Time 14:32 Sent To  
Notes
2021-11-29 14:33:04SIGNATURE REVIEW FAILED
 1) THE FOLLOWING DOCUMENTS APPEAR TO BE COPIES OF
 SIGNED AND SEALED DOCUMENTS OF A PROFESSIONAL ENGINEER
 "GEOTECHNICAL ENGINEERING STUDY" AND 'THE THRESHOLD
 INSPECTOR AGREEMENT"
  
 2) THE FOLLOWING STRUCTURAL PLANS LABELED "000-004 &
 006-008 & 100-109 & 115-121 & 125-126 &
 200,202,203,205,206 210,211, & 220-222,
 230,300,301,310, 315, 400,430 & 600-604"
 APPEAR TO BE COPIES OF A DIGITAL SEAL AND SIGNATURE OF
 THE ENGINEER OF RECORD
  
 PLEASE FOLLOW THE INSTRUCTIONS BELOW TO CORRECT THESE
 ISSUES
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2021-11-29 13:20:54 
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2022-01-07 Cont ID  
Sent By rmcphers Date 2022-01-07 Time 13:16 Rev Time 0.00
Received By rmcphers Date 2022-01-07 Time 13:16 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By rmcphers Date 2021-12-16 Time 15:17 Rev Time 0.00
Received By rmcphers Date 2021-12-16 Time 15:16 Sent To  
Notes
2021-12-16 15:21:00THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
  
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
  
  
 B) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. (THIS
 STATEMENT IS MISSING ON THE STRUCTURAL DRAWINGS)
  
 C) FOR THE THRESHOLD/SPECIAL INSPECTOR PLEASE PROVIDE A
 RESUME OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
 THE RESUME MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 D) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-09 Cont ID  
Sent By aaponte Date 2022-02-09 Time 13:41 Rev Time 0.00
Received By aaponte Date 2022-02-09 Time 12:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-11-24 Cont ID  
Sent By aaponte Date 2021-11-24 Time 11:56 Rev Time 0.00
Received By aaponte Date 2021-11-24 Time 11:56 Sent To  
Notes
***NONE***