| Plan Review Stops For Permit 21080907 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
P |
Date |
2022-05-03 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-05-03 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-05-03 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2022-05-03 14:36:31 | SUITE NUMBERS PRESENTED AND APPROVED, APPLICANT MIKE | | | IZZO WILL NOTIFY ADDRESSING IF THE UNITS ARE TO BE | | | SUBDIVIDED AT A LATER DATE. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2022-03-11 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-03-11 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-03-11 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2022-03-11 16:17:20 | PREVIOUS COMMENTS NOT ADDRESSED |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-02-01 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-02-01 |
Time |
15:38 |
Sent To |
|
|
| Notes |
| 2022-02-01 15:39:28 | ADDRESS ESTABLISHED, UNIT ADDRESSES NEED TO BE | | | ESTABLISH FOR ALL FLOORS EXEMPT THE GROUND FLOOR. | | | PLEASE EMAIL [email protected] OR CALL 561-805-6659 TO | | | ESTABLISH UNIT ADDRESSES. | | | |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-11-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-11-05 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-11-05 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2021-11-05 16:11:15 | INCORRECT PCN. MIKE IZZO REACHED OUT PROPOSED THE | | | FOLLOWING ADDRESSES: | | | 162 LAKEVIEW AVE ? RETAIL SPACE A | | | 180 LAKEVIEW AVE ? MAIN ENTRANCE (PRIMARY ADDRESS FOR | | | PROJECT) | | | 184 LAKEVIEW AVE ? RETAIL SPACE B | | | 828 CHASE ST ? LOBBY | | | 155 OKEECHOBEE BLVD ? OFFICE/READING ROOM | | | | | | | | | WAITING TO HEAR BACK, PLEASE CONTACT [email protected] OR | | | CALL 561-805-6659 TO DISCUSS ADDRESSING ISSUES. |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
P |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
2022-04-27 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
2022-04-27 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2022-04-27 12:39:28 | 1% HAS BEEN ESCROWED. LOCATION FOR PUBLIC ART HAS BEEN | | | IDENTIFIED. ARTIST HAS BEEN SELECTED. ART PROPOSAL MUST | | | BE REFLECTED ON THE SITE PLAN. | | | QUESTIONS CONTACT [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-06 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-06 |
Time |
08:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-23 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-23 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2022-08-23 10:39:24 | PRIVATE PROVIDER AUDIT ONLY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-15 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-14 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2022-07-15 09:24:24 | NEW HI RISE OFFICE BLDG. | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING G-011 - STAIRWELLS SHOULD NOT HAVE THE NOTES | | | - " FLOOD VENTS", " AREA BELOW THE DFE BUT ABOVE THE | | | BFE" - I BELIEVE THAT ALL THE STAIRWELLS HAVE BEEN | | | RAISED TO THE DFE. | | | | | | 2) DRAWING G-011 - RED LINE DRAWN FOR THE "WALLS | | | ENGINEERED FOR FLOOD LOADS" - SHOULD INCLUDE THE | | | EXTERIOR WALL ALONGSIDE THE EXTERIOR RAMP WHERE THE FF | | | INSIDE IS ALSO LOW - (COULD THE FLOOD DOOR BE USED AS | | | THE EXTERIOR DOOR? WHICH WILL DO AWAY WITH FLOOD VENTS | | | AND USING 2 FLOOD DOORS.) | | | | | | 3) DRAWING LS-118 - THE FIRE SERVICE ELEVATOR LOBBY - | | | PART OF THE WALLS DO NOT SHOW AS FIRE RATED. | | | | | | 4) DRAWING G-006 - BUILDING ZONING DATA - FLOOD ZONE | | | SHOWN IS INCORRECT. | | | | | | 5) DRAWING LS-101 - STAIR "C" SHOWS A WALL IN THE PATH | | | OF EGRESS - AND IT IS UNCLEAR AS TO WHAT THE EXTERIOR | | | DOOR OPENS TO (STAIR?). | | | | | | 6) DRAWING A-031 - STAIR FLOOR SLAB ELEVATIONS SHOULD | | | MATCH ELEVATIONS SHOWN ON DRAWING G-011. | | | | | | 7) DRAWING A-733 - DETAIL 2 - STAIR "C" FF NEEDS TO | | | MATCH G-011 | | | | | | 8) DRAWING A-233 - DETAIL 2 - STAIR "C" FF NEEDS TO | | | MATCH G-011 | | | | | | 9) DRAWING A-356 - DETAIL 3 - NEEDS TO MATCH DRAWING | | | G-011 | | | | | | 10) DRAWING A - 357 - STAIR "D" - DETAIL 1 - NEEDS TO | | | MATCH DRAWING G-011 | | | | | | 11) PLEASE PROVIDE PRODUCT APPROVALS, ICC VALUATIONS OR | | | ENGINEERING TEST REPORTS FOR THE FLOOD VENTS AND FLOOD | | | DOORS - OTHER THAN MANUFACTURES DATA. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-08-23 |
Time |
12:36 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-22 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2022-08-23 12:37:24 | PRIVATE PROVIDER AUDIT ONLY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-07-25 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-07-14 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2022-07-25 08:07:34 | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | CODES IN EFFECT: | | | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | | | | 1) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND | | | OVERCURRENT PROTECTION BETWEEN PANELS 2M5 AND 4M5 ON | | | SHEET E 704. IN ADDITION, FED FROM NOMENCLATURE, IS | | | INCORRECT ON PANEL SCHEDULE 2M5. FBC 107.2 | | | 2) THERE APPEARS TO BE DISCREPANCIES IN THE ONE LINE | | | RISER DIAGRAM DETAILING, ATS ELEVATOR PARKING, NORMAL | | | FEED, FROM MAIN 4 ON SHEET E 503, MAIN 1 ON SHEET E 501 | | | AND DB 1 SHEET E 703. PLEASE CORRECT AS APPLICABLE. FBC | | | 107.2 | | | 3) RISER DIAGRAM DETAILS 250 Y CONDUCTORS FED FROM 800 | | | AMP BREAKER FOR ATS ELEV-PARKING ON SHEET E-501. PLEASE | | | CORRECT AS APPLICABLE. NEC 215.5 | | | 4) RISER DIAGRAM ON SHEET E-503 DETAILS A 600 AMP RATED | | | TRANSFER SWITCH, ATS-O-RESTAURANT, FED FROM A 800 AMP | | | BREAKER FROM MAIN 2 ON SHEET E-501 AND A 600 AMP | | | BREAKER FROM ESB SWITCHBOARD, ON SHEET E-503. PLEASE | | | CORRECT AS APPLICABLE. NEC 215.5 | | | 5) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND | | | OVERCURRENT PROTECTION BETWEEN PANELS 4P2 AND 2P2. FBC | | | 107.2 | | | 6) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND | | | OVERCURRENT PROTECTION BETWEEN PANELS 2F8A AND 4F8. FBC | | | 107.2 | | | 7) PLEASE CORRECT INCONSISTENT TRANSFORMER RATING AND | | | OVERCURRENT PROTECTION BETWEEN PANELS 2Q9 AND 4Q9. FBC | | | 107.2 | | | 8) ESB SWITCHBOARD SCHEDULE DETAILS TWO FIRE PUMPS ON | | | SHEET E-704, RISER DETAILS ONE FIRE PUMP CORRECT AS | | | APPLICABLE. FBC 107.2 | | | 9) PLEASE PROVIDE A LEGEND FOR SYMBOLS USED ON ONE LINE | | | DIAGRAMS. SYMBOL FR AND G. FBC 107.2 | | | 10) PLEASE PROVIDE DETAILS ON RISER DIAGRAMS SHOWING | | | COMPLIANCE WITH NEC 215.10 AND 230.95 FOR 1000 AMP AND | | | ABOVE EQUIPMENT GROUND FAULT PROTECTION. FBC 107.2 | | | 11) PLEASE PROVIDE NOTES STATING ALL LOW VOLTAGE SYSTEM | | | WIRING INCLUDING BUT NOT LIMITED TO, DATA, PHONE, | | | ACCESS CONTROL, FIRE ALARM, BDA, REQUIRE SEPARATE | | | PERMITS FOR EACH SYSTEM. ADDITIONALLY, GENERATORS, | | | LIGHTNING PROTECTION, PV SYSTEMS, POOLS, SIGNS AND | | | LANDSCAPE LIGHTING REQUIRE SEPARATE PERMITS. | | | 12) ELECTRIC ROOMS ON 2ND AND 3RD FLOOR DETAILS | | | EQUIPMENT WITH OVERCURRENT DEVICES RATED 800 AMPS OR | | | MORE. IT APPEARS THE DOORS DETAILED AT THESE ROOMS ARE | | | NOT EQUIPPED WITH PANIC DOOR HARDWARE. NEC 110.26 | | | (3)(C) | | | 13) RISER DIAGRAM ON SHEET E-504 DETAILS CONDUCTORS | | | FROM DOF TO OFFICE ATS AS 400Y. SHEET E- 503 DETAILS | | | 3000 Y CONDUCTORS. PLEASE CORRECT AS APPLICABLE. NEC | | | 215.5 | | | 14) RISER DIAGRAM ON SHEET 503 DETAILS 400 Y CONDUCTORS | | | FROM OFFICE ATS TO ESB SWITCHBOARD FED FROM 3000 AMP | | | BREAKER. PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 15) RISER DIAGRAM ON SHEET E-503 DETAILS 400 Y | | | CONDUCTORS FROM ATS OFFICE TO MAIN 1. SHEET E-501 | | | DETAILS 3000 Y CONDUCTORS FROM MAIN 1 TO ATS OFFICE. | | | PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 16) PLEASE DETAIL DESTINATION OF LOAD SIDE CONDUCTORS | | | FROM ALL ATS EQUIPMENT ON SHEET E-503. NEC 215.5 | | | 17) PLEASE ENSURE TO CORRECT ANY PANEL SCHEDULES | | | MISLABELED FROM THE ABOVE CORRECTIONS. NEC 215.5 | | | 18) PLEASE PROVIDE DETAILS ON VERTICAL CONDUCTOR | | | SUPPORTS. ALL APPLICABLE CONDUCTORS, IE, GENERATOR, | | | ETC. NEC 300.19 | | | 19) FEED BREAKER FOR PANEL 4P1, ON PANEL SCHEDULE FOR | | | DPP, ON SHEET E-703, IS DETAILED AS 20 AMP. PANEL | | | SCHEDULE 4P1 ON SHEET E 701 IS DETAILED AS A 400 AMP | | | MAIN BREAKER PANEL. PLEASE CORRECT AS APPLICABLE. NEC | | | 215.5 | | | 20) PLEASE PROVIDE ALL RATINGS FOR SWITCHBOARDS DMP, | | | DQP ON SHEET E-703. NEC 215.5 | | | 21) PANEL SCHEDULES DETAIL PANEL 4E2 WITH 400 AMP MAIN | | | BREAKER FED FROM A 150 AMP BREAKER FROM PANEL DLS. IF | | | THIS IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC | | | 215.5 | | | 22) FEED BREAKER FOR PANEL 4P4, ON PANEL SCHEDULE FOR | | | DPP, ON SHEET E-703, IS DETAILED AS 20 AMP. PANEL | | | SCHEDULE 4P4 ON SHEET E 701 IS DETAILED AS A 250-AMP | | | BUS RATING WITH A 400 AMP MAIN BREAKER. PLEASE CORRECT | | | AS APPLICABLE. NEC 215.5 | | | 23) RISER SHEET E-504 DETAILS PANEL 4P7 BEING FED FROM | | | PANELBOARD DPP. PANEL 4P7 IS NOT DETAILED IN PANEL | | | SCHEDULE ON FOR DPP, SHEET E-703. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 24) PLEASE PROVIDE DETAILS ON MINI POWER CENTERS. NEC | | | 215.5 | | | 25) DOF SWITCHBOARD SCHEDULE ON SHEET E 705 DETAIL 3000 | | | AMP BUSWAY FEED. RISER DIAGRAM ON SHEET E 504, DETAILS | | | A 2000 AMP BUSWAY FEED. PLEASE CORRECT AS APPLICABLE. | | | NEC 215.5 | | | 26) PANEL SCHEDULES ON SHEET E-709 DETAIL PANELS BEING | | | FED FROM 3000 AMP BUSWAY. RISER DIAGRAM ON SHEET E-504 | | | DETAILS A 2000 AMP BUSWAY FEEDING THESE PANELS. PLEASE | | | CORRECT AS APPLICABLE. NEC 215.5 | | | 27) PANEL SCHEDULES ON SHEET E-710 DETAIL PANELS BEING | | | FED FROM 3000 AMP BUSWAY. RISER DIAGRAM ON SHEET E-504 | | | DETAILS A 2000 AMP BUSWAY FEEDING THESE PANELS. PLEASE | | | CORRECT AS APPLICABLE. NEC 215.5 | | | 28) TRANSFORMER ON PANEL SCHEDULE 2M19, SHEET E-711, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 29) TRANSFORMER ON PANEL SCHEDULE 2F20A, SHEET E-712, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 30) TRANSFORMER ON PANEL SCHEDULE 2F21A, SHEET E-712, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 31) PANEL SCHEDULE DETAILS PANEL 2F21A, SHEET E-712, AS | | | 250 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS | | | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 32) TRANSFORMER ON PANEL SCHEDULE 2F22A, SHEET E-713, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 33) TRANSFORMER ON PANEL SCHEDULE 2M22, SHEET E-713, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 34) TRANSFORMER ON PANEL SCHEDULE 2F23A, SHEET E-713, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 35) PANEL SCHEDULE DETAILS PANEL 2F23A, SHEET E-712, AS | | | 250 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS | | | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 36) TRANSFORMER ON PANEL SCHEDULE 4E23, SHEET E-713, | | | INCORRECTLY DETAILED AS A T5. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 37) TRANSFORMER ON PANEL SCHEDULE 2F24A, SHEET E-714, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 38) PANEL SCHEDULE 4F24 DETAILS PANEL AS MLO FED FROM | | | 1000 AMP BUSWAY. IF THIS IS INCORRECT, PLEASE CORRECT | | | AS APPLICABLE. NEC 215.5 | | | 39) TRANSFORMER ON PANEL SCHEDULE 4Q24, SHEET E-714, | | | DETAILS A T5. RISER DIAGRAM ON SHEET E 505 DETAILS A T4 | | | TRANSFORMER. PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 40) TRANSFORMER ON PANEL SCHEDULE 2Q24, SHEET E-714, | | | INCORRECTLY DETAILED AS A T6. PLEASE CORRECT AS | | | APPLICABLE. NEC 215.5 | | | 41) PANEL SCHEDULE DETAILS PANEL 2Q24, SHEET E-714, AS | | | 400 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS | | | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 42) PANEL SCHEDULE DETAILS PANEL 2MR, SHEET E-714, AS | | | 400 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS | | | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 43) PANEL SCHEDULE DETAILS PANEL 2QR, SHEET E-714, AS | | | 400 BUS AMP RATING WITH A 400 AMP MAIN BREAKER. IF THIS | | | IS INCORRECT, PLEASE CORRECT AS APPLICABLE. NEC 215.5 | | | 44) PLEASE ENSURE ALL RISERS AND PANEL SCHEDULES | | | CONCUR. NEC 215.5 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2022-06-16 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
2022-06-16 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-16 15:01:36 | PASSED. COMMENTS ARE BEING SENT TO ENGINEER FOR | | | REVISIONS BUT DO NOT AFFECT THE BUILDING. AFTER | | | APPROVAL, REVISED PLANS NEEDS TO UPLOADED INTO PERMIT. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-04-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-04-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-27 07:46:43 | WHEN APPROVED ENGINEERING PLANS ARE RELEASED, UPLOAD TO | | | BUILDING PERMIT. | | | | | | THANKS, | | | | | | RICK ROSSANO | | | SENIOR PROJECT COORDINATOR | | | CITY OF WPB ENGINEERING SERVICES | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-03-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-03-14 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-03-14 12:16:49 | UNDER FORMAL ENGINEERING SUBMITTAL REVIEW E21080045. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-01-13 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
2022-01-13 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-13 16:36:26 | UNDER FORMAL ENGINEERING SUBMITTAL REVIEW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-08-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-08-31 |
Time |
10:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-08-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-08-15 |
Time |
13:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-05-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-05-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-05-24 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2022-05-24 15:29:38 | FIRE PROVISO: | | | ANY PROPOSED BDA SYSTEM SHALL BE COORDINATED WITH MARK | | | FILLA, PALM BEACH COUNTY, | | | PUBLIC SAFETY RADIO SYSTEMS MANAGER, FOR ALL RADIO | | | SIGNAL DETAILS, OUTBOUND SIGNAL | | | STRENGTH AND ANTENNA DIRECTION, AS OUR RADIOS OPERATE | | | ON THAT SYSTEM. | | | | | | THE SYSTEM CANNOT BE INSTALLED NOR TURNED ON WITHOUT | | | HIS REVIEW AND APPROVAL. | | | | | | [email protected] 561-233-0837 | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-03-22 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-03-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-03-17 |
Time |
15:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-01-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-01-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-12-27 |
Time |
15:29 |
Sent To |
|
|
| Notes |
| 2021-12-27 15:32:10 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE INDICATIONS ON THE CIVIL SHEETS OF | | | UNDEGROUND FIRE LINES, INCLUDING THE FDC & DDCV. | | | | | | ALL FIRE LINE UNDERGROUND WORK INCLUDING THE FDC & DDCV | | | SHALL INSTALLED PER NFPA 24 AND UNDER SEPARATE PERMIT | | | AND SHOP DRAWINGS . | | | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON | | | THE CIVIL SHEET C - 400. | | | | | | | | | | | | 2) THERE ARE INDICATIONS OF AN ELECTIRC FIRE PUMP AND A | | | GENERATOR; HOWEVER, THERE IS NO INDICATON THAT THE | | | ELECTRIC FIRE PUMP WILL BE POWERED BY THE GENERATOR IN | | | THE EVENT OF LOSS OF POWER. | | | | | | PER NFPA 20 | | | | | | 9.3 ALTERNATE POWER. | | | 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT | | | LEAST | | | ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE | | | THE | | | HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY | | | OF THE | | | FIRE DEPARTMENT APPARATUS. | | | 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT | | | DESCRIBED IN | | | 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE | | | PROVIDED | | | WHERE THE NORMAL SOURCE IS NOT RELIABLE. | | | 9.3.3 AN ALTERNATE SOURCE OF POWER FOR THE PRIMARY FIRE | | | PUMP | | | SHALL NOT BE REQUIRED WHERE A BACKUP ENGINE-DRIVEN FIRE | | | PUMP, | | | BACKUP STEAM TURBINE-DRIVEN FIRE PUMP, OR BACKUP | | | ELECTRIC | | | MOTOR?DRIVEN FIRE PUMP WITH INDEPENDENT POWER SOURCE | | | MEETING | | | 9.2.2 IS INSTALLED IN ACCORDANCE WITH THIS STANDARD. | | | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO | | | COMPLY ON THE LS, FP & GENERATOR SHEETS | | | | | | | | | 3) THERE ARE NO INDICATIONS OF A BDA SYSTEM | | | | | | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY | | | RADIO ENHANCEMENT SERVICES. | | | | | | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM | | | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT | | | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL | | | DETERMINED BY THE AHJ. | | | | | | PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC | | | SAFETY RADIO SYSTEMS MANAGER, AS OUR RADIOS OPERATE ON | | | THEIR SYSTEM FOR DETAILED RADIO FREQUENCY AND | | | INSTALLATION INSTRUCTIONS. | | | | | | THERE IS NO WAY TO DETERMINE IF YOUR BUILDING WOULD | | | NEED IT OR NOT WITHOUT PROPER TESTING. | | | | | | SHOULD YOUR BUILDING NOT PASS THE TESTING/SURVEY, AN | | | AMPLIFICATION SYSTEM WOULD BE REQUIRED. | | | | | | SHOULD YOUR BUILDING PASS THE TESTING/SURVEY I WOULD | | | COME IN WITH OUR PORTABLE RADIOS AND CONDUCT AN | | | OPERATIONAL TEST TO CONFIRM. IF THE PORTABLE RADIO TEST | | | FAILS AN AMPLIFICATION SYSTEM IS REQUIRED. | | | | | | THE OWNER/CONTRACTOR WOULD BE RESPONSIBLE TO CONDUCT | | | THE TESTING/SURVEY BY A QUALIFIED THIRD PARTY. | | | | | | A BDA PERMIT IS REQUIRED SEPARATE FROM ANY OTHER | | | PERMIT. | | | | | | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKOWLEDGEMENT TO | | | COMPLY ON THE LS SHEET LS - 101. | | | | | | | | | | | | 4) THERE IS NO RATIONAL ANALYSIS DOCUMENT THAT COULD BE | | | REVIEWED FOR THE SMOKE CONTROL SYSTEM(S) APPLICABLE | | | SEQUENCE OF OPERATION. | | | | | | THE SMOKE CONTROL SHEETS WERE REVIEWED; HOWEVER, THE | | | INFORMATION PROVIDED ON THOSE SHEETS DOES NOT PROVIDE | | | CLEAR INDICATIONS IN A LOGICAL ORDER. | | | | | | PLEASE REVIEW AND PROVIDE A DETAILED DOCUMENT FOR | | | REVIEW. | | | | | | | | | | | | 5) ON THE LIFE SAFETY SHEETS FLOORS 1 THRU 3 , THERE | | | DOES NOT APPEAR TO BE AN EXIT SIGN WITHIN THE THE FSV | | | OVER THE EXIT DOOR TO LEADING TO THE STAIRWELL. | | | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-02 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-02 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-24 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-24 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2022-08-24 16:34:47 | 2ND REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21080907 | | | 8/23/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | FAILED AUDIT COMMENTS #3 & 5 ARE LISTED WITH NOTES IN | | | CAPS ADDED FOR CLARIFICATION. | | | | | | 3) FAILED. P-201- P-224: PLEASE PROVIDE NOTES AND | | | DETAILS ON THE PLANS INDICATING THE LOCATIONS OF THE | | | 2-HR FIRE RATED CHASE SPECIFIED ON THE DRAWING- SEC. | | | 107.2.1 WPB. PLEASE NOTE THAT THE PIPING SHALL NOT | | | PENETRATE INTO THE INTERIOR EXIT STAIRWAY- SEC. 1023.5 | | | FBC B. THE LOCATIONS ARE NOW SHOWN HOWEVER THE | | | NARRATIVE RESPONSE REFERENCES DETAIL 12 ON A-714. | | | DETAIL 12 SHOWS A SHAFT ENCLOSURE USING THE CONCRETE | | | SLAB AS ONE SIDE AND NOT A FOUR-SIDED FRAMED VERTICAL | | | CHASE AS THE PLANS APPEAR TO INDICATE. THE DETAIL ALSO | | | REFERENCES MEP DRAWINGS FOR PIPE SUPPORT METHOD. I WAS | | | NOT ABLE TO LOCATE A PIPE SUPPORT DETAIL FOR THE 4-INCH | | | SCHEDULE 40 METAL PIPES. | | | | | | 5) FAILED A & B. P-201 & P-802: THE DRAWINGS APPEAR TO | | | SHOW THE LOW PRESSURE PIPE CONNECTION TO THE MAIN | | | UPSTREAM OF THE 2 PSI PIPE CONNECTIONS TO THE | | | GENERATORS. PLEASE REFER TO SECS. 5.5.1 & 7.9.7 NFPA | | | 110 AND PROVIDE AN ENLARGED DETAIL FOR THE GAS SERVICE | | | ENTRANCE. | | | A) SHOW THE GENERATOR GAS PIPES AND SHUT OFF VALVES | | | WILL BE CONNECTED ON THE SUPPLY SIDE OF THE MAIN VALVE | | | AND WILL BE MARKED AS SUPPLYING EMERGENCY GENERATORS- | | | SEC 7.9.7 NFPA 110. AND SEC. 409.3.3 FBC FG. | | | B) SHOW THE LOCATION OF THE LOW PRESSURE GAS PIPE | | | CONNECTION, SHUT OFF VALVE, AND PRESSURE REGULATOR- | | | SEC. 410.2 FBC FG. | | | IN RESPONSE TO THE COMMENTS THE NARRATIVE STATES A GAS | | | SERVICE ENTRANCE DETAIL IS SHOWN ON P-201 OR P-802 | | | HOWEVER THE DETAIL WAS NOT PROVIDED. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-18 |
Time |
13:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-15 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2022-07-18 13:36:54 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 21080907 | | | 7/18/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | GAS AUDIT. PLEASE REVIEW THE COMMENTS BELOW. | | | | | | 1) SHEET P-802: THE 2 PSI PIPE SIZING TABLE 402.4(4) | | | SPECIFIED IS A LOW-PRESSURE TABLE. PLEASE REMOVE AND | | | REPLACE WITH EITHER TABLE 402.4(5) OR 402.4(6) FBC FG. | | | | | | 2) P-802: USING THE LOW-PRESSURE SIZING TABLE 402.4(2) | | | SPECIFIED, THE 2-INCH PIPE IS LIMITED TO 546 CFH AT 400 | | | FT. TOTAL DEVELOPED LENGTH. PLEASE INCREASE THE SIZE OF | | | THE PIPE TO 4-INCH PER THE TABLE. | | | | | | 3) P-201- P-224: PLEASE PROVIDE NOTES AND DETAILS ON | | | THE PLANS INDICATING THE LOCATIONS OF THE 2-HR FIRE | | | RATED CHASE SPECIFIED ON THE DRAWING- SEC. 107.2.1 WPB. | | | PLEASE NOTE THAT THE PIPING SHALL NOT PENETRATE INTO | | | THE INTERIOR EXIT STAIRWAY- SEC. 1023.5 FBC B. | | | | | | 4) P-225 & P-802: SEPARATE PERMITS ARE REQUIRED FOR THE | | | GENERATORS. PLACE NOTES ON THE PLANS ACCORDINGLY- SEC. | | | 105.1 & 107.2.1 WPB. PLEASE CLARIFY IF THE GENERATORS | | | ARE FOR STANDBY AND EMERGENCY USE AND INDICATE WHICH | | | BUILDING SYSTEM LOADS ARE BEING SUPPLIED BY THE UNITS- | | | SECS. 403.8.3 & 403.4.8.4 FBC B. | | | | | | 5) P-201 & P-802: THE DRAWINGS APPEAR TO SHOW THE LOW | | | PRESSURE PIPE CONNECTION TO THE MAIN UPSTREAM OF THE 2 | | | PSI PIPE CONNECTIONS TO THE GENERATORS. PLEASE REFER TO | | | SECS. 5.5.1 & 7.9.7 NFPA 110 AND PROVIDE AN ENLARGED | | | DETAIL FOR THE GAS SERVICE ENTRANCE. | | | A) SHOW THE GENERATOR GAS PIPES AND SHUT OFF VALVES | | | WILL BE CONNECTED ON THE SUPPLY SIDE OF THE MAIN VALVE | | | AND WILL BE MARKED AS SUPPLYING EMERGENCY GENERATORS- | | | SEC 7.9.7 NFPA 110. AND SEC. 409.3.3 FBC FG. | | | B) SHOW THE LOCATION OF THE LOW PRESSURE GAS PIPE | | | CONNECTION, SHUT OFF VALVE, AND PRESSURE REGULATOR- | | | SEC. 410.2 FBC FG. | | | | | | 6) SUBMIT COMPLETE SPECIFICATIONS FOR THE GENERATORS- | | | SEC. 616.1 FBC FG. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
N |
Date |
2022-01-06 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2022-01-06 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-01-06 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-06 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-31 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-09-01 |
Time |
14:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-30 |
Time |
15:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-24 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-16 |
Time |
12:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2022-08-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-08-16 |
Time |
12:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-06 |
Time |
06:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-25 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-05 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-06-30 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-25 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2022-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-06-24 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-16 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-06-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-06-03 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-05-31 |
Time |
16:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-05-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-05-28 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-05-19 |
Time |
07:41 |
Sent To |
|
|
| Notes |
| 2022-05-21 13:17:10 | NEW ELECTRICAL EMERGENCY LIGHTING PAGES, FA PAGES | | | SUBMITTED, ROUTED TO FIRE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-04-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-04-27 |
Time |
14:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-04-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-04-07 |
Time |
06:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-03-11 |
Time |
06:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-24 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-01-24 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-12-23 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-08-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-08-19 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-19 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2022-08-19 13:45:51 | RECEIPT MU-2022-07094 - $747,548.73 PAID | | | 1/26/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-08-17 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-08-17 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-08-17 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2021-08-17 16:59:26 | 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC | | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-22 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-22 |
Time |
12:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-13 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-13 |
Time |
12:41 |
Sent To |
|
|
| Notes |
| 2022-07-13 12:52:31 | PERMIT ? 21080907 | | | 1ST CYCLE MECHANICAL AUDIT | | | | | | | | | 1) REVISE THE ENERGY CALCULATIONS TO LIST THE NUMBER OF | | | STORIES IN THIS BUILDING. IT CURRENTLY STATES THE | | | NUMBER OF STORIES AS 1. FBC 107.2.1 | | | | | | 2) THE ENERGY CALCULATIONS, PAGE 10 OF 64, LISTS A | | | ERU-3. SHEET M-700 OF THE DRAWINGS DOES NOT LIST A | | | ERU-3. EXPLAIN. FBC 107.2.1 | | | | | | 3) THERE SEEMS TO BE SEVERAL FCU?S LISTED ON THE ENERGY | | | CALCULATIONS, BUT THEY ARE MISSING FROM THE FCU | | | SCHEDULE ON SHEET M-701. EXPLAIN. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
P |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-15 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-15 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2022-07-15 09:25:25 | SEE FOUNDATION 21080908 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-02 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-02 |
Time |
11:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-24 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-24 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2022-08-24 15:04:24 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 21080907 | | | 8/23/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLUMBING PLAN AUDIT. | | | FAILED COMMENTS FROM THE 1ST AUDIT ARE PRINTED BELOW | | | WITH ADDITIONALS NOTES IN CAP LETTERS FOR | | | CLARIFICATION. PLEASE REVIEW THE COIMMENTS BELOW AND | | | NOTE THE FOLLOWING: | | | | | | DUE TO A RECENT CHANGE IN PROCESS, THE POTABLE WATER | | | BACKFLOW PREVENTER , GREASE INTERCEPTOR, AND OIL/SAND | | | INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR | | | TO ISSUANCE OF THE PRIMARY PERMIT. YOU CAN SUBMIT AN | | | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE | | | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT | | | APPLICATION TO [email protected] . YOU WILL | | | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU | | | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE | | | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT | | | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER | | | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL | | | AND I WILL CHANGE THE REVIEW STATUS TO PASS. | | | | | | 2) FAILED ITEM 2B SHEET LS-101: BOH: B OCCUPANCY- 2 | | | WATER CLOSETS AND 2 LAVATORIES ARE REQUIRED- 1 EACH FOR | | | MALE AND FEMALE USE. PLEASE NOTE SEPARATE FACILITIES | | | FOR MALE AND FEMALE USE ARE REQUIRED- SEE SEC. 403.2. | | | ITEM #4 AND CORRECT THE CALCULATIONS. REVISED SHEET | | | LS-100: THE CALCULATIONS ARE NOT BROKEN DOWN PER GENDER | | | AND INDICATE A DEFICIENCY OF 1 WATER CLOSET AND 1 | | | LAVATORY. | | | | | | 12) FAILED. P-200: COMMENT #11 IS ALSO APPLICABLE TO | | | THE OIL INTERCEPTOR. PROVIDE INSTALLATION DETAILS AND | | | NOTES ON THE PLAN, AND SUBMIT MANUFACTURERS | | | INSTALLATION GUIDELINES FOR HIGH WATER AND HYDROSTATIC | | | PRESSURE CONDITIONS, AND FOR VEHICULAR LOAD PROTECTION. | | | THE NARRATIVE RESPONSE INDICATES FLOWABLE FILL DETAILS | | | ON P-504, HOWEVER THE DETAILS THERE ARE FOR THE SCHIER | | | INTERCEPTOR. DETAILS FOR THE ZURN OIL INTERCEPTOR WHICH | | | IS SHOWN ON P-505 ARE NOT PROVIDED. | | | | | | 13) FAILED. P-200: PROVIDE RAIN WATER CISTERN | | | INSTALLATION DETAILS AND NOTES ON THE PLAN AND SUBMIT | | | MANUFACTURERS SPECIFICATIONS FOR THE TANK AND THE | | | MANHOLE COVER. THE TANK AND COVER SHALL BE WATER TIGHT | | | AND DESIGNED TO WITHSTAND HIGH WATER AND HYDROSTATIC | | | PRESSURE CONDITIONS- SEC.- 309.2 FBC P AND SEC. 7.3.2 | | | ASCE 24-14. BASED ON THE RESPONSE NARRATIVE PLEASE | | | IDENTIFY THE WATER TANK SHOWN ON THE PLAN AS A CONCRETE | | | RAIN CISTERN. PLEASE SHOW THE LOCATION OF THE MANHOLE | | | ON THE PLAN AND PROVIDE EITHER NOTES OR DETAILS | | | VERIFYING THE COVER WILL BE MINIMUM 24-INCHES IN | | | DIAMTER, WATER TIGHT, AND LOCKABLE- SECS. 1301.9.6 AND | | | 1303.12 FBC P. PLEASE NOTE THAT NON-POTABLE SIGNAGE IS | | | REQUIRED PER SEC.- 1301.3. | | | | | | 15) FAILED. P-200: A WASTE RECEPTOR IS NOT SHOWN IN THE | | | TRASH COMPACTOR AREA. PLEASE REVIEW MANUFACTURER'S | | | SPECIFICATIONS AND MAINTENANCE GUIDELINES. THE | | | MANUFACTURER MAY RECOMMEND INSTALLATION OF A RECEPTOR | | | AND DRAIN TO CONVEY HYDRAULIC FLUID AND OTHER LIQUID | | | WASTES FROM THE COMPACTOR TO APPROVED PLACES OF | | | DISPOSAL- SEC. 107.2.1 WPB. THE REVISED PLAN INDICATES | | | KITTY LITTER WILL BE USED TO DISPOSE OF THE HYDRAULIC | | | FLUID. KITTY LITTER DOES NOT APPEAR TO BE AN APPROVED | | | METHOD FOR REMOVING HYDRAULIC FLUID FROM THE WASTE | | | WATER. PLEASE SUBMIT THE REQUESTED MANUFACTURER'S | | | SPECIFICATIONS FOR THE COMPACTOR AND REFER TO SEC. | | | 1003.1 FBC P- AN OIL INTERCEPTOR IS REQUIRED. | | | | | | 18) FAILED ITEM C. P-200, P-803 & P-805: | | | C) FAILED. P-805: SHOW THE LOCATION OF THE 6-INCH VENT | | | STACK CONNECTION AT THE BASE OF THE 8-INCH SOIL STACK | | | (SS/1)- SEC. 904.4 FBC P. THE 6-INCH VENT CONNECTION | | | FOR THE 8-INCH SOIL STACK- SS/1 AT THE BASRE OF THE | | | STACK IS NOT SHOWN ON P-805 OR P-200. ALSO MISSING IS | | | THE REQUIRED VENT AT THE BASE OF SOIL STACK SS/2. | | | | | | 19) FAILED. P-200, P-601, & P-801: PLEASE PROVIDE A | | | SCHEDULE FOR THE DOMESTIC, FIRE, IRRIGATION, AND | | | COOLING TOWER WATER SUPPLY BACKFLOW PREVENTERS SHOWN ON | | | THE PLANS- SECS. C, D, & E WPB UTILITIES CROSS | | | CONNECTION MANUAL. THE BF SCHEDULE ON P-601 INDICATES A | | | DOUBLE CHECK VALVE BF FOR THE RESTAURANT POTABLE WATER | | | HOWEVER AN RPZ IS REQUIRED PER THE WPB UTILITIES CROSS | | | CONNECTION MANUAL | | | | | | 21) FAILED A, B & E. P-501- FBC C P: | | | A) FAILED. DETAIL 5- PROVIDE AN OVERFLOW DRAIN DETAIL- | | | SECS. 1105.1 & 1108.1. AN OVERFLOW DRAIN WOULD BE | | | DESIGNED TO HAVE THE INLET 2-INCHES ABOVE THE ROOF | | | SURFACE. PLEASE REVIEW ZURN MANUFACTURER?S SPECS. | | | B) FAILED. DETAIL 7- SHOW A MEANS OF THERMAL EXPANSION | | | CONTROL FOR THE WATER HEATER- SEC. 607.3.THE EXPANSION | | | TANK CONNECTION SHALL BE DOWNSTREAM OF THE CHECK VALVE. | | | THE CURRENT LOCATION SHOWN IS UPSTREAM. | | | E) FAILED. DETAIL 11- INDICATE HOW TEMPERED WATER WILL | | | BE DELIVERED FROM THE LAVATORIES- SECS. 419.5 & | | | 607.1.2. THE WATER HEATER SHALL HAVE AN INTEGRAL ASSE | | | 1070 APPROVED TEMPERATURE LIMITING DEVICE IF USED AT | | | THE LAVATORIES, OTHERWISE PROVIDE AN ASSE APPROVED | | | MIXING VALVE FOR TEMPERED WATER DELIVERY. | | | | | | 22) FAILED. P-208 & P-801: SHOW HW, HWR, & CW WATER | | | SUPPLY BRANCH AND FIXTURE PIPING RUNS AND CONNECTIONS | | | TO THE FIXTURES ON THE FLOOR PLAN, AND PROVIDE AN | | | ENLARGED WATER RISER DRAWING- SECS.107.2.1 & | | | 107.3.5.1.3 WPB. REFER TO NOTE ON P-801. PROVIDE TRAP | | | SEAL PROTECTION FOR THE FLOOR DRAINS- SEC. 1102.4.1 FBC | | | P. | | | | | | 23) FAILED. A- 101, 102, 103, 104, 108 & P-201, 202, | | | 203, 204, 208: LABEL THE BATHROOMS AND TOILETS ROOMS AS | | | EITHER MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC P. | | | IDENTIFY THE LOCATIONS OF REQUIRED SERVICE SINKS AND | | | DRINKING FOUNTAINS AND INCLUDE PIPING DETAILS- SEC. | | | 107.2.1 WPB. THE RESPONSE NARRATIVE INDICATES 1ST FLOOR | | | DRINKING FOUNTAIN AT TARGET (01-303A) HOWEVER NO | | | DRINKING FOUNTAIN SHOWN AT THAT LOCATION. REQUIRED | | | DRINKING FOUNTAINS NOT SHOWN ON THE 4TH OR 8TH FLOORS. | | | PLEASE NOTE THE DRINKING FOUINTAIN AT TARGET (02-128) | | | ON A-102 IS PROTRUDING INTO THE CIRCULATION PATH- SEC. | | | 307.2 FBC ACC. | | | | | | 24) FAILED. A-108: PROVIDE PLUMBING FIXTURE | | | CALCULATIONS FOR THE 8TH FLOOR BATH AND TOILET ROOMS. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED NUMBER OF FIXTURES- TABLE 403.2 FBC P. PLEASE | | | NOTE THAT DRINKING FOUNTAINS AND SERVICE SINKS ARE | | | REQUIRED FIXTURES FOR A AND B OCCUPANCIES. IDENTIFY THE | | | LOCATIONS AND PROVIDE PLUMBING PIPING DETAILS- SEC. | | | 107.2.1 WPB. DRINKING FOUNTAIN LOCATION AND PIPING | | | DETAILS NOT PROVIDED. | | | | | | 25) FAILED. A-660- A-108: ENLARGED DRAWINGS AND DETAILS | | | FOR THE ACCESSIBLE 8TH FLOOR TERRACE SINGLE USER TOILET | | | ROOMS NOT PROVIDED- SEC. 107.2.1 WPB. THE DIMENSIONS OF | | | THE CLEAR FLOOR SPACES FOR THE FIXTURES NOT PROVIDED. | | | | | | 26) FAILED. A-660 DETAILS 1 & 7: THE DIMENSIONS OF THE | | | CLEAR FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES | | | ARE NOT SHOWN- SECS. 604.3 & 606.2 FBC ACC. DIMENSIONS | | | SHOWN FOR THE WATER CLOSETS ARE INCORRECT. 60-INCHES | | | WIDE X 56-INCHES DEEP CLEAR FLOOR SPACES REQUIRED. | | | | | | 32) FAILED. DEFERRED SUBMITTALS: PLEASE PROVIDE A LIST | | | OF DEFERRED SUBMITTALS INCLUDING, BUT NOT LIMITED TO | | | WATER HEATERS, EXPANSION TANKS, RECIRCULATION PUMPS, | | | SUMP PUMPS, MASTER AND POINT OF USE THERMOSTATIC MIXING | | | VALVES, BACKFLOW PREVENTERS, TRAP PRIMERS, WATER HAMMER | | | ARRESTORS, ACCESSIBLE PLUMBING FIXTURES, AND ROOF AND | | | OVERFLOW DRAINS- SEC. 107.3.4.1 WPB. PLEASE PLACE THE | | | LIST ON THE PLAN. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-18 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-14 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2022-07-18 11:29:19 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21080907 | | | 7/15/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLUMBING PLAN AUDIT. | | | PLEASE REVIEW THE FOLLOWING COMMENTS. | | | | | | 1) SHEET G-000 OR G-001: PROVIDE ON THE PLAN A LIST OF | | | REQUIRED ITEMS TO BE UNDER SEPARATE PERMITS INCLUDING, | | | BUT NOT LIMITED TO- BACKFLOW PREVENTERS, FIRE LINE, | | | FIRE SPRINKLERS, FIRE PUMP, GREASE INTERCEPTOR, | | | OIL/SAND INTERCEPTOR, EMERGENCY AND STANDBY GENERATORS, | | | IRRIGATION, TRASH COMPACTOR, AND THE TENANT BUILDOUTS. | | | PLEASE NOTE EACH REQUIRED BACKFLOW SHALL BE SEPARATELY | | | PERMITTED INCLUDING THE BF DEVICES FOR THE POTABLE | | | WATER SERVICE, FIRE LINE, IRRIGATION, AND THE COOLING | | | TOWER. | | | DUE TO A RECENT CHANGE IN PROCESS, THE BACKFLOW, GREASE | | | INTERCEPTOR, AND OIL/SAND INTERCEPTOR PERMITS ARE | | | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE | | | PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO | | | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED | | | BY EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected] . YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE | | | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL | | | CHANGE THE REVIEW STATUS TO PASS. | | | | | | 2) SHEET LS-101: THE PLUMBING FIXTURE CALCULATIONS ARE | | | NOT IN COMPLIANCE WITH TABLE 403.2 FBC P. | | | A) RETAIL A & B: M OCCUPANCIES- 2 WATER CLOSETS AND 2 | | | LAVATORIES ARE REQUIRED- 1 EACH FOR MALE AND FEMALE | | | USE. PLEASE NOTE SEPARATE FACILITIES FOR MALE AND | | | FEMALE USE ARE REQUIRED- SEE SEC. 403.2 ITEM #3 AND | | | CORRECT THE CALCULATIONS. | | | B) BOH: B OCCUPANCY- 2 WATER CLOSETS AND 2 LAVATORIES | | | ARE REQUIRED- 1 EACH FOR MALE AND FEMALE USE. PLEASE | | | NOTE SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE | | | REQUIRED- SEE SEC. 403.2. ITEM #4 AND CORRECT THE | | | CALCULATIONS. | | | C) READING ROOM: A OCCUPANCY- 2 WATER CLOSETS AND 2 | | | LAVATORIES ARE REQUIRED- 1 EACH FOR MALE AND FEMALE. | | | PLEASE NOTE SEPARATE FACILITIES FOR MALE AND FEMALE USE | | | ARE REQUIRED- SEE SEC. 403.2. DRINKING FOUNTAINS AND | | | SERVICE SINKS ARE ALSO REQUIRED FIXTURES FOR THE | | | READING ROOM. PLEASE CORRECT THE CALCULATIONS. | | | | | | 3) SHEETS P-200 & P-805: THE COOLING TOWER DRAIN LINE | | | IS LABELED A SANITARY LINE HOWEVER UNCONTAMINATED | | | COOLING WATER IS PROHIBITED FROM DISCHARGING INTO THE | | | CITY SANITARY SYSTEM PER SEC. 90-126 (5) WPB CODE OR | | | ORDINANCES. PLEASE CONTACT THE WPB UTILITIES DEPT. FOR | | | ASSISTANCE AT 561-494-1074. | | | | | | 4) P-200: THE COOLING TOWER DRAIN LINE IS LABELED BOTH | | | 6-INCH AND 8-INCH ON THE PLAN- PLEASE CORRECT- SEC. | | | 107.2.1 WPB. | | | | | | 5) P-200 & P-805: SHOW THE LOCATION OF THE FUTURE | | | SANITARY LINE FOR RETAIL B ON SHEET P-805- SEC. 107.2.1 | | | WPB. | | | | | | 6) P-200: SHOW THE TRENCH DRAIN PIPE POINT OF | | | CONNECTION TO AN APPROVED PLACE OF DISPOSAL- SEC. 301.3 | | | FBC P. | | | | | | 7) P-200 & P-805: PLEASE IDENTIFY THE WHAT FIXTURE OR | | | EQUIPMENT DRAINAGE IS BEING CONVEYED FROM THE HUB DRAIN | | | TO THE OIL INTERCEPTOR- SEC. 1003.4 FBC P. PLEASE SEE | | | SEC. 1003.4.2.2 FBC P AND CLARIFY THE NEED FOR THE | | | INTERCEPTOR AND THE CAPACITY WAS CALCULATED. WILL | | | VEHICLES BE REPAIRED OR WASHED IN THE DOCK AREA? | | | | | | 8) P-200: INDICATE THE TYPES OF SLEEVES FOR THE GREASE | | | WASTE AND SANITARY LINE AND SUBMIT MANUFACTURERS | | | SPECIFICATIONS AND INSTALLATION MANUAL FOR THE HEAT | | | TRACE SYSTEM- SEC. 305.2 FBC P & SEC. 107.2.1 WPB. | | | CLARIFY HOW THE SYSTEM WILL BE MADE WATER TIGHT PER THE | | | NOTE ON THE PLAN- SEC. 309.2 FBC P. | | | | | | 9) P-200: THE SLEEVE NOTE IN THE LOADING DOCK CALLS OUT | | | A 6-INCH SANITARY HOWEVER THE ARROW POINTS TO AN | | | 8-INCH- PLEASE CLARIFY- SEC. 107.2.1 WPB. | | | | | | 10) P-200: THE BUILDING IS BEING CONSTRUCTED IN AN AE | | | FLOOD HAZARD ZONE. REFER TO SEC. 309.2 FBC P FLOOD | | | HAZARD AND SEC. 7.3 ASCE 24-14: THE PLUMBING SYSTEMS, | | | EQUIPMENT, FIXTURES AND OTHER COMPONENTS SYSTEM SHALL | | | BE INSTALLED ABOVE THE DESIGN FLOOD ELEVATION HEIGHT, | | | OR MEET THE EXCEPTION UNDER 309.2. PROVIDE NOTES ON | | | G-011 THAT ARE APPLICABLE TO THE PLUMBING SYSTEMS. | | | A) P-200: PROVIDE NOTES AND/OR DETAILS ON THE PLAN | | | SHOWING COMPLIANCE WITH 7.3.1 ASCE 24-14: UNDERGROUND | | | PIPING AND PLUMBING SYSTEMS SHALL BE BURIED TO A DEPTH | | | SUFFICIENT TO PREVENT MOVEMENT, SEPARATION, OR LOSS DUE | | | TO FLOODING AND EROSION UNDER DESIGN FLOOD CONDITIONS. | | | B) P-200: OPENINGS IN THE PLUMBING SYSTEMS BELOW THE | | | DESIGN FLOOD ELEVATION HEIGHT SHALL BE PROTECTED WITH | | | AUTOMATIC BACKWATER VALVES. SHOW COMPLIANCE WITH NOTES | | | AND DETAILS ON THE PLANS. IT APPEARS THAT THE TRENCH | | | DRAIN AND HUB DRAIN OPENINGS IN THE LOADING DOCK AREA, | | | AND THE FLOOR DRAIN IN THE PUMP ROOM ARE BELOW THE | | | HEIGHT AND WILL REQUIRE THE VALVES- SEC. 714.1 FBC P. | | | | | | 11) P-200: PROVIDE NOTES TO INDICATE THE GREASE | | | INTERCEPTOR AND SOLIDS INTERCEPTOR WILL BE INSTALLED IN | | | A WATER TIGHT CONCRETE VAULT WITH SEALED, WATER TIGHT | | | MANHOLE COVERS- SEC. 309.2 FBC P AND SEC. 7.3.2 ASCE | | | 24-14. PROVIDE DETAILS ON THE PLAN AND MARKUP ALL | | | APPLICABLE INSTALLATION DETAILS SHOWN ON P-504 | | | INCLUDING THE INSTALLATION OF A MINIMUM 8-INCH SLAB ON | | | TOP OF THE VAULT. | | | | | | 12) P-200: COMMENT #11 IS ALSO APPLICABLE TO THE OIL | | | INTERCEPTOR. PROVIDE INSTALLATION DETAILS AND NOTES ON | | | THE PLAN, AND SUBMIT MANUFACTURERS INSTALLATION | | | GUIDELINES FOR HIGH WATER AND HYDROSTATIC PRESSURE | | | CONDITIONS, AND FOR VEHICULAR LOAD PROTECTION. | | | | | | 13) P-200: PROVIDE RAIN WATER CISTERN INSTALLATION | | | DETAILS AND NOTES ON THE PLAN AND SUBMIT MANUFACTURERS | | | SPECIFICATIONS FOR THE TANK AND THE MANHOLE COVER. THE | | | TANK AND COVER SHALL BE WATER TIGHT AND DESIGNED TO | | | WITHSTAND HIGH WATER AND HYDROSTATIC PRESSURE | | | CONDITIONS- SEC.- 309.2 FBC P AND SEC. 7.3.2 ASCE | | | 24-14. | | | | | | 14) P-200: VERIFY THE PUMPS HAVE ADEQUATE SEALS TO | | | RESIST FLOOD WATER INTRUSION- SEC. 309.2 AND SEC. 7.3.3 | | | ASCE 24-14. | | | | | | 15) P-200: A WASTE RECEPTOR IS NOT SHOWN IN THE TRASH | | | COMPACTOR AREA. PLEASE REVIEW MANUFACTURER'S | | | SPECIFICATIONS AND MAINTENANCE GUIDELINES. THE | | | MANUFACTURER MAY RECOMMEND INSTALLATION OF A RECEPTOR | | | AND DRAIN TO CONVEY HYDRAULIC FLUID AND OTHER LIQUID | | | WASTES FROM THE COMPACTOR TO APPROVED PLACES OF | | | DISPOSAL- SEC. 107.2.1 WPB. | | | 16) P-201: THERE APPEARS TO BE A DRAIN PIPE PENETRATING | | | INTO EXIT STAIR B WHICH IS PROHIBITED PER SEC. 1023.5 | | | FBC B. | | | | | | 17) P-805: THE 6-INCH SANITARY DRAIN PIPES APPEAR TO BE | | | MISLABELED AS COOLING DRAINS WITH NOTES AT THE 4TH AND | | | 6TH FLOORS. ARE THESE NOTES MEANT TO INDICATE | | | CONDENSATE DRAINS? FOR CLARITY PLEASE PROVIDE A | | | SEPARATE CONDENSATE DISPOSAL RISER DRAWING, AND NOTE | | | THAT CONDENSATE SHALL NOT DRAIN INTO THE SANITARY | | | SYSTEM- SEC. 90-126 (5) WPB CODE OF ORDINANCES. | | | | | | 18) P-200, P-803 & P-805: | | | A) CORRECT THE 839 DFU TOTAL FOR THE 8-INCH (SS/3) | | | SHOWN ON P-803. THE RISER ON P-805 SHOWS 155 DFU'S FOR | | | THE PIPE- SEC. 107.2.1 WPB. | | | B) HD-B IS MISLABELED AS THE 8-INCH COOLING TOWER DRAIN | | | ON P-200. PLEASE CORRECT- SEC. 107.2.1 WPB. | | | C) P-805: SHOW THE LOCATION OF THE 6-INCH VENT STACK | | | CONNECTION AT THE BASE OF THE 8-INCH SOIL STACK (SS/1)- | | | SEC. 904.4 FBC P. | | | D) P-803: THE 6-INCH AND 4-INCH RELIEF VENTS NOTED ARE | | | INCORRECTLY SIZED PER SEC. 908.1 FBC P. THE VENTS SHALL | | | BE 3-INCH AND 4-INCH IN SIZE. PLEASE SHOW THE RELIEF | | | VENT PIPE RUNS ON THE RISER. | | | E) P-803: A 3-INCH RELIEF VENT IS REQUIRED ON LEVEL 5 | | | FOR THE 4-INCH STACK- SEC. 908.1 AND 908.2. | | | F) P-803: SHOW THE LOCATIONS OF THE REQUIRED 6-INCH | | | RELIEF VENTS FOR THE 6-INCH STACK (SS/1)- SEC. 908.1 & | | | 908.2. | | | | | | 19) P-200, P-601, & P-801: PLEASE PROVIDE A SCHEDULE | | | FOR THE DOMESTIC, FIRE, IRRIGATION, AND COOLING TOWER | | | WATER SUPPLY BACKFLOW PREVENTERS SHOWN ON THE PLANS- | | | SECS. C, D, & E WPB UTILITIES CROSS CONNECTION MANUAL. | | | | | | 20) P-200 & P-804: THE STORM RISER DOES NOT SHOW THE | | | VERTICAL RW DRAIN CONNECTIONS TO HORIZONTAL UNDERGROUND | | | DRAINS INCLUDING THE 12-INCH RW CONNECTION TO THE MAIN | | | 15-INCH STORM DRAIN- SEC. 1101.2 FBC P. | | | | | | 21) P-501- FBC C P: | | | A) DETAIL 5- PROVIDE AN OVERFLOW DRAIN DETAIL- SECS. | | | 1105.1 & 1108.1. | | | B) DETAIL 7- SHOW A MEANS OF THERMAL EXPANSION CONTROL | | | FOR THE WATER HEATER- SEC. 607.3. | | | C) DETAIL 7- THE HWR LINE SHALL MAKE CONNECTION INTO | | | THE THERMOSTATIC MIXING VALVE- SEC. 607.2.2 | | | D) DETAIL 11- A DEDICATED SHUT OFF VALVE IS REQUIRED | | | FOR SUPPLY LINE TO THE WATER HEATER- SEC. 503.1. | | | E) DETAIL 11- INDICATE HOW TEMPERED WATER WILL BE | | | DELIVERED FROM THE LAVATORIES- SECS. 419.5 & 607.1.2. | | | | | | 22) P-208 & P-801: SHOW HW, HWR, & CW WATER SUPPLY | | | BRANCH AND FIXTURE PIPING RUNS AND CONNECTIONS TO THE | | | FIXTURES ON THE FLOOR PLAN, AND PROVIDE AN ENLARGED | | | WATER RISER DRAWING- SECS.107.2.1 & 107.3.5.1.3 WPB. | | | REFER TO NOTE ON P-801. | | | | | | 23) A- 101, 102, 103, 104, 108 & P-201, 202, 203, 204, | | | 208: LABEL THE BATHROOMS AND TOILETS ROOMS AS EITHER | | | MALE, FEMALE, OR UNISEX- SEC. 403.2 FBC P. IDENTIFY THE | | | LOCATIONS OF REQUIRED SERVICE SINKS AND DRINKING | | | FOUNTAINS AND INCLUDE PIPING DETAILS- SEC. 107.2.1 WPB. | | | | | | 24) A-108: PROVIDE PLUMBING FIXTURE CALCULATIONS FOR | | | THE 8TH FLOOR BATH AND TOILET ROOMS. PROVIDE A SCHEDULE | | | THAT INDICATES THE REQUIRED AND PROVIDED NUMBER OF | | | FIXTURES- TABLE 403.2 FBC P. PLEASE NOTE THAT DRINKING | | | FOUNTAINS AND SERVICE SINKS ARE REQUIRED FIXTURES FOR A | | | AND B OCCUPANCIES. IDENTIFY THE LOCATIONS AND PROVIDE | | | PLUMBING PIPING DETAILS- SEC. 107.2.1 WPB. | | | | | | 25) A-660- A-108: ENLARGED DRAWINGS AND DETAILS FOR THE | | | ACCESSIBLE 8TH FLOOR TERRACE SINGLE USER TOILET ROOMS | | | NOT PROVIDED- SEC. 107.2.1 WPB. | | | | | | 26) A-660 DETAILS 1 & 7: THE DIMENSIONS OF THE CLEAR | | | FLOOR SPACES FOR THE WATER CLOSETS AND LAVATORIES ARE | | | NOT SHOWN- SECS. 604.3 & 606.2 FBC ACC. | | | | | | 27) A-660 DETAILS 1 & 7: THE DIMENSIONS OF THE TURNING | | | CIRCLES NOT SHOWN- SEC. 304.3 FBC ACC. | | | | | | 28) A-660 & G-009- MISSING OR INCORRECT ACCESSIBLE | | | BATHROOM DETAILS PER FBC ACC. | | | A) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE | | | WALLS- SEC. 604.2. | | | B) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO | | | THE REFLECTIVE SURFACES- SEC. 603.3 | | | C) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4, | | | FIGURES 604. NOTE: MEASUREMENTS SHOWN ARE NOT TO THE | | | TOPS OF THE GRIPPING SURFACES. | | | D) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. | | | 606.2 | | | E) THE ACCESSIBLE TRANSFER SHOWERS SHALL BE 36 X 36 | | | INCHES CLEAR INSIDE DIMENSIONS- SEC. 608.2.1 WPB. THE | | | PLAN SHOWS 48-INCH WIDE SHOWERS THAT ARE NOT IN | | | COMPLIANCE. | | | F) SHOW THE CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS | | | FOR THE SHOWER- SEC. 608.2.1 | | | G) SHOW THE LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF | | | GRAB BARS FOR THE ACCESSIBLE SHOWER- SECS. 608.3 AND | | | 608.3.1 | | | H) LOCATIONS OF CONTROLS, FAUCETS, AND SHOWER SPRAYS IN | | | THE SHOWERS- SEC. 608.5.1. | | | I) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6. | | | J) ENLARGED ACCESSIBLE SHOWER SEAT DETAILS- SECS. | | | 610.3- 610.3.2. | | | | | | 29) A-811: ACCESSIBLE VANITY SINK KNEE AND TOE SPACE | | | CLEARANCES NOT SHOWN IN ACCORDANCE WITH SECS. & FIGURES | | | 306.2 & 306.3 FBC ACC. | | | | | | 30) P-224: THE FCU 24-02 IS PROHIBITED FROM BEING | | | INSTALLED IN THE INTERIOR EXIT STAIRWAY- SEC. 1023.5 | | | FBC P. | | | | | | 31) PROVIDE A CONDENSATE DISPOSAL RISER- SEC. | | | 107.3.5.1.3 WPB. | | | | | | 32) DEFERRED SUBMITTALS: PLEASE PROVIDE A LIST OF | | | DEFERRED SUBMITTALS INCLUDING, BUT NOT LIMITED TO WATER | | | HEATERS, EXPANSION TANKS, RECIRCULATION PUMPS, SUMP | | | PUMPS, MASTER AND POINT OF USE THERMOSTATIC MIXING | | | VALVES, BACKFLOW PREVENTERS, TRAP PRIMERS, WATER HAMMER | | | ARRESTORS, ACCESSIBLE PLUMBING FIXTURES, AND ROOF AND | | | OVERFLOW DRAINS- SEC. 107.3.4.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-18 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-15 |
Time |
08:03 |
Sent To |
|
|
| Notes |
| 2022-07-18 11:46:00 | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE GREASE | | | INTERCEPTOR AND SOLIDS INTERCEPTOR, AND THE OIL | | | SEPARATOR. |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-18 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-15 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2022-07-18 11:46:56 | A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR THE | | | IRRIGATION SYSTEM. |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
9 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-09-01 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-09-01 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
8 |
Status |
P |
Date |
2022-08-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-08-19 |
Time |
06:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-17 |
Time |
12:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
7 |
Status |
P |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-12 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-12 |
Time |
15:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
6 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-06-30 |
Time |
10:06 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-30 |
Time |
10:06 |
Sent To |
|
|
| Notes |
| 2022-06-30 10:28:42 | FS553.791, AFFIDAVIT IS NOT CONSISTENT WITH THE | | | DOCUMENTS UPLOADED, AND IT DOES NOT APPEAR THAT ALL | | | REQUIRED PAGES WERE SUBMITTED. | | | | | | FOR INSTANCE, THE FOLLOWING PAGES ARE ON THE INDEX BUT | | | WERE NOT UPLOADED TO PROJECTDOX AND ARE NOT INCLUDED IN | | | THE AFFIDAVIT. IT APPEARS THAT LIFE SAFETY PAGES AND | | | THE MISSING STRUCTURAL PAGE ARE REQUIRED, UNCLEAR IF | | | OTHER PAGES ARE REQUIRED. | | | | | | LS-116 TOWER - SIXTEENTH FLOOR PLAN - EMR (APPEARS TO | | | BE REQUIRED) | | | LS-117 TOWER - SEVENTEENTH FLOOR PLAN - EMR (APPEARS TO | | | BE REQUIRED) | | | A-405 FIFTH FLOOR - REFLECTED CEILING PLAN | | | A-406 SIXTH FLOOR - REFLECTED CEILING PLAN | | | A-540A EXTERIOR WALL TYPE 01 - TEE ALTERNATE | | | A-631 ELEVATOR LOBBY | | | A-800 TYPICAL LOBBY DETAILS | | | S-127 MECHANICAL DUNNAGE FRAMING (APPEARS TO BE | | | REQUIRED) | | | | | | THE FOLLOWING PAGES WERE UPLOADED, ARE INCLUDED IN THE | | | INDEX, BUT I WAS UNABLE TO LOCATE THEM ON THE | | | AFFIDAVIT: | | | | | | A-415 TYPICAL MID RISE REFLECTED CEILING PLAN | | | A-421 TYPICAL HIGH RISE REFLECTED CEILING PLAN | | | | | | A-821 WAS NOT UPLOADED TO PROJECTDOX BUT IS ON THE | | | AFFIDAVIT. | | | | | | PLEASE CHECK ALL. THIS MAY NOT BE A COMPLETE LIST. THE | | | AFFIDAVIT IS TO INCLUDE ALL FBC ITEMS WITH THE REVISION | | | DATE OF THE PLAN PAGES UPLOADED. THE SUBMITTAL IS TO | | | INCLUDE ALL DOCUMENTS REQUIRED TO DEMONSTRATE CODE | | | COMPLIANCE. ALL PAGES LISTED ON THE AFFIDAVIT ARE | | | REQUIRED TO BE UPLOADED OR, IF NOT NECESSARY, REMOVED | | | FROM THE AFFIDAVIT. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
5 |
Status |
F |
Date |
2022-06-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-06-24 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-23 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2022-06-23 13:52:36 | FS553.791, AFFIDAVIT REVIEW: | | | | | | 1. SHEETS A-003, A-004, A-780 HAVE DATES THAT DO NOT | | | MATCH THE AFFIDAVIT. | | | | | | 2. SHEET A-365, A-613, A-625, A-661 ARE 75% | | | CONSTRUCTION DOCUMENTS, SUBMIT 100% DRAWING. DATES DO | | | NOT MATCH THE AFFIDAVIT. | | | | | | 3. SHEET A-545 WAS UPLOADED TWICE WITH TWO DIFFERENT | | | NAMES SO THE FILE DID NOT VERSION PROPERLY. EACH FILE | | | NAME SHOULD BE UNIQUE SO IT CORRESPONDS WITH THE PAGE | | | LISTED ON THE AFFIDAVIT. | | | | | | 4. SHEET A-821 WAS REMOVED FROM THE AFFIDAVIT (WAS | | | PREVIOUSLY ON AFFIDAVIT, NOT IN PROJECTDOX), BUT IS | | | STILL ON THE INDEX. | | | | | | 5. REVIEW FROM 5/28, COMMENT #7 DOES NOT APPEAR TO BE | | | ADDRESSED: | | | | | | UNABLE TO LOCATE AN AFFIDAVIT FOR FIRE ALARM, TELECOM, | | | SECURITY DRAWINGS. | | | | | | 6. PLEASE CHECK ALL. | | | | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
4 |
Status |
F |
Date |
2022-06-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-06-03 |
Time |
07:14 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-01 |
Time |
07:46 |
Sent To |
|
|
| Notes |
| 2022-06-02 17:09:17 | 6/3 - REVIEW OF AFFIDAVIT WILL BE DONE AFTER APPLICANT | | | HAS UPLOADED ALL PLANS TO SATISFY OUTSIDE ENTITIES AND | | | AFTER ENGINEERING, FIRE, ZONING HAVE APPROVED THOSE | | | PLANS/THEIR REVIEWS. THERE ARE CURRENTLY TWO DIFFERENT | | | VERSIONS OF CIVIL PLANS UPLOADED SO IT IS NOT CLEAR | | | WHAT ENGINEERING, FIRE, ZONING REVIEWED. THE MULTIPAGE | | | PDF WAS UPLOADED IN A MANNER THAT MADE THE SUBMITTAL | | | EXTREMELY DIFFICULT TO FIND. THE NEW ENGINEERING PLAN | | | WAS UPLOADED AFTER ZONING PASSED THE REVIEW ON 4/8 BUT | | | BECAUSE THE OLD CIVIL PAGES WERE NOT SUPERSEDED AS | | | REQUIRED, IT WAS NOT ROUTED TO ZONING AND FIRE REVIEW. | | | YOU CANNOT HAVE TWO DIFFERENT VERSIONS/DESIGNS OF THE | | | SAME PAGES UPLOADED TO PROJECTDOX. | | | | | | | | | ****************************************************** | | | 6/1 - AFFIDAVIT REVIEW IN PROGRESS (NOT COMPLETE) | | | | | | 1. THIS PROJECT CANNOT GO TO BUILDING DIVISION AUDIT | | | UNTIL THE ENGINEERING ISSUE IS RESOLVED. ENGINEERING | | | PASSED THE REVIEW WITH PROVISO TO UPLOAD THE APPROVED | | | ENGINEERING PLANS. THERE ARE 28 CIVIL PAGES UPLOADED TO | | | PROJECTDOX THAT ARE OUTDATED (PER ENGINEERING). THEY | | | WERE UPLOADED IN MARCH AND ARE NOT THE APPROVED PLANS. | | | A MULTIPAGE PDF (30 PAGES) WAS UPLOADED TO THE DRAWINGS | | | FOLDER RATHER THAN SUPPORTING DOCS. DUE TO THE NAME | | | THAT THE FILE WAS NAMED (APPROVED ENGINEERING PLANS), | | | THIS FILE WAS NUMBER 765 IN THE DRAWINGS FOLDER IN | | | PROJECTDOX. THIS DOES NOT MEET ENGINEER'S PROVISO AND | | | WAS ALSO NOT SEEN BY ZONING AND FIRE. ZONING PASSED THE | | | PROJECT ON 4/8, THE NEW ENGINEERING PLANS UPLOADED ON | | | 4/27. | | | | | | 2. SEE PREVIOUS LIST, A-821 IS NOT IN PROJECTDOX, NOT | | | ON THE AFFIDAVIT, BUT IT IS INCLUDED IN THE INDEX. | | | | | | | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2022-05-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-05-28 |
Time |
13:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-05-24 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2022-05-28 13:34:37 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FS553.791, AN ACCURATE AFFIDAVIT IS REQUIRED PRIOR TO | | | BUILDING DIVISION AUDIT. | | | | | | 1. ELECTRICAL AFFIDAVIT LACKS THE NAME OF THE DESIGN | | | PROFESSIONAL. | | | 2. E-339.A DATE ON THE PLAN DOESN'T MATCH THE | | | AFFIDAVIT. PLAN UPLOADED IS 75%. ALL DOCUMENTS SHOULD | | | BE 100% CONSTRUCTION DRAWINGS. | | | 3. MECHANICAL PAGES APPEAR OK BUT AFFIDAVIT LACKS THE | | | NAME OF THE DESIGN PROFESSIONAL, VERIFY ALL. | | | 4. M703 WAS UPLOADED TO PROJECTDOX, BUT LOCKED AT | | | APPLICANT'S REQUEST. PLEASE REQUEST THAT ALL LOCKED | | | FILES BE DELETED. IT APPEARS THAT THESE ARE SOME FILES | | | THAT SHOULD BE DELETED: | | | A405, A406, A420 | | | 248 WIND DIAGRAMS (DUPLICATE, NOT LOCKED) | | | 5. S-012 WAS UPLOADED TWICE, ONCE INCORRECTLY NAMED, | | | REQUEST THAT IT BE DELETED. | | | 6. A-821, A-415, A-421 ARE NOT ON THE AFFIDAVIT, UNABLE | | | TO LOCATE IN PROJECTDOX. | | | 7. UNABLE TO LOCATE AN AFFIDAVIT FOR FIRE ALARM, | | | TELECOM, SECURITY DRAWINGS. | | | 8. CHECK ALL, THIS LIST MAY NOT BE A COMPLETE LIST OF | | | ALL ERRORS/DISCREPANCIES. | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2022-05-01 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-04-30 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-04-30 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-30 19:27:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FS553.791, AN ACCURATE AFFIDAVIT IS REQUIRED PRIOR TO | | | BUILDING DIVISION AUDIT. | | | | | | 1. G000 IS LISTED ON THE BUILDING AFFIDAVIT, UNABLE TO | | | LOCATE IN THE SUBMITTAL. (OTHER G SHEETS ON AFFIDAVIT | | | OK) | | | 2. A365 ON AFFIDAVIT IS A DIFFERENT DATE THAN WHAT WAS | | | UPLOADED. THE FILE UPLOADED IS A 75% DRAWING. THIS | | | COMMENT ALSO APPLIES TO OTHERS INCLUDING A405, A406, | | | A420, A545. CHECK ALL. | | | 3. A545, TWO VERSIONS OF THE SAME PAGE WAS UPLOADED. | | | PLEASE VERSION PLANS CORRECTLY AND CONTACT | | | [email protected] TO REMOVE PAGES THAT NEED TO BE | | | DELETED. CHECK ALL. | | | 4. M703 IS NOT INCLUDED IN THE AFFIDAVIT AND IS A 75% | | | DRAWING. | | | 5. ELECTRICAL AFFIDAVIT STATES THERE ARE 140 PAGES, 142 | | | ARE ON THE LIST. | | | 5. 142 ELECTRICAL PAGES ARE ON THE AFFIDAVIT, 133 PAGES | | | WERE UPLOADED. A FEW EXAMPLES OF MISSING PAGES: E339.A, | | | E339.B, E340.A, E340.B. CHECK ALL. | | | 6. I WAS UNABLE TO LOCATE AFFIDAVITS FOR ALL PAGES, FOR | | | EXAMPLE FA, TC, SE PAGES. | | | 7. PLUMBING AFFIDAVIT APPEARS OK, BUT PLEASE VERIFY. | | | 8. S-012 IS NOT NAMED PROPERLY IN PROJECTDOX, PLEASE | | | UPLOAD FILE PROPERLY NAMED AND REQUEST TO HAVE THE | | | PREVIOUSLY UPLOADED PAGE DELETED (EMAIL | | | [email protected]). | | | 9. I WAS UNABLE TO LOCATE SHEET S-413 IN PROJECTDOX BUT | | | IT IS INCLUDED ON THE STRUCTURAL AFFIDAVIT. | | | 10. SHEET S-600 WAS UPLOADED TO PROJECTDOX BUT IS NOT | | | INCLUDED ON THE AFFIDAVIT. | | | 11. CHECK ALL, THIS LIST MAY NOT BE A COMPLETE LIST OF | | | ALL ERRORS/DISCREPANCIES. | | | 12. COURTESY NOTICE - THIS PROJECT HAS A FAILED | | | ADDRESSING REVIEW. NOTE THAT THE PERMIT CARD WILL NOT | | | PRINT WITH A FAILED REVIEW, PLEASE RESOLVE AT | | | APPLICANT'S CONVENIENCE. | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2021-08-19 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-08-17 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-08-17 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2021-08-19 13:49:15 | PLEASE PROVIDE CERTIFICATE OF INSURANCE (COI) | | | ALSO, PLEASE PROVIDE QUALIFICATIONS FOR REVIEWERS AND | | | INSPECTORS WITH THEIR LICENSES. | | | | | | FOR PLAN REVIEW PROVIDE PRIVATE PROVIDER PLAN REVIEW | | | COMPLIANCE AFFIDAVIT. | | | | | | UPLOAD ALL DOCUMENTS INTO THE SUPPORTING DOCUMENTS | | | FOLDER. | | | | | | DYLAN BATTLES | | | 561-805-6718 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-15 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-15 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2022-07-15 09:26:07 | ROOFING SYSTEM TO BE DEFERRED |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-02 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-02 |
Time |
13:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-15 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-15 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2022-07-15 09:27:00 | SEE FOUNDATION PERMIT 21080908 | | 2022-06-03 07:24:50 | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2022-04-06 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2022-03-11 |
Time |
14:12 |
Sent To |
|
|
| Notes |
| 2022-04-06 14:57:45 | PROVISO: | | | 1. UTILITY LINES (STORM) ALONG LAKEVIEW AND OKEECHOBEE | | | SHALL BE COORDINATED TO AVOID ANY CONFLICT WITH | | | PROPOSED TREES. | | | 2. PARKING SPACE P14 ON THE 3RD FLOOR SHALL BE LABEL AS | | | COMPACT SPACE. | | | 3. FINAL SPEC FOR THE LIGHT FIXTURES AND POLES ALONG | | | THE STREET FRONTAGE SHALL BE COORDINATED AND APPROVED | | | BY THE CITY AS A SEPARATE ELECTRICAL PERMIT. | | | 4. A TRANSPORTATION DEMAND MANAGEMENT AGREEMENT LISTING | | | ALL TDM INITIATIVES REQUIRED FOR THE PROJECT SHALL BE | | | APPROVED BY THE CITY BEFORE FINAL CO. | | | 5. PROJECT SHALL OBTAIN LEED SILVER CERTIFICATION. | | | 6. APPLICANT SHALL OBTAIN FDOT APPROVAL FOR ALL | | | PROPOSED IMPROVEMENTS ON FDOT ROW ACCORDING WITH THE | | | SITE PLAN. | | | 7. PROPERTY SHALL BE REPLATTED BEFORE FINAL CO. | | | 8. FINAL LOCATION OF THE TENDER HOUSE PARKING SHALL BE | | | APPROVED BY THE CITY. | | | 9. PAYMENT FOR THE PARKING ABOVE MINIMUM ALLOWED IS | | | REQUIRED (60 SPACES*862=$51,720 PER YEAR) . | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-24 |
|
|
Cont ID |
|
| Sent By |
aaponta |
Date |
2022-01-24 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2022-01-24 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2022-01-24 11:51:23 | 1. PLEASE CHECK CONFLICT WITH STORM LINE TO REMAIN | | | ALONG LAKEVIEW AVENUE AND THE PROPOSED STREET TREES | | | (SHEET C-200) | | | 2. PLEASE CHECK CONDLICT WITH STORM LINE ON SOUTH SIDE | | | OF CHURCH AND THE PROPOSED TREES (SHEET C-400) | | | 3. PLEASE PROVIDE AN OUTLINE OF EXISTING ELEVATION OVER | | | THE PROPOSED STREET SECTIONS TO COMPARE THE DIFFERENCE | | | BETWEEN EXISTING SIDEWALK/CURB/PLANTING ELEVATION AND | | | PROPOSED. | | | 4. SHEET C-702 SHALL BE RENAMED AS VALET OPERATIONS ARE | | | NOT PERMITTED WITHIN THE PORTE COCHERE ALONG LAKEVIEW | | | AVENUE. | | | 5. PLEASE DISCUSS THE POSSIBILITY TO EXTEND THE FLAGLER | | | DRIVE MEDIAN TO PROVIDE BETTER PROTECTION TO | | | PEDESTRIANS CROSSING FROM NE CORNER OF PROJECT. HIGH | | | VISIBILITY PEDESTRIAN STRIPING SHALL BE PROVIDED. SHEET | | | C-800. | | | 6. PLEASE EXPLAIN HOW THE DIAGRAM SHOWING OPEN/ | | | ENCLOSED AREA IN THE GARAGE (SHEET LS-001) WILL IMPACT | | | THE LOCATION OF THE GREEN SCREEN WITH PLANT MATERIAL | | | PROPOSED FOR THE GARAGE. | | | 7. PLEASE EXPLAIN HOW THE TWO SPACES NORTH OF THE RAMP | | | ON THE 2ND FLOOR WORK. THEY DON'T SEEM TO HAVE A DRIVE | | | AISLE. | | | 8. PLEASE DIMENSION THE PARKING GARAGE TO CONFIRM | | | COMPLIANCE WITH DRIVE AISLE WIDTH AND PARKING SPACE | | | WIDTH AND LENGHT. | | | 9. PLEASE REMOVE WHEEL STOPS FROM THE TANDEM PARKING | | | SPACES. | | | 10. PLEASE INLCUDE CALL OUT MATERIALS ON FACADE | | | DRAWINGS. | | | 11. AMOUNT OF LOVERS INCLUDED AT THE GROUND LEVEL | | | DIFFERS FROM THE DAC APPROVAL. DAC APPROVAL INCLUDED | | | SPANDREL GLASS TO HIDE UTILITY ROOM OR NON-ACIVE | | | USES.PLEASE ADJUST OR JUSTIFY CHANGE. | | | 13. SECTIONS IN SHEET A-250, A-251 AND A-252 SHALL | | | INCLUDE THE SIDEWALK ELEVATION, PLANTING AREA AND | | | TRAVEL LANES. | | | 14. DAC APPROVAL INCLUDED A STEP DOWN DESIGN FOR THE | | | RESTAURANT PATIO. PROPPOSED DESIGN IS A SINGLE LEVEL | | | LOCATED 3'-6" ABOVE THE PARK LEVEL, BREAKING THE | | | RELATIONSHIP BETWEEN THE RESTAURANT OUTDOOR DINING AND | | | THE PARK ORIGINALLY PROPOSED. | | | 15. PLEASE PROVIDE SPEC DETAILS FOR FIXTURE ELC AND | | | ELC2 SPECIFIED AS THE STREET FIXTURE (NOT LISTED IN | | | SHEET E-330) . FURTHER DISCUSSION NEEDED REGARDING THE | | | FIXTURES AND POLES TO MATCH SURROUNDING. | | | 16. PLEASE PROVIDE GENERAL PROJECT DATA INFORMATION ON | | | THE SITE PLAN SHEET, INCLUDING SITE AREA, ALLOWABLE | | | GBA, PROPOSED GBA FOR OFFICE, RESTAURAN + CHUCH, | | | PARKING SPACES REQUIRED/PROVIDED PER NET AREA, BIKE | | | PARKIGN REQUIRED/PROVIDED. | | | 17. PLEASE SUBMIT ZONING SUPPORTING INFORMATION TO | | | CONFIRM COMPLIANCE WITH MINIMUM SETBACKS, MAX BUILDING | | | FOOTPRINT, PLANAR BREAKS ETC (AS INCLUDED IN SITE PLAN | | | APPROVAL). | | | 18. A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED | | | INCLUDING ALL CALCULATIONS TO CONFIRM COMPLIANCE WITH | | | PUBLIC AND PRIVATE OPEN SPACE REQUIREMENTS. | | | 19. PLEASE PROVIDE DETAIL INFORMATION REGARDING THE | | | GREEN LIVING SCREEN PROPOSED FOR THE PARKING GARAGE. | | | 20. PLEASE PROVIDE INFORMATION REGARDING COMPLIANCE | | | WITH REQUIRED TDMS FOR THE OBD. | | | 21.PLEASE PROVIDE INFORMATION TO CONFIRM THE PROJECT IS | | | CONDUCTING THE PROCESS FOR LEED GOLD CERTIFICATION | | | REQUIRED FOR THE OBD INCENTIVE. | | | 22. PLEASE PROVIDE INFORMATION REGARDING THE PROPOSED | | | PEDESTRIAN CROSSING ENHANCEMENTS AT THE PROJECT | | | CORNERS. | | | 23. PLEASE PROVIDE INFORMATION TO CONFIRM APPROVAL FROM | | | FDOT FOR THE IMPROVEMENTS WITHIN THE LAKEVIEW AND | | | OKEECHOBEE ROW. | | | 24. PROPERTY SHALL BE RE-PLATTED. | | | FOR ADDITIONAL INFORMATIONS PLEASE CONTACT ANA MARIA | | | APONTE AT 561-822-1439. |
|
|