Plan Review Details - Permit 21080887
Plan Review Stops For Permit 21080887
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-13 Cont ID  
Sent By rmcdouga Date 2021-10-13 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2021-10-13 Time 16:51 Sent To  
Notes
2021-10-13 16:59:41CONTRACTOR EMAILED PERMISSION TO CHANGE NOTE ON THE
 SURVEY TO REQUIRE THE GENERATOR EXHAUST TO BE 10' FROM
 OPENINGS INTO THE BUILDING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-15 Cont ID  
Sent By rmcdouga Date 2021-09-15 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2021-09-15 Time 15:57 Sent To  
Notes
2021-09-15 16:06:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. PLEASE NOTE
 THIS ON THE SURVEY.
  
 R303.5.1 INTAKE OPENINGS
  
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
 FOR THE PURPOSE OF THIS SECTION, THE EXHAUST FROM
 DWELLING UNIT TOILET ROOMS, BATHROOMS AND KITCHENS
 SHALL NOT BE CONSIDERED AS HAZARDOUS OR NOXIOUS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-02 Cont ID  
Sent By jleahy Date 2021-09-02 Time 16:06 Rev Time 0.00
Received By jleahy Date 2021-08-18 Time 15:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-15 Cont ID  
Sent By rmcdouga Date 2021-09-15 Time 16:07 Rev Time 0.00
Received By rmcdouga Date 2021-08-18 Time 07:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-18 Cont ID  
Sent By jleahy Date 2021-08-18 Time 16:08 Rev Time 0.00
Received By jleahy Date 2021-08-18 Time 15:16 Sent To  
Notes
2021-08-18 16:08:53SENT SIGNED SLAB PLAN TO STORAGE JLEAHY

Review Stop Z ZONING
Rev No 1 Status P Date 2021-08-31 Cont ID  
Sent By kalexand Date 2021-08-31 Time 18:04 Rev Time 0.00
Received By kalexand Date 2021-08-31 Time 18:04 Sent To  
Notes
***NONE***