Plan Review Details - Permit 21080869
Plan Review Stops For Permit 21080869
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-08-31 Cont ID  
Sent By cpuell Date 2021-08-31 Time 13:20 Rev Time 0.00
Received By cpuell Date 2021-08-31 Time 13:20 Sent To  
Notes
2021-08-31 13:21:04ADDRESS ADDED TO COMMUNITY PLUS

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 10:43 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 10:43 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 11:30 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 11:30 Sent To  
Notes
2021-11-17 11:30:58PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 09:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-01-13 Cont ID  
Sent By rmcphers Date 2022-01-13 Time 13:28 Rev Time 0.00
Received By rmcphers Date 2022-01-13 Time 13:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 10:43 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 10:37 Sent To  
Notes
2021-12-15 10:43:11REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE E MAIL THE [email protected] AND ASK
 THEM TO REMOVE THE DRAWINGS FROM PROJECTDOX THAT DO NOT
 PERTAIN TO THIS PERMIT.
  
  
 2) FOR THE FLOORING OTHER THAN CARPET PLEASE PROVIDE
 THE FOLLOWING ACOUSTICAL TEST REPORTS - OR ADD THE
 REQUIRED TEST REPORTS FOR THE FLOORING IIC AND STC TO
 THE ITEMS TO BE DEFERRED ON DRAWING T1.0
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 11:29 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 11:19 Sent To  
Notes
2021-11-17 11:29:49REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A GENERAL STATEMENT AS TO THE FIRE
 CLASSIFICATION OF FINISHES - PLEASE SHOW THE REQUIRED
 FIRE CLASSIFICATIONS FOR THE WALL FINISHES, CEILING
 FINISHES AND FLOORING FINISHES FBC CHAPTER 8
  
 2) PRODUCT APPROVAL PROVIDED FOR THE ROOFING = ROOFING
 SYSTEM TO BE USED ON THE PROVIDED PRODUCT APPROVAL
 REQUIRES ADDITIONAL SIGNED AND SEALED ATTACHMENT
 DETAILS FROM AN ARCHITECT OR ENGINEER FOR ROOF WIND
 ZONES 2 AND 3 WHICH REQUIRE A HIGHER PRESSURE THAN THE
 MAXIMUM SHOWN ON THE PRODUCT APPROVAL (-60) - SEE
 GENERAL LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL.
  
 3) ALL PRODUCT APPROVALS AND SHOP DRAWINGS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD.
 FBC WPB 107.3.4
  
 4) FOR THE FLOORING OTHER THAN CARPET PLEASE PROVIDE
 THE FOLLOWING ACOUSTICAL TEST REPORTS -
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 09:54 Rev Time 0.00
Received By rmcphers Date 2021-10-13 Time 10:10 Sent To  
Notes
2021-10-14 09:55:11REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE REQUIRED FIRE CLASSIFICATIONS FOR
 THE WALL FINISHES, CEILING FINISHES AND FLOORING
 FINISHES FBC CHAPTER 8
  
 2) DRAWING A0.3 THE EFFICIENCY UNIT MARKED -
 "ACCESSIBLE SHOWER UNIT" - IS NOT MARKED CORRECTLY - IT
 IS NOT THE ACCESSIBLE UNIT - PLEASE CORRECT.
  
 3) PLEASE PROVIDE COMPLETE (FRONT PAGE AND THE
 INSTALLATION INSTRUCTIONS) PRODUCT APPROVALS FOR THE
 NEW EXTERIOR WINDOWS, EXTERIOR DOORS AND ROOFING
 SYSTEM.
  
 4) ALL PRODUCT APPROVALS AND SHOP DRAWINGS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD.
 FBC WPB 107.3.4
  
 5) PLEASE SHOW IF BUILDING IS SPRINKLERED OR NON
 SPRINKLERED FBC CHAPTER 5
  
 6) DRAWING C5.0 - ACCESSIBLE PARKING SPACE SHOULD SHOW
 AS 12 FOOT WIDE. FBC ACCESSIBILITY 502.2
  
 7) FOR THE FLOORING OTHER THAN CARPET PLEASE PROVIDE
 THE FOLLOWING ACOUSTICAL TEST REPORTS -
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 8) WHEN ASKING TO DEFER ITEMS SUCH AS PRODUCT APPROVAL
 OR SHOP DRAWINGS FOR WINDOWS, EXTERIOR DOORS, ROOFING,
 RAILING, ETC. PLEASE PROVIDE A DEFERRED SUBMITTALS LIST
 ON THE DRAWINGS - FBC WPB 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL
 ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A
 NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-14 Cont ID  
Sent By jleahy Date 2021-10-14 Time 15:40 Rev Time 0.00
Received By jleahy Date 2021-10-14 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2023-01-06 Cont ID  
Sent By mpeterso Date 2023-01-06 Time 15:35 Rev Time 0.00
Received By mpeterso Date 2023-01-06 Time 15:35 Sent To  
Notes
2023-01-06 15:36:48ROOM TROUBLE ANNUCIATOR WIRING ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-12-16 Cont ID  
Sent By cwalker Date 2021-12-16 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-10 Cont ID  
Sent By pleduc Date 2021-11-10 Time   Rev Time 0.00
Received By pleduc Date 2021-11-10 Time 14:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-16 Cont ID  
Sent By pleduc Date 2021-09-16 Time   Rev Time 0.00
Received By pleduc Date 2021-09-16 Time 15:52 Sent To  
Notes
2021-09-16 15:53:06THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET S 2.2 - THERE IS AN INDICATION OF A PORTE
 COCHERE WITH A CLEARANCE HEIGHT OF 12'0".
  
 THE REQUIRED HEIGHT OF A FIRE LANE IS 13'6".
  
 AS THE SITE EMERGENCY VEHICLE TRAVEL PATH REQUIRES
 NAVIGATION OF THIS LOW HEIGHT STRUCTURE APPLICABLE
 WARNING SIGNAGE IS NEEDED TO DIRECT TRAFFIC AROUND. NO
 PARKING/FIRE LANE INDICATORS NEED TO BE PLACED AT THE
 GO AROUND LANE TO ENSURE NO PARKING.
  
 ADDITIONALLY, RAISING THE HEIGHT TO 13'6" WOULD ALLOW
 RESCUE VEHICLES TO USE THIS STRUCTURE FOR EMS TRANSPORT
 IN STORMY WEATHER.
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR COMPLIANCE.
  
 2) THERE ARE NO INDICATIONS IF THE BUILDING/ROOMS WILL
 REMIAN OCCUPIED DURING CONSTRUCTION AND WHAT LIFE
 SAFETY MEASURES WILL BE PUT IN PLACE TO MAINTAIN
 REQUIRED EXIT TRAVEL PATHS AND EXIT DISCHARGE.
  
 PLEASE PROVIDE DETAILS.
  
  
 2A) THERE ARE NO INDCATIONS OF FIRE ALARM OR FIRE
 SPRINKLER WORK.
  
 IF APPLICABLE, ALL FIRE SPRINKLER & FIRE ALARM WORK.
 INCLUDING DEMO, SHALL BE DONE UNDER SEPARATE PERMITS &
 SHOP DRAWINGS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT
  
  
 3) THERE ARE INDICATIONS OF BBQ AREAS AT THE PAVILLION.
  
 PLEASE PROVIDE WHAT TYPE OF BBQ, FUEL SOURCE, FUEL
 STORAGE AREA, FIRE EXTINQUISHER LOCATIONS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2021-12-22 Cont ID  
Sent By ccole Date 2021-12-22 Time 10:20 Rev Time 0.00
Received By ccole Date 2021-12-21 Time 15:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-11-19 Cont ID  
Sent By ccole Date 2021-11-19 Time 16:45 Rev Time 0.00
Received By ccole Date 2021-11-18 Time 09:38 Sent To  
Notes
2021-11-19 16:47:032ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21080869
 11/19/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAP LETTERS.
  
 1) FAILED 1F. SHEET P2.4: PROVIDE A COMPLETE GAS RISER
 DRAWING THAT INCLUDES ALL NEW AND EXISTING GAS PIPING
 AND APPLIANCES IN THE BUILDING- SECTIONS 401.3 & 401.4
 FBC FG. THE CURRENT SHOWS ONLY PIPING TO THE DRYERS.
 REFER TO SECTIONS 402.1, 402.2 & 402.3 FBC FG. THE
 RISER SHALL INDICATE:
 F) FAILED. BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 PLEASE PROVIDE THE INDIVIDUAL LOW PRESSURE BRANCH PIPE
 LENGTHS AND THE TOTAL LOW PRESSURE PIPING RUN.
  
 8) FAILED. P2.4: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE GAS-FIRED DRYERS AND INDICATE HOW THE AIR WILL
 BE PROVIDED- SECTION 304.1 FBC FG. PLEASE PROVIDE THE
 COMBUSATION AIR CALCULATIONS ON THE PLAN.
  
 9) FAILED. P2.4: PROVIDE A GAS DRYER EXHAUST DIAGRAM
 INDICATING THE TYPE AND SIZE OF EXHAUST DUCTS, TOTAL
 RUN LENGTH OF THE SYSTEM, AND TERMINATION LOCATION-
 SECTION 614.1 FBC FG. SHOW THE LOCATION OF REQUIRED
 CLEANOUTS- 614.3 AND PROVIDE TERMINATION CAP DETAILS-
 614.4 FBC FG. NOT PROVIDED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-10-13 Cont ID  
Sent By ccole Date 2021-10-13 Time 11:51 Rev Time 0.00
Received By ccole Date 2021-10-13 Time 11:50 Sent To  
Notes
2021-10-13 11:52:491ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21080869
 10/13/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2.4: PROVIDE A COMPLETE GAS RISER DRAWING
 THAT INCLUDES ALL NEW AND EXISTING GAS PIPING AND
 APPLIANCES IN THE BUILDING- SECTIONS 401.3 & 401.4 FBC
 FG. THE CURRENT SHOWS ONLY PIPING TO THE DRYERS. REFER
 TO SECTIONS 402.1, 402.2 & 402.3 FBC FG. THE RISER
 SHALL INDICATE:
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE
 UNIONS.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS OF DRIPS AND SEDIMENT TRAPS.
 J) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) P0.2 & P2.4: PLEASE SHOW THE LOCATIONS OF THE
 REGULATORS, TEE FITTINGS, AND PIPE UNIONS- SECTIONS
 410.2, 410.2(5,6, &7). LIST THE MAKES AND MODELS OF THE
 REGULATORS AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 MARKED UP OR HIGHLIGHTED TO SHOW THE SELECTED MODELS,
 THE MAX INLET AND OUTLET SIZE AND PRESSURES ETC.
  
 3) P0.2: SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR THE WATER HEATERS- SECTION
 624.1 FBC FG. THE CURRENT PLANS DO NOT PROVIDE ENOUGH
 INFORMATION TO PERFORM A COMPLETE REVIEW OF THE WATER
 HEATERS INCLUDING REQUIRED CONDENSATE DISPOSAL, AND
 COMBUSTION AIR AND VENTING PLANS- SEE COMMENTS 4, 5, &
 6 BELOW.
  
 4) P0.1, P2.4: INDICATE THE TYPES AND SIZES OF
 CONDENSATE PIPING FROM THE WATER HEATER AND SHOW THE
 PIPING RUNS FOR THE WATER HEATERS TO THE FLOOR SINK-
 SECTION 307.2 & 307.3 FBC FG. PLEASE NOTE THAT A
 NEUTRALIZING DEVICE MAY BE REQUIRED TO PROTECT THE
 DRAINAGE SYSTEM FROM CORROSIVE WASTE. PLEASE REVIEW THE
 MANUFACTURER'S RECOMMENDATIONS.
  
 5) P0.2 & P2.4: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE GAS WATER HEATERS- SECTION 304.1 FBC FG. THE PLAN
 SHOWS (2) EXISTING 24X16 INCH OPENINGS. REFER TO
 SECTION 304.6.1 FBC FG AND PROVIDE AN ELEVATION DETAIL
 TO SHOW THE REQUIRED OPENING LOCATIONS. PLEASE NOTE THE
 WATER HEATER DIAGRAM SHOWS A 3-INCH COMBUSTION AIR
 INTAKE DUCT ELBOW.
  
 6) P2.4: PROVIDE A VENTING PLAN FOR THE WATER HEATERS
 INCLUDING A DIAGRAM THAT SHOWS THE TYPE AND SIZE OF
 VENT DUCTS, LENGTHS OF VENT CONNECTORS, RISERS, VENT
 TRUNKS AND TOTAL VENT RUN MEASUREMENT TO THE
 TERMINATION CAP ON THE ROOF. CLARIFY HOW THE SYSTEM WAS
 SIZED AND SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 COMPONENTS- SECTIONS 503.1 & 624.1 FBC FG. THE DETAIL
 SHALL SHOW THE ROOF FLASHING AND THIMBLE- SECTION
 503.6.6 AND ALL REQUIRED CLEARANCES- 503.6.4.
  
 7) P0.1 & P2.4: INDICATE THE MAKES AND MODELS OF THE
 DRYERS AND SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION MANUALS. THE CURRENT PLANS DO NOT PROVIDE
 ENOUGH INFORMATION TO PERFORM A COMPLETE REVIEW OF THE
 DRYERS INCLUDING REQUIRED COMBUSTION AIR AND VENTING
 PLANS- SEE COMMENTS 8 & 9 BELOW.
  
 8) P2.4: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED DRYERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SECTION 304.1 FBC FG.
  
 9) P2.4: PROVIDE A GAS DRYER EXHAUST DIAGRAM INDICATING
 THE TYPE AND SIZE OF EXHAUST DUCTS, TOTAL RUN LENGTH OF
 THE SYSTEM, AND TERMINATION LOCATION- SECTION 614.1 FBC
 FG. SHOW THE LOCATION OF REQUIRED CLEANOUTS- 614.3 AND
 PROVIDE TERMINATION CAP DETAILS- 614.4 FBC FG.
  
 10) P0.1: NEW GAS PIPE PENETRATIONS OF THE EXISTING
 SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR
 SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND
 APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-13 Cont ID  
Sent By dbattles Date 2022-01-13 Time 16:30 Rev Time 0.00
Received By dbattles Date 2022-01-13 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-12-22 Time   Rev Time 0.00
Received By aoliver Date 2021-12-13 Time 07:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-22 Cont ID  
Sent By lmarchan Date 2021-11-22 Time 14:20 Rev Time 0.00
Received By lmarchan Date 2021-11-09 Time 06:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-18 Cont ID  
Sent By lmarchan Date 2021-10-18 Time 10:22 Rev Time 0.00
Received By lmarchan Date 2021-09-15 Time 13:49 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 09:52 Sent To  
Notes
2021-10-14 09:52:48NOT REQUIRED - NO ADDITION - NO CHANGE OF OCCUPANCY

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-01-13 Cont ID  
Sent By medwards Date 2021-12-17 Time 14:08 Rev Time 0.00
Received By medwards Date 2021-12-17 Time 14:08 Sent To  
Notes
2021-12-17 14:08:36APPROVED WITH PRIVISO:
 FIELD INSPECTOR TO VERIFY DRYER DUCT CONNECTION, SIZE
 AND TERMINATION LOCATION. ME

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-12 Cont ID  
Sent By medwards Date 2021-11-12 Time 08:36 Rev Time 0.00
Received By medwards Date 2021-11-12 Time 08:36 Sent To  
Notes
2021-11-12 08:36:212ND REVIEW FBC-2020 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OUTDOOR AIR CHART PROVIDED FOR THE COMMON AREAS
 IS FOR THE BUILDING ONLY. PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS FOR THE USE OF EACH SPACE INCLUDING THE
 OCCUPANTS. FBC M 403.3.1.1 AND TABLE 403.3.1.1; FBC EBC
 809
  
 2) PLEASE SHOW THE DRYER DUCT TYPE, SIZE AND A DRAWING
 SHOWING THE PATH TO THE TERMINATION LOCATION FOR EACH
 DRYER IN THE LAUNDRY ROOMS. FBC M 504
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-08 Cont ID  
Sent By medwards Date 2021-10-08 Time 11:19 Rev Time 0.00
Received By medwards Date 2021-10-08 Time 11:19 Sent To  
Notes
2021-10-08 11:19:271ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080869
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE ENTIRE COMCHECK DOCUMENTS FROM
 THE MECHANICAL SYSTEMS. FBC EC C403.2.1
  
 2) PLEASE SHOW HOW YOU WILL PROVIDE THE REQUIRED
 OUTDOOR VENTILATION. FBC M 402 & 403
  
 3) PLEASE SHOW THE OUTDOOR AIR CALCULATIONS FOR THE
 BUSINESS AND COMMON AREAS. FBC M 403.3.1.1 AND TABLE
 403.3.1.1
  
 4) PLEASE PROVIDE THE SPECIFICATIONS FOR THE KITCHEN
 HOODS WITH THE FIRE SUPPRESSING SYSTEM. FBC 107.2.1
  
  
 5) ARE THE DRYER DUCTS IN THE LAUNDRY GOING TO BE
 REPLACED?
  
 6) IF THE CLOTHES DRYERS ARE TO BE NEW PLEASE PROVIDE
 THE SPECIFICATIONS FOR THE COMMERCIAL DRYERS.
  
 7) SHEET M1.1: PLEASE SHOW THE OUTDOOR AIR DUCTWORK FOR
 THE AH-1. FBC M 403
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-01-13 Cont ID  
Sent By ccole Date 2022-01-13 Time 11:03 Rev Time 0.00
Received By ccole Date 2021-12-21 Time 15:18 Sent To  
Notes
2021-12-22 11:03:44FBC- 2020 ACCESSIBILITY PROVISOS- STANDARD ROLL-IN TYPE
 SHOWERS:
  
 1) SEC. 607.8: THRESHOLDS IN ROLL-IN TYPE SHOWER
 COMPARTMENTS SHALL BE 1/2-INCH HIGH MAXIMUM IN
 ACCORDANCE WITH 303.
  
 2) SEC. 608.2.2: STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS SHALL BE 30 INCHES WIDE MINIMUM BY 60
 INCHES DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT
 CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 60
 INCHES WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
  
 3) SEC. 608.2.2.1 CLEARANCE UNDER THE EXCEPTION- "A
 LAVATORY COMPLYING WITH 606 SHALL BE PERMITTED ON ONE
 30 INCH WIDE MINIMUM SIDE OF THE CLEARANCE PROVIDED
 THAT IT IS NOT ON THE SIDE OF THE CLEARANCE ADJACENT TO
 THE CONTROLS OR, WHERE PROVIDED, NOT ON THE SIDE OF THE
 CLEARANCE ADJACENT TO THE SHOWER SEAT.

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-11-19 Cont ID  
Sent By ccole Date 2021-11-19 Time 16:12 Rev Time 0.00
Received By ccole Date 2021-11-18 Time 09:38 Sent To  
Notes
2021-11-19 16:16:542ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21080869
 11/19/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. THE 1ST REVIEW COMMENTS
 LISTED BELOW ARE MARKED AS PASSED OR FAILED.
 EXPLANATORY NOTES IN CAP LETTERS HAVE BEEN ADDED TI
 FAILED COMMENTS. IN RESPONSE TO COMMENTS 1-14 LISTED
 BELOW THE ARCHITECT?S RESPONSE NARRATIVE IS STATING THE
 PLANS ARE TO BE REVIEWED IN ACCORDANCE WITH FBC-2020
 ACCESSIBILITY CODE.
  
 1) PASSED- SEE NOTES ABOVE. T1-0 CODE DATA: PROVIDE ON
 THE PLAN A LIST OF CURRENT FLORIDA CODES AND STANDARDS
 USED IN THE DESIGN OF THE PROJECT. PLEASE NOTE THAT
 ALTERATIONS TO PUBLIC SPACES AND BATHROOMS SHALL BE IN
 COMPLIANCE WITH THE FBC-2020 7TH EDITION ACCESSIBILITY
 CODE. ALTERATIONS TO DWELLING UNITS IN MULTI-FAMILY
 BUILDINGS CONSTRUCTED UNDER THE FAIR HOUSING ACT DESIGN
 MANUAL SHALL BE IN COMPLIANCE WITH THE DESIGN MANUAL.
 IN THIS CASE THE BUILDING WAS CONSTRUCTED IN 1972 WHICH
 PRECEDED THE MARCH 13, 1991 DATE WHEN THE FHDA
 CONSTRUCTION REQUIREMENTS FOR MULTIFAMILY BUILDINGS
 WENT INTO EFFECT. THE CURRENT PLANS PROVIDE NO
 INFORMATION OR GUIDANCE AS TO WHICH CODES SHOULD BE
 APPLIED. BASED ON THE DRAWINGS THE ALTERATIONS TO THE
 DWELLING UNITS WILL BE REVIEWED USING THE FAIR HOUSING
 DESIGN ACT MANUAL.
  
 3) PASSED- SEE NOTES ABOVE. T1-0: PLEASE REFER TO PAGE
 7 OF THE INTRODUCTION TO THE FAIR HOUSING DESIGN ACT
 MANUAL: THE DESIGN PROFESSIONAL OF RECORD SHALL
 INDICATE ON THE PLANS WHICH OF THE TWO BATHROOM TYPES
 IS THE BASIS OF DESIGN- SPECIFICATION TYPE A OR B ON
 THE PLANS. PLEASE REFER TO PAGES 7.34- 7.39 OF THE
 DESIGN MANUAL FOR EXPLANATORY INFORMATION ON
 SPECIFICATION A & B AND SHOW COMPLIANCE. A COMPLETE AND
 ACCURATE REVIEW OF THE PROJECT CANNOT BE COMPLETED
 WITHOUT THE TYPE A OR B DESIGNATION.
  
 4) PASSED- SEE NOTES ABOVE. A0.3, A0.4, A1.1, A1.2: AS
 NOTED IN COMMENT #3 ABOVE PLEASE DESIGNATE TYPE A OR B
 AS THE BASIS OF DESIGN ON THE FLOOR PLANS.
  
 5) FAILED A1.1 & A1.2: PROVIDE THE DIMENSIONS OF THE
 CLEAR FLOOR SPACE DIAGRAMS SHOWN ON THE PLANS IN FOR
 THE KITCHEN SINKS AND APPLIANCES, WATER CLOSETS,
 LAVATORIES AND VANITIES, BATHTUBS, AND SHOWERS- SEE
 PAGES 7.1- 7.59 OF THE MANUAL. REQUESTED CLEAR FLOOR
 SPACE DIMENSIONS NOT PROVIDED. ARCHITECT IS REFERENCING
 FBC-ACC. PLEASE SEE SECTIONS 604.3, 606.2, 607.2, &
 608.2 AND PROVIDE THE DIMENSIONS.
  
 6) FAILED. A1.1 & A1.2: BASED ON THE LOCATIONS OF THE
 LAVATORY SINKS BY THE BATHTUB, IT APPEARS THAT
 SPECIFICATION TYPE A HAS BEEN SELECTED FOR THE
 BATHROOMS. PLEASE REFER TO PAGE 7.53- SPECIFICATION A-
 DIAGRAM 1 AND CONFIRM THIS IS THE CHOSEN DESIGN.
 PROVIDE THE DIMENSIONS OF THE CLEAR FLOOR SPACE
 DIAGRAMS AT THE BATHTUB AND LAVATORIES. REQUESTED CLEAR
 FLOOR SPACE DIMENSIONS NOT PROVIDED. THE ARCHITECT IS
 REFERENCING THE FBC- ACC FOR COMPLIANCE. PLEASE SEE
 FIGURE 607.2 FBC ACC.
  
 7) PASSED. A7.1: REFER TO COMMENT #1 AND PROVIDE CODE
 COMPLIANCE DATA NOTES ON THE PLAN- SECTION 107.2.1 WPB.
 IT APPEARS SOME OF THE DETAILS ON THE SHEET ARE DERIVED
 FROM ICC/ANSI A117.1-2003, AND SOME FROM THE FAIR
 HOUSING DESIGN ACT MANUAL.
  
 8) FAILED. A7.2- CABINET SECTION: THE DETAIL DOES NOT
 PROVIDE THE MAXIMUM 19-INCH EXTENSION OF THE CLEAR
 FLOOR SPACE UNDER THE LAVATORY- PAGE 7.52 FAIR HOUSING
 DESIGN ACT MANUAL. REFER TO SECTION 606.2 AND FIGURES
 306.2 & 306.3 FBC ACC.
  
 9) FAILED. A7.1: PLEASE PROVIDE THE HEIGHTS OF THE
 TOILET SEATS FROM THE FINISHED FLOORS- PAGE 7.60 FHDA.
 REFER TO SECTION 604.4 FBC ACC.- THE SEAT HEIGHT SHALL
 BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM MEASURED TO
 THE TOP OF THE SEAT.
  
 10) PASSED. A7.1- ELEV. 7 & 16: SHOW THE 27-INCH
 MINIMUM KNEE SPACE AT THE SINK- PAGE- 7.52 FHDA.
  
 11) FAILED. A7.1 ELEV. 4, 5, 11, 12, 20: IT APPEARS THE
 ACCESSIBLE BATHTUB MAY BE DESIGNED IN ACCORDANCE WITH
 THE ICC/ANSI A117.1-2003. BASED ON THE ANSI STANDARD IT
 APPEARS THE GRAB BARS SHOWN IN THE DETAIL ARE NOT IN
 COMPLIANCE WITH SECTION AND FIGURE 607.4.1(A) FOR
 LENGTH AND SPACING FROM THE HEAD WALL. REFER TO FIG.
 607.4.1(B) AND PROVIDE THE CONTROL WALL GRAB BAR
 INSTALLATION DETAIL. REFER TO FIGURES 607.4.2 FBC ACC.
  
 12) FAILED. A7.1 REFER TO SECTIONS 607.3 AND 610.2
 ICC/ANSI A117.1-2003 AND PROVIDE BATHTUB SEAT
 DIMENSIONS AND MOUNTING HEIGHTS. REFER TO FIGURE 610.2
 FBC ACC.
  
 13) FAILED. A7.1 ELEV. 8, 9, 10, 19: REFER TO FIGURES
 608.3.2 & 608.5.2 AND PROVIDE THE ACCESSIBLE SHOWER
 GRAB BAR INSTALLATION LENGTHS, SPACES AND MOUNTING
 HEIGHTS. REFER TO FIGURE 608.3.2 FBC ACC.
  
 14) FAILED. A7.1 ELEV. 8, 11, 13, 19, 20: REFER TO FIG.
 604.5.1 & 604.5.2 AND SHOW THE CORRECT LENGTHS AND
 SPACINGS OF THE WATER CLOSET GRAB BARS. REFER TO
 FIGURES 604.5.1 & 604.5.2 FBC ACC.
  
 15) PASSED. P0.1: PROVIDE THE EFFICIENCY RATINGS OF THE
 TANKLESS WATER HEATERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- TABLE C404.2 FBC EC.
  
 16) FAILED. P0.1 & P0.2: PROVIDE HW PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC. PLEASE PROVIDE
 THE SPECIFICATIONS ON THE PLAN- SECTION 107.2.1 WPB.
  
 17) FAILED. P1.1: SHOW THE 6-INCH BUILDING DRAIN POINT
 OF CONNECT TO THE MAIN SEWER. IF SHOWN ON A CIVIL PLAN,
 PLEASE PROVIDE THE SHEET- SECTION 107.2.1 WPB. POINT OF
 CONNECTION ON SHEET C4.0 NOT SHOWN.
  
 18) PASSED. P1.1: PLEASE PROVIDE AN ENLARGED PIPING
 INSTALLATION DRAWING FOR THE LINT TRAP AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 1003.6 FBC P.
 THE LOCATION AND CAPACITY OF THE INTERCEPTOR SHALL BE
 IN ACCORDANCE WITH MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION GUIDELINES.
  
 19) PASSED. P2.3: THE KITCHEN SINK (SINK 1) DRAIN PIPES
 SHALL NOT CONNECT INTO THE WET VENT FOR THE BATHROOMS.
 THE DRAIN SHALL CONNECT DOWNSTREAM OF THE TUB FIXTURE
 DRAIN CONNECTION- SECTION 912.1 FBC P.
  
 20) PASSED. P1.1 & P2.1: SHOW THE CW RISER LOCATIONS-
 SECTION 107.2.1 WPB.
  
 21) FAILED. P2.3: SHOW REQUIRED SHUTOFF VALVES FOR THE
 CW DOWN FEED PIPES SHOWN IN THE RISERS- SECTION 606 FBC
 P. CW WAS A TYPO- SHUTOFF VALVES FOR HW DOWNFEED PIPES
 NOT SHOWN.
  
 22) PASSED. P1.2 & P2.4: SHOW HW AND HWR LINES RUNS
 FROM THE STORAGE ROOM TO THE LINES RUNNING ABOVE THE
 CORRIDOR CEILING- SECTION 607.1 FBC P.
  
 23) PASSED. P2.3: SHOW THE HW LINE CONNECTIONS TO THE
 SOURCES OF THE HOT WATER- SECTION 607.1 FBC P.
  
 24) PASSED. P0.2: WH-3 & WH-4 APPEAR TO BE MISSING THE
 HWR CONNECTIONS- SECTION 607.2 FBC P.
  
 25) PASSED. P0.1 P2.4: PROVIDE TRAP SEAL PROTECTION FOR
 THE FLOOR SINK IN THE WH STORAGE ROOM- SECTION 1002.4
 FBC P.
  
 26) PASSED. PROVIDE A SHOWER PAN DETAIL IN COMPLIANCE
 WITH- SECTION 421.5.2 FBC P. SHOW THE TYPE OF LINER TO
 BE INSTALLED AND SLOPE OF THE LINER.
  
 27) FAILED. RELOCATING THE SHOWER DRAIN OUTLETS WILL
 REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB. WHICH SHEET IS THE
 NOTE ON?
  
 28) FAILED. NEW DRAIN PIPE PENETRATIONS OF THE EXISTING
 SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR
 SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND
 APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN-
 SECTION 714.4.1.2 FBC B. DETAIL ON P0.1 IS FOR METAL
 PIPING. PROVIDE PENETRATION DETAIL FOR PVC DRAINS AND
 VENTS (IF PVC IS TO BE INSTALLED).
  
 29) PASSED. SHEET L-5: THE IRRIGATION PLANS ARE
 PROVIDING NOTES ONLY AND NO ALTERATION DRAWINGS AND
 DETAILS. PROVIDE COMPLETE PLANS AND DETAILS INCLUDING
 LOCATIONS OF NEW AND ALTERED PIPING AND CONTROLS, AND
 INCLUDE EQUIPMENT SCHEDULES- SECTION 107.2.1 WPB.
 PLEASE NOTE THAT IRRIGATION CAN BE DEFERRED AND
 SUBMITTED UNDER A SEPARATE PERMIT. RELOCATION OF THE
 EXISTING BACKFLOW PREVENTER OR NEW BF PREVENTER
 INSTALLATION SHALL BE DONE UNDER SEPARATE PERMIT. N
 ADDITIONAL SEPARATE PERMIT- SECTIONS 105.1 & 107.1 WPB,
 AND SECTION D. WPB MANUAL FOR CROSS-CONNECTION CONTROL.
  
 NEW COMMENTS:
  
 1) SHEETS P1.1 & P2.4: THE CONDENSATE SHALL NOT DRAIN
 INTO THE CITY SANITARY IN ACCORDANCE WITH SECTION
 90-126. PLEASE DISCHARGE THE CONDENSATE TO AN APPROVED
 LOCATION SUCH AS THE STORM DRAIN, DRYWELL OR
 DRAINFIELD.
  
 2) P0.1: BASED ON THE ENGINEER?S NOTE CITING WATER
 PRESSURE TEST NOT PROVIDED, PLEASE INDICATE WHAT WATER
 PRESSURE WAS USED TO DESIGN THE SYSTEM AND SIZE THE
 PIPING- SECTION 604.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-13 Cont ID  
Sent By ccole Date 2021-10-13 Time 11:48 Rev Time 0.00
Received By ccole Date 2021-10-08 Time 17:52 Sent To  
Notes
2021-10-13 11:50:411ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21080869
 10/13/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) T1-0 CODE DATA: PROVIDE ON THE PLAN A LIST OF
 CURRENT FLORIDA CODES AND STANDARDS USED IN THE DESIGN
 OF THE PROJECT. PLEASE NOTE THAT ALTERATIONS TO PUBLIC
 SPACES AND BATHROOMS SHALL BE IN COMPLIANCE WITH THE
 FBC-2020 7TH EDITION ACCESSIBILITY CODE. ALTERATIONS TO
 DWELLING UNITS IN MULTI-FAMILY BUILDINGS CONSTRUCTED
 UNDER THE FAIR HOUSING ACT DESIGN MANUAL SHALL BE IN
 COMPLIANCE WITH THE DESIGN MANUAL. IN THIS CASE THE
 BUILDING WAS CONSTRUCTED IN 1972 WHICH PRECEDED THE
 MARCH 13, 1991 DATE WHEN THE FHDA CONSTRUCTION
 REQUIREMENTS FOR MULTIFAMILY BUILDINGS WENT INTO
 EFFECT. THE CURRENT PLANS PROVIDE NO INFORMATION OR
 GUIDANCE AS TO WHICH CODES SHOULD BE APPLIED. BASED ON
 THE DRAWINGS THE ALTERATIONS TO THE DWELLING UNITS WILL
 BE REVIEWED USING THE FAIR HOUSING DESIGN ACT MANUAL.
  
 2) T1-0: PLEASE PROVIDE A NUMBERED MASTER LIST OF
 DWELLING UNITS PER FLOOR THAT ARE BEING RENOVATED FOR
 INCREASED ACCESSIBILITY. PLEASE NUMBER EACH OF THE
 APARTMENTS ON THE PLUMBING OR ARCHITECTURAL FLOOR PLAN
 DRAWINGS SO THEY CORRELATE WITH THE LIST AND CLARIFY
 HOW THE NUMBER OF APARTMENTS WERE DETERMINED- ACCORDING
 TO WHICH STANDARD OR WHICH SECTION OF THE FAIR HOUSING
 DESIGN ACT MANUAL.
  
 3) T1-0: PLEASE REFER TO PAGE 7 OF THE INTRODUCTION TO
 THE FAIR HOUSING DESIGN ACT MANUAL: THE DESIGN
 PROFESSIONAL OF RECORD SHALL INDICATE ON THE PLANS
 WHICH OF THE TWO BATHROOM TYPES IS THE BASIS OF DESIGN-
 SPECIFICATION TYPE A OR B ON THE PLANS. PLEASE REFER TO
 PAGES 7.34- 7.39 OF THE DESIGN MANUAL FOR EXPLANATORY
 INFORMATION ON SPECIFICATION A & B AND SHOW COMPLIANCE.
 A COMPLETE AND ACCURATE REVIEW OF THE PROJECT CANNOT BE
 COMPLETED WITHOUT THE TYPE A OR B DESIGNATION.
  
 4) A0.3, A0.4, A1.1, A1.2: AS NOTED IN COMMENT #3 ABOVE
 PLEASE DESIGNATE TYPE A OR B AS THE BASIS OF DESIGN ON
 THE FLOOR PLANS.
  
 5) A1.1 & A1.2: PROVIDE THE DIMENSIONS OF THE CLEAR
 FLOOR SPACE DIAGRAMS SHOWN ON THE PLANS IN FOR THE
 KITCHEN SINKS AND APPLIANCES, WATER CLOSETS, LAVATORIES
 AND VANITIES, BATHTUBS, AND SHOWERS- SEE PAGES 7.1-
 7.59 OF THE MANUAL.
 PAGES 7.1- 7.30: CLEAR FLOOR SPACES FOR SINKS AND
 APPLIANCES
 PAGES 7.1- 7.30: CLEARANCES BETWEEN KITCHEN COUNTERS
 AND ALL OPPOSING ELEMENTS.
 PAGES 7.12- 7.16: REMOVABLE SINK AND APPLIANCE CABINET
 DOORS INCLUDING KNEE SPACES.
 PAGES 7.40-7.46: WATER CLOSET CLEAR FLOOR SPACES AND
 GRAB BAR LOCATIONS
 PAGES 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR AND
 KNEE AND TOE CLEARANCES.
 PAGES 7.53- 7.55: BATHTUB CLEAR FLOOR SPACE AND CONTROL
 LOCATIONS
 PAGES 7.56- 7.59: SHOWER CLEAR FLOOR SPACES AND CONTROL
 LOCATIONS.
  
 6) A1.1 & A1.2: BASED ON THE LOCATIONS OF THE LAVATORY
 SINKS BY THE BATHTUB, IT APPEARS THAT SPECIFICATION
 TYPE A HAS BEEN SELECTED FOR THE BATHROOMS. PLEASE
 REFER TO PAGE 7.53- SPECIFICATION A- DIAGRAM 1 AND
 CONFIRM THIS IS THE CHOSEN DESIGN. PROVIDE THE
 DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS AT THE
 BATHTUB AND LAVATORIES.
  
 7) A7.1: REFER TO COMMENT #1 AND PROVIDE CODE
 COMPLIANCE DATA NOTES ON THE PLAN- SECTION 107.2.1 WPB.
 IT APPEARS SOME OF THE DETAILS ON THE SHEET ARE DERIVED
 FROM ICC/ANSI A117.1-2003, AND SOME FROM THE FAIR
 HOUSING DESIGN ACT MANUAL.
  
 8) A7.1: THE TYPICAL LAVATORY DETAIL DOES NOT PROVIDE
 THE MAXIMUM 19-INCH EXTENSION OF THE CLEAR FLOOR SPACE
 UNDER THE LAVATORY- PAGE 7.52 FAIR HOUSING DESIGN ACT
 MANUAL.
  
 9) A7.1: PLEASE PROVIDE THE HEIGHTS OF THE TOILET SEATS
 FROM THE FINISHED FLOORS- PAGE 7.60 FHDA.
  
 10) A7.1- ELEV. 7 & 16: SHOW THE 27-INCH MINIMUM KNEE
 SPACE AT THE SINK- PAGE- 7.52 FHDA.
  
 11) A7.1 ELEV. 4, 5, 11, 12, 20: IT APPEARS THE
 ACCESSIBLE BATHTUB MAY BE DESIGNED IN ACCORDANCE WITH
 THE ICC/ANSI A117.1-2003. BASED ON THE ANSI STANDARD IT
 APPEARS THE GRAB BARS SHOWN IN THE DETAIL ARE NOT IN
 COMPLIANCE WITH SECTION AND FIGURE 607.4.1(A) FOR
 LENGTH AND SPACING FROM THE HEAD WALL. REFER TO FIG.
 607.4.1(B) AND PROVIDE THE CONTROL WALL GRAB BAR
 INSTALLATION DETAIL.
  
 12) A7.1 REFER TO SECTIONS 607.3 AND 610.2 ICC/ANSI
 A117.1-2003 AND PROVIDE BATHTUB SEAT DIMENSIONS AND
 MOUNTING HEIGHTS.
  
 13) A7.1 ELEV. 8, 9, 10, 19: REFER TO FIGURES 608.3.2 &
 608.5.2 AND PROVIDE THE ACCESSIBLE SHOWER GRAB BAR
 INSTALLATION LENGTHS, SPACES AND MOUNTING HEIGHTS.
  
 14) A7.1 ELEV. 8, 11, 13, 19, 20: REFER TO FIG. 604.5.1
 & 604.5.2 AND SHOW THE CORRECT LENGTHS AND SPACINGS OF
 THE WATER CLOSET GRAB BARS.
  
 15) P0.1: PROVIDE THE EFFICIENCY RATINGS OF THE
 TANKLESS WATER HEATERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- TABLE C404.2 FBC EC.
  
 16) P0.1 & P0.2: PROVIDE HW PIPE INSULATION
 SPECIFICATIONS- TABLE C403.2.10 FBC EC.
  
 17) P1.1: SHOW THE 6-INCH BUILDING DRAIN POINT OF
 CONNECT TO THE MAIN SEWER. IF SHOWN ON A CIVIL PLAN,
 PLEASE PROVIDE THE SHEET- SECTION 107.2.1 WPB.
  
 18) P1.1: PLEASE PROVIDE AN ENLARGED PIPING
 INSTALLATION DRAWING FOR THE LINT TRAP AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 1003.6 FBC P.
 THE LOCATION AND CAPACITY OF THE INTERCEPTOR SHALL BE
 IN ACCORDANCE WITH MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION GUIDELINES.
  
 19) P2.3: THE KITCHEN SINK (SINK 1) DRAIN PIPES SHALL
 NOT CONNECT INTO THE WET VENT FOR THE BATHROOMS. THE
 DRAIN SHALL CONNECT DOWNSTREAM OF THE TUB FIXTURE DRAIN
 CONNECTION- SECTION 912.1 FBC P.
  
 20) P1.1 & P2.1: SHOW THE CW RISER LOCATIONS- SECTION
 107.2.1 WPB.
  
 21) P2.3: SHOW REQUIRED SHUTOFF VALVES FOR THE CW DOWN
 FEED PIPES SHOWN IN THE RISERS- SECTION 606 FBC P.
  
 22) P1.2 & P2.4: SHOW HW AND HWR LINES RUNS FROM THE
 STORAGE ROOM TO THE LINES RUNNING ABOVE THE CORRIDOR
 CEILING- SECTION 607.1 FBC P.
  
 23) P2.3: SHOW THE HW LINE CONNECTIONS TO THE SOURCES
 OF THE HOT WATER- SECTION 607.1 FBC P.
  
 24) P0.2: WH-3 & WH-4 APPEAR TO MISSING THE HWR
 CONNECTIONS- SECTION 607.2 FBC P.
  
 25) P0.1 P2.4: PROVIDE TRAP SEAL PROTECTION FOR THE
 FLOOR SINK IN THE WH STORAGE ROOM- SECTION 1002.4 FBC
 P.
  
 26) PROVIDE A SHOWER PAN DETAIL IN COMPLIANCE WITH-
 SECTION 421.5.2 FBC P. SHOW THE TYPE OF LINER TO BE
 INSTALLED AND SLOPE OF THE LINER.
  
 27) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE
 THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE
 REINFORCING STEEL OR POST STRESSED FLOOR TENDONS.
 PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE
 WILL BE MET- SECTION 107.2.1 WPB.
  
 28) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION
 714.4.1.2 FBC B.
  
 29) SHEET L-5: THE IRRIGATION PLANS ARE PROVIDING NOTES
 ONLY AND NO ALTERATION DRAWINGS AND DETAILS. PROVIDE
 COMPLETE PLANS AND DETAILS INCLUDING LOCATIONS OF NEW
 AND ALTERED PIPING AND CONTROLS, AND INCLUDE EQUIPMENT
 SCHEDULES- SECTION 107.2.1 WPB. PLEASE NOTE THAT
 IRRIGATION CAN BE DEFERRED AND SUBMITTED UNDER A
 SEPARATE PERMIT. RELOCATION OF THE EXISTING BACKFLOW
 PREVENTER OR NEW BF PREVENTER INSTALLATION SHALL BE
 DONE UNDER SEPARATE PERMIT. N ADDITIONAL SEPARATE
 PERMIT- SECTIONS 105.1 & 107.1 WPB, AND SECTION D. WPB
 MANUAL FOR CROSS-CONNECTION CONTROL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 2021-11-22 Cont ID  
Sent By   Date 2021-11-22 Time   Rev Time 0.00
Received By   Date 2021-11-22 Time   Sent To  
Notes
2021-11-22 14:06:45NO FURTHER COMMENTS.
  
 MATT HEJAZI
 DEPT OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-10-18 Time   Rev Time 0.00
Received By   Date 2021-10-18 Time   Sent To  
Notes
2021-10-18 08:59:26PLEASE PROVIDE:
 1- UPDATED DUMPSTER ENCLOSURE (SHEET C5.0) TO REFLECT
 THE REQUIREMENTS OF THE CITY`S SPEC, GC-7. FOR A
 FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7.
  
 2- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE?S
 WHEEL PATH) FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - DUAL AXLES
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 10:43 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 10:43 Sent To  
Notes
2021-12-15 10:44:01ROOFING TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 11:31 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 11:31 Sent To  
Notes
2021-11-17 11:31:44SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 09:48 Sent To  
Notes
2021-10-14 09:48:59SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-01-13 Cont ID  
Sent By dbattles Date 2022-01-13 Time 13:50 Rev Time 0.00
Received By dbattles Date 2022-01-13 Time 13:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 11:18 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 11:18 Sent To  
Notes
2021-12-15 11:19:39SIGNATURE REVIEW
  
 DRAWINGS - ALL "C"DRAWINGS, "S" DRAWINGS WITH AN UPLOAD
 DATE OF 9/14/21 TO PROJECTDOX, ALL "LS" PLANS, ALL "A"
 PLANS, ALL "M" PLANS, ALL "E" PLANS, ALL "P" PLANS IN
 PROJECTDOX DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE
 READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 11:43 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 11:43 Sent To  
Notes
2021-11-17 11:48:33SIGNATURE REVIEW
  
 DRAWINGS T1.0, ALL "C"DRAWINGS, "S" DRAWINGS WITH AN
 UPLOAD DATE OF 9/14/21 TO PROJECTDOX, ALL "LS" PLANS,
 ALL "A" PLANS, ALL "M" PLANS, ALL "E" PLANS, ALL "P"
 PLANS IN PROJECTDOX DO NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 09:49 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 09:49 Sent To  
Notes
2021-10-14 09:51:33SIGNATURE REVIEW
  
 ALL OF THE SIGNED AND SEALED DRAWINGS IN PROJECTDOX DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By rthermid Date 2021-09-29 Time   Rev Time  
Received By   Date 2021-09-29 Time   Sent To I
Notes
***NONE***