| Plan Review Stops For Permit 21080815 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-11-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-11-15 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-11-15 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2022-11-15 12:39:57 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-14 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-14 |
Time |
09:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2023-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-10 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-10 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2023-02-10 09:17:23 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB | | | 107.3.4 | | | | | | 2) PLEASE PROVIDE THE FRONT PAGE OF THE FLORIDA PRODUCT | | | APPROVAL FOR THE SLIDING WINDOWS FL17595 | | | | | | 3) PLEASE PROVIDE THE EXTERIOR WINDOR/DOOR FLASHING | | | DETAILS - FBC R703.1.1 WATER RESISTANCE. | | | THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND | | | CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION | | | OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A | | | WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS | | | REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO | | | THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR | | | CLADDING. | | | EXCEPTIONS: | | | 1.A WEATHER-RESISTANT EXTERIOR WALL ENVELOPE SHALL NOT | | | BE REQUIRED OVER CONCRETE OR MASONRY WALLS DESIGNED IN | | | ACCORDANCE WITH CHAPTER 6 AND FLASHED IN ACCORDANCE | | | WITH SECTION R703.4. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-13 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-13 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2022-12-13 13:46:17 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND | | | ROOFING SYSTEMS. ALL PRODUCT APPROVALS NEED TO BE | | | REVIEWED AND MARKED APPROVED BY THE DESIGNER OF RECORD | | | FBC WPB 107.3.4 | | | | | | 2) PLEASE PROVIDE THE EXTERIOR WINDOR/DOOR FLASHING | | | DETAILS - FBC R703.1.1 WATER RESISTANCE. | | | THE EXTERIOR WALL ENVELOPE SHALL BE DESIGNED AND | | | CONSTRUCTED IN A MANNER THAT PREVENTS THE ACCUMULATION | | | OF WATER WITHIN THE WALL ASSEMBLY BY PROVIDING A | | | WATER-RESISTANT BARRIER BEHIND THE EXTERIOR CLADDING AS | | | REQUIRED BY SECTION R703.2 AND A MEANS OF DRAINING TO | | | THE EXTERIOR WATER THAT PENETRATES THE EXTERIOR | | | CLADDING. | | | EXCEPTIONS: | | | 1.A WEATHER-RESISTANT EXTERIOR WALL ENVELOPE SHALL NOT | | | BE REQUIRED OVER CONCRETE OR MASONRY WALLS DESIGNED IN | | | ACCORDANCE WITH CHAPTER 6 AND FLASHED IN ACCORDANCE | | | WITH SECTION R703.4. | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-15 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-15 |
Time |
09:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-12-05 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-12-05 |
Time |
14:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-14 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-08 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2023-02-15 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-02-15 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-02-08 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-12-14 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-12-14 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-11-14 |
Time |
07:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2023-05-31 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2023-05-31 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2023-04-26 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2023-05-25 11:52:57 | MU-2023-019333-0000 $1,945.04 PAID - AO | | 2023-04-26 11:08:01 | 4/26/23 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-13 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-13 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2022-12-13 13:47:35 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2023-02-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-14 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-14 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-11-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-21 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-21 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2022-11-21 16:21:03 | 1ST REVIEW FMC | | | PERMIT: 21080815 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) FORM R405-2020 ITEM NUMBER 5 ASKS IF THIS IS A WORST | | | CASE. THIS DOES NOT MEET THE EXCEPTION FOR WORST CASE. | | | PLEASE CORRECT THIS ITEM. FEC R405.4.2.1 ??? EXCEPTION | | | | | | 2) THE HVAC CALCULATIONS HAVE THE REFERENCE CITY AS | | | MIAMI, PLEASE CHANGE TO WEST PALM BEACH. IT ALSO DOES | | | NOT HAVE THE PROJECT ADDRESS LISTED. PLEASE SHOW THIS | | | CALCULATION IS FOR THE PROJECT ADDRESS. FBC 107.3.5 | | | | | | 3) SHEET M-1: PLEASE PROVIDE THE CFM???S OF THE RANGE | | | HOOD FAN. FRC M1503.4 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2023-02-09 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2023-02-09 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2023-02-09 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-11-15 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-15 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-11-15 |
Time |
09:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2023-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-10 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-10 |
Time |
09:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-12-13 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-12-13 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-12-13 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2022-12-13 13:48:05 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2023-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-03-14 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-03-14 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2023-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2023-02-10 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2023-02-10 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-11-17 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-11-17 |
Time |
14:38 |
Rev Time |
|
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2023-03-09 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-03-09 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-03-09 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2023-02-13 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2023-02-13 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2023-02-13 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2023-02-13 12:29:31 | 2/13/2023 FAILED | | | | | | PLEASE APPLY FOR A LANDSCAPE PERMIT | | | | | | PLEASE APPLY FOR A DRVIEWAY PERMIT | | | | | | PLEASE APPLY FOR A FENCE PERMIT | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-12-01 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-12-01 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2022-12-01 13:05:07 | 12/1/2022 FAILED | | | | | | PLEASE APPLY FOR A LANDSCAPE PERMIT | | | A SEPERATE PERMIT IS REQUIRED FOR THE FOLLOWING: | | | DRIVEWAYS, POOLS/POOL EQUIPMENT, MECHANICAL EQUIPMENT, | | | WALLS/FENCE/GATES, IRRIGATION, ETC. | | | | | | PER THE ZLR THE PROPOSED PROJECT DOES NOT MEET THE SIDE | | | SETBACKS, BOTH SIDES PROPOSE 5 FEET. | | | BOTH SIDES MUST EQUAL A TOTAL OF 15 FEET WHEN ADDED | | | TOGETHER AND A 5 FEET MINIMUM IS REQUIRED. | | | | | | | | | 3.MINIMUM SETBACKS FOR PRINCIPAL BUILDING. | | | A.FRONT: 25 FEET; | | | B.CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60 | | | FEET WIDE; | | | C.REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS | | | LESS; | | | D.SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL. | | | | | | | | | VALENTINA BROGLIA | | | [email protected] |
|
|