Plan Review Details - Permit 21080772
Plan Review Stops For Permit 21080772
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-04 Cont ID  
Sent By rmcdouga Date 2021-10-04 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2021-10-04 Time 16:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-17 Cont ID  
Sent By rmcdouga Date 2021-09-17 Time 07:43 Rev Time 0.00
Received By rmcdouga Date 2021-09-17 Time 07:43 Sent To  
Notes
2021-09-17 07:58:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE SIGNED AND SEALED ENGINEER'S FOUNDATION
 EVALUATION AND REPAIR REPORT WITH CALCULATIONS. FBC
 AMEND. 107.1
  
 2) SUBMIT THE ENGINEER'S SIGNED AND SEALED REPAIR
 DETAILS AND PLANS WITH THE SPECIFIC LOCATIONS OF THE
 REPAIR PILES. FBC AMEND. 107.2.1
  
 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 REPAIR PILES THAT WILL BE USED. FBC AMEND. 107.2.1
  
 4) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION ON
 THE SUBMITTED PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED WHEN MORE INFORMATION IS PROVIDED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-04 Cont ID  
Sent By rmcdouga Date 2021-10-04 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2021-09-23 Time 08:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-17 Cont ID  
Sent By rmcdouga Date 2021-09-17 Time 07:43 Rev Time 0.00
Received By rmcdouga Date 2021-08-19 Time 08:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-09-24 Cont ID  
Sent By rmcdouga Date 2021-09-24 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2021-09-24 Time 16:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-17 Cont ID  
Sent By rmcdouga Date 2021-09-17 Time 07:43 Rev Time 0.00
Received By rmcdouga Date 2021-09-17 Time 07:43 Sent To  
Notes
2021-09-17 07:45:21SUBMIT SIGNED AND SEALED FOUNDATION REPAIR DOCUMENTS
 FROM A FLORIDA LICENSED ENGINEER. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop Z ZONING
Rev No 1 Status N Date 2021-08-31 Cont ID  
Sent By awooten Date 2021-08-31 Time   Rev Time  
Received By awooten Date 2021-08-31 Time   Sent To  
Notes
***NONE***