| 2021-10-22 08:32:31 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 10/22/21 - A RESPONSE LETTER WAS SUBMITTED, IT APPEARS |
| | TO IMPLY THAT CORETEC FLOORING WITH SELETAC |
| | UNDERLAYMENT IS PROPOSED. IT IS NOT CLEAR WHY A |
| | SEPARATE UNDERLAYMENT IS PROPOSED WHEN THE CORETEC |
| | APPEARS TO COMPLY WITH STC/IIC REQUIREMENTS (STC 52, |
| | IIC 51). EXCEEDING MINIMUM CODE COMPLIANCE IS ALWAYS |
| | ACCEPTABLE BUT THEN THE UNDERLAYMENT NEEDS TO COMPLY |
| | WITH FLAME SPREAD. |
| | |
| | IF YOU ADD AN UNDERLAYMENT THE UNDERLAYMENT IS REQUIRED |
| | TO COMPLY WITH THE REQUIREMENT FOR FLAME SPREAD TEST |
| | FBC B 603.1. IF SELETAC UNDERLAYMENT IS PROPOSED, |
| | SUBMIT FLAME SPREAD (REQUIREMENT C BELOW). REQUIREMENTS |
| | A AND B (STC/IIC) ARE SATISFIED BY THE STC/IIC TEST |
| | REPORT FOR CORETEC FLOORING. |
| | |
| | |
| | ************************* |
| | 1. FOR THE FLOORING PROPOSED, PROVIDE THE STC AND IIC |
| | TEST REPORTS. |
| | |
| | CLARIFY PROPOSED INSTALLATION. CORETEC SPECS WERE |
| | SUBMITTED; THIS FLOORING HAS SOUNDPROOFING INTEGRAL TO |
| | THE FLOORING. SELETAC UNDERLAYMENT SPECS WAS ALSO |
| | SUBMITTED. |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. IF UNDERLAYMENT IS PROPOSED, FBC 603.1, ALLOWABLE |
| | MATERIALS IN NON COMBUSTIBLE BUILDINGS, SEE ITEM 2, |
| | EXCEPTION 2, ACOUSTICAL INSULATION INSTALLED BETWEEN A |
| | FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN |
| | ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF PROPOSED |
| | WORK, FBC 107. |
| | |
| | |