Plan Review Details - Permit 21080762
Plan Review Stops For Permit 21080762
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-11-08 Cont ID  
Sent By cthroop Date 2021-11-08 Time 14:43 Rev Time 0.00
Received By cthroop Date 2021-11-08 Time 14:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-22 Cont ID  
Sent By shill Date 2021-10-22 Time 08:13 Rev Time 0.00
Received By shill Date 2021-10-22 Time 08:13 Sent To  
Notes
2021-10-22 08:32:31****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 10/22/21 - A RESPONSE LETTER WAS SUBMITTED, IT APPEARS
 TO IMPLY THAT CORETEC FLOORING WITH SELETAC
 UNDERLAYMENT IS PROPOSED. IT IS NOT CLEAR WHY A
 SEPARATE UNDERLAYMENT IS PROPOSED WHEN THE CORETEC
 APPEARS TO COMPLY WITH STC/IIC REQUIREMENTS (STC 52,
 IIC 51). EXCEEDING MINIMUM CODE COMPLIANCE IS ALWAYS
 ACCEPTABLE BUT THEN THE UNDERLAYMENT NEEDS TO COMPLY
 WITH FLAME SPREAD.
  
 IF YOU ADD AN UNDERLAYMENT THE UNDERLAYMENT IS REQUIRED
 TO COMPLY WITH THE REQUIREMENT FOR FLAME SPREAD TEST
 FBC B 603.1. IF SELETAC UNDERLAYMENT IS PROPOSED,
 SUBMIT FLAME SPREAD (REQUIREMENT C BELOW). REQUIREMENTS
 A AND B (STC/IIC) ARE SATISFIED BY THE STC/IIC TEST
 REPORT FOR CORETEC FLOORING.
  
  
 *************************
 1. FOR THE FLOORING PROPOSED, PROVIDE THE STC AND IIC
 TEST REPORTS.
  
 CLARIFY PROPOSED INSTALLATION. CORETEC SPECS WERE
 SUBMITTED; THIS FLOORING HAS SOUNDPROOFING INTEGRAL TO
 THE FLOORING. SELETAC UNDERLAYMENT SPECS WAS ALSO
 SUBMITTED.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. IF UNDERLAYMENT IS PROPOSED, FBC 603.1, ALLOWABLE
 MATERIALS IN NON COMBUSTIBLE BUILDINGS, SEE ITEM 2,
 EXCEPTION 2, ACOUSTICAL INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF PROPOSED
 WORK, FBC 107.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 16:28 Rev Time 0.00
Received By shill Date 2021-10-10 Time 16:28 Sent To  
Notes
2021-10-10 16:35:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FOR THE FLOORING PROPOSED, PROVIDE THE STC AND IIC
 TEST REPORTS.
  
 CLARIFY PROPOSED INSTALLATION. CORETEC SPECS WERE
 SUBMITTED; THIS FLOORING HAS SOUNDPROOFING INTEGRAL TO
 THE FLOORING. SELETAC UNDERLAYMENT SPECS WAS ALSO
 SUBMITTED.
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. IF UNDERLAYMENT IS PROPOSED, FBC 603.1, ALLOWABLE
 MATERIALS IN NON COMBUSTIBLE BUILDINGS, SEE ITEM 2,
 EXCEPTION 2, ACOUSTICAL INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2. PROVIDE A FLOOR PLAN SHOWING LOCATION OF PROPOSED
 WORK, FBC 107.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By pleduc Date 2021-10-20 Time   Rev Time 0.00
Received By pleduc Date 2021-10-20 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-10-05 Cont ID  
Sent By pleduc Date 2021-10-05 Time   Rev Time 0.00
Received By pleduc Date 2021-10-05 Time 15:14 Sent To  
Notes
2021-10-05 15:22:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE
 LOCATION OF THE PROPOSED LOCATIONS OF THE FLOORING.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN
 INDICATING THE ROOMS WITH THE PROPOSED FLOORING.
  
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-08 Cont ID  
Sent By cthroop Date 2021-11-08 Time 14:43 Rev Time 0.00
Received By cthroop Date 2021-11-01 Time 07:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-22 Cont ID  
Sent By shill Date 2021-10-22 Time 09:32 Rev Time 0.00
Received By shill Date 2021-10-19 Time 08:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 16:36 Rev Time 0.00
Received By shill Date 2021-09-29 Time 08:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-10-22 Cont ID  
Sent By shill Date 2021-10-22 Time 08:34 Rev Time 0.00
Received By shill Date 2021-10-22 Time 08:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 16:36 Rev Time 0.00
Received By shill Date 2021-10-10 Time 16:36 Sent To  
Notes
***NONE***