Plan Review Details - Permit 21080731
Plan Review Stops For Permit 21080731
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-08-31 Cont ID  
Sent By cpuell Date 2021-08-31 Time 14:43 Rev Time 0.00
Received By cpuell Date 2021-08-31 Time 14:43 Sent To  
Notes
2021-12-02 16:10:52553.791, F.S. PRIVATE PROVIDER PLAN REVIEW COMPLIANCE
 AFFIDAVIT.
 PLEASE LIST ALL DOCUMENTS REVIEWED ON THE PLAN REVIEW
 COMPLIANCE AFFIDAVIT.
 ONLY DRAWING SHEETS ARE LISTED, BUT PRODUCT APPROVALS,
 ENERGY CALS AND OTHER DOCUMENTS IN THE SUPPORTING
 DOCUMENTS FOLDER SHOULD BE REVIEWED BY PRIVATE PROVIDER
 SO THE CITY CAN DO AUDIT ONLY.
  
 ALSO, THIS PROPERTY IS IN A FLOOD ZONE.
 THE CITY WILL DO THE NFIP REVIEW, BUT WE WILL NEED AN
 ELEVATION CERTIFICATE.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
2021-08-31 14:46:00ORIGINAL ADDRESS LEFT THE LOCATION OF THE MAIN ENTRANCE
 DIDN'T CHANGE. A CABANA IS ON THE PROPERTY BUT ATTACHED
 TO THE MAIN HOUSE AND UNDER THE SAME ROOM AND
 ACCESSIBLE FROM THE MAIN HOUSE. NO ADDITIONAL ADDRESS
 REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-07-15 Cont ID  
Sent By cthroop Date 2022-07-15 Time 06:22 Rev Time 0.00
Received By cthroop Date 2022-07-14 Time 16:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-07-06 Cont ID  
Sent By cthroop Date 2022-07-06 Time 11:23 Rev Time 0.00
Received By cthroop Date 2022-07-06 Time 06:57 Sent To  
Notes
2022-07-06 11:24:45FINAL BUILDING REVIEW APPROVAL PENDING APPROVAL OF
 CONSTRUCTION DRAWING ELEVATION CERTIFICATE. SEE
 COMMENTS UNDER 4TH NFIP REVIEW DATED 7/6/2022. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-06-29 Cont ID  
Sent By cthroop Date 2022-06-29 Time 13:24 Rev Time 0.00
Received By cthroop Date 2022-06-29 Time 12:53 Sent To  
Notes
2022-06-29 13:26:35FINAL BUILDING REVIEW APPROVAL PENDING APPROVAL OF
 CONSTRUCTION DRAWING ELEVATION CERTIFICATE. SEE
 COMMENTS UNDER 3RD NFIP REVIEW DATED 6/27/22. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-04-06 Cont ID  
Sent By cthroop Date 2022-04-06 Time 11:03 Rev Time 0.00
Received By cthroop Date 2022-03-31 Time 14:13 Sent To  
Notes
2022-04-06 11:46:58BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 NOTICE: THIS PROJECT IS LOCATED IN A SPECIAL FLOOD
 HAZARD AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS
 SITE IS AE WITH A BASE FLOOD ELEVATION (BFE) OF 6'0"
 NAVD. THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE
 NO. 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF
 FREEBOARD. THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT
 OR ABOVE 8'0" NAVD.
  
 1. CORRECTED (FINISHED FLOOR ELEVATIONS PLACED ON FLOOR
 PLAN, PAGE A100, ELEVATION PLANS A200 AND A201. FIRST
 FLOOR SLAB IS 8.0' NAVD AND GARAGE FLOOR IS 6.6' NAVD).
  
 2.THE GARAGE FLOOR IS BELOW THE DFE OF 8'0" NAVD.
 (ADDITIONAL INFORMATION REQUIRED)
 FLOOD OPENINGS ARE REQUIRED.
  
 ENGINEERED FLOOD VENTS
  
 2A) ATTACH A COPY OF THE EVALUATION SERVICE REPORT
 ISSUED BY THE INTERNATIONAL CODE COUNCIL EVALUATION
 SERVICE (ICC ES). (DESIGNER SHALL IDENTIFY SMART VENT
 MODEL TO BE INSTALLED)
 2B) PROVIDE FLORIDA PRODUCT APPROVALS FOR PROPOSED
 SMART VENTS. (DESIGNER SHALL IDENTIFY SMART VENT MODEL
 TO BE INSTALLED)
  
 2C) FLOOD OPENINGS SHALL BE INSTALLED PER
 R322.2.2.1INSTALLATION OF OPENINGS: (FOUNDATION PLAN S1
 SHOWS FLOOD VENTS INSTALLED ON SAME WALL) SEE BELOW FOR
 LOCATION.
 2D) SHOW NUMBER AND LOCATION OF FLOOD OPENINGS ON FLOOR
 PLAN. INCLUDE THE FLORIDA PRODUCT APPROVAL NUMBER AND
 IDENTIFY THE VENT MODEL TO BE INSTALLED. (INCLUDED THE
 SQUARE INCH/SQUARE FOOT DATA)
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS.
 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN
 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN
 DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION.
  
  
 3.CORRECTED. CONSTRUCTION DRAWING ELEVATION CERTIFICATE
 SUBMITTED FOR REVIEW.
  
  
 4. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3 (NOT
 SUBMITTED FOR REVIEW)
  
  
 5. PROVIDE A SOILS REPORT. (NOT SUBMITTED FOR REVIEW)
  
  
 6. REF. WINDOW SCHEDULE: CORRECTED
  
  
 7. PROVIDE PRODUCT APPROVALS FOR EXT. DOORS: (NOT
 SUBMITTED FOR REVIEW)
  
  
 8. DESIGNER SPECIFIES CEILING INSULATION SHALL BE
 ICYNENE SPRAY FOAM INSULATION WITH A VALUE OF R-30.
 (PLAN PAGE A302). ENERGY SUBMITTAL USES A CEILING
 R-VALUE OF R-20. PLEASE CLARIFY?
 (NOT ADDRESSED)
  
 9. DESIGNER SPECIFIES CMU WALL INSULATION SHALL HAVE A
 R-VALUE OF R-11. (PLAN PAGE A303). ENERGY SUBMITTAL
 USES A CMU WALL R-VALUE OF R-20. PLEASE CLARIFY?
 (NOT ADDRESSED)
  
 10. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY
 FOAM INSULATION. (NOT SUBMITTED FOR REVIEW)
  
 NEW COMMENTS:
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC)
 COMMENTS PER FB107.
  
 1. SECTION AA) GARAGE SQUARE FOOTAGE STATES 575SF. PLAN
 PAGE A100. STATES GARAGE IS 667SF.
 2. SECTION A9B) NUMBER OF FLOOD OPENINGS STATES N/A.
 PLAN PAGE AOOO SHOWS 2 FLOOD OPENINGS.
 3. A9C) TOTAL NET AREA STATES N/A. THIS DATA WILL BE
 FROM THE TYPE OF FLOOD VENTS INSTALLED. ENGINEERED OR
 NON-ENGINEERED.
 4. SECTION A9D) ENGINEERED FLOOD OPENINGS STATES NO. IF
 NON-ENGINEERED FLOOD OPENINGS ARE INSTALLED, PROVIDE A
 DETAIL BY A QUALIFIED DESIGN PROFESSIONAL, SIGNED AND
 SEALED.
 5. SECTION C2D) TOP OF GARAGE FLOOR STATES 7.7FT. PLAN
 PAGE A100 STATES 6.6FT.
 6. C2E) LOWEST ELEVATION OF MACHINERY STATES N/A.
 MACHINERY SERVICING THE BUILDING SHALL BE AT OR ABOVE
 THE DFE OF 8.0FT NAVD.
 7. C2F) LOWEST ADJACENT GRADE. REQUIRED DATA NOT
 AVAILABLE. SITE DRAINAGE PLAN HAS NOT BEEN SUBMITTED
 FOR REVIEW.
 8. C2G) HIGHEST ADJACENT GRADE. REQUIRED DATA NOT
 AVAILABLE. SITE DRAINAGE PLAN HAS NOT BEEN SUBMITTED
 FOR REVIEW.
 9. SECTION D COMMENTS: TYPE OF EQUIPMENT AND LOCATION
 REQUIRED. (SEE DIRECTIONS IN COMMENTS NARRATIVE BLOCK)
 10. ELEVATION CERTIFICATE IS MISSING PAGES 5 AND 6.
 (PHOTOS). FEMA REQUIRES A COMPLETE EC. NOTE: NO PHOTOS
 ARE REQUIRED FOR THE CONSTRUCTION DRAWING EC.
  
  
 PROVISO: PLAN PAGE S1. SUBMIT AN UNDER CONSTRUCTION EC
 AT PLACEMENT OF FIRST FLOOR.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By cthroop Date 2021-12-27 Time 17:09 Rev Time 0.00
Received By cthroop Date 2021-12-27 Time 10:32 Sent To  
Notes
2021-12-27 17:10:15BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE
 IS AE WITH A BASE FLOOD ELEVATION (BFE) OF 6'0" NAVD.
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 8'0" NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
  
 2.PLACE THE FINISHED FLOOR ELEVATION (FFE) OF THE MAIN
 DWELLING UNIT AND THE ATTACHED GARAGE ON THE SITE PLAN,
 THE FLOOR PLAN AND THE FOUNDATION PLAN.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3.THE GARAGE FLOOR IS BELOW THE DFE OF 8'0" NAVD.
 FLOOD OPENINGS ARE REQUIRED.
 R322.2.2ENCLOSED AREA BELOW DESIGN FLOOD ELEVATION.
 ENCLOSED AREAS, INCLUDING CRAWL SPACES, THAT ARE BELOW
 THE DESIGN FLOOD ELEVATION SHALL:
 1.BE USED SOLELY FOR PARKING OF VEHICLES, BUILDING
 ACCESS OR STORAGE.
 2.BE PROVIDED WITH FLOOD OPENINGS THAT MEET THE
 FOLLOWING CRITERIA AND ARE INSTALLED IN ACCORDANCE WITH
 SECTION R322.2.2.1:
 3.THE TOTAL NET AREA OF NON-ENGINEERED OPENINGS SHALL
 BE NOT LESS THAN 1 SQUARE INCH (645 MM2) FOR EACH
 SQUARE FOOT (0.093 M2) OF ENCLOSED AREA WHERE THE
 ENCLOSED AREA IS MEASURED ON THE EXTERIOR OF THE
 ENCLOSURE WALLS, OR THE OPENINGS SHALL BE DESIGNED AS
 ENGINEERED OPENINGS AND THE CONSTRUCTION DOCUMENTS
 SHALL INCLUDE A STATEMENT BY A REGISTERED DESIGN
 PROFESSIONAL THAT THE DESIGN OF THE OPENINGS WILL
 PROVIDE FOR EQUALIZATION OF HYDROSTATIC FLOOD FORCES ON
 EXTERIOR WALLS BY ALLOWING FOR THE AUTOMATIC ENTRY AND
 EXIT OF FLOODWATERS AS SPECIFIED IN SECTION 2.7.2.2 OF
 ASCE 24.
 4.OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM) IN
 ANY DIRECTION IN THE PLANE OF THE WALL.
 5.THE PRESENCE OF LOUVERS, BLADES, SCREENS AND
 FACEPLATES OR OTHER COVERS AND DEVICES SHALL ALLOW THE
 AUTOMATIC FLOW OF FLOODWATER INTO AND OUT OF THE
 ENCLOSED AREAS AND SHALL BE ACCOUNTED FOR IN THE
 DETERMINATION OF THE NET OPEN AREA.
  
 OPTION:
 ENGINEERED FLOOD VENTS
 1) PROVIDE ENGINEERED FLOOD VENTS. (SMART VENTS)
 2) ATTACH A COPY OF THE INDIVIDUAL ENGINEERED FLOOD
 VENT CERTIFICATION OR EVALUATION SERVICE REPORT ISSUED
 BY THE INTERNATIONAL CODE COUNCIL EVALUATION SERVICE
 (ICC ES).
 3) PROVIDE FLORIDA PRODUCT APPROVALS FOR PROPOSED SMART
 VENTS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE
 9N-3 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD.
 4) FLOOD OPENINGS SHALL BE INSTALLED PER
 R322.2.2.1INSTALLATION OF OPENINGS:
 5) SHOW NUMBER AND LOCATION OF FLOOD OPENINGS ON
 FOUNDATION PLAN. INCLUDE THE FLORIDA PRODUCT APPROVAL
 NUMBER AND IDENTIFY THE VENT MODEL TO BE INSTALLED.
 R322.2.2.1INSTALLATION OF OPENINGS.
 THE WALLS OF ENCLOSED AREAS SHALL HAVE OPENINGS
 INSTALLED SUCH THAT:
 1. 1.THERE SHALL BE NOT LESS THAN TWO OPENINGS ON
 DIFFERENT SIDES OF EACH ENCLOSED AREA; IF A BUILDING
 HAS MORE THAN ONE ENCLOSED AREA BELOW THE DESIGN FLOOD
 ELEVATION, EACH AREA SHALL HAVE OPENINGS.
 2. 2.THE BOTTOM OF EACH OPENING SHALL BE NOT MORE THAN
 1 FOOT (305 MM) ABOVE THE HIGHER OF THE FINAL INTERIOR
 GRADE OR FLOOR AND THE FINISHED EXTERIOR GRADE
 IMMEDIATELY UNDER EACH OPENING.
 3. 3.OPENINGS SHALL BE PERMITTED TO BE INSTALLED IN
 DOORS AND WINDOWS; DOORS AND WINDOWS WITHOUT INSTALLED
 OPENINGS DO NOT MEET THE REQUIREMENTS OF THIS SECTION.
  
 FEMA TECHNICAL BULLETIN #1
 LOCATION OF FLOOD OPENINGS
 THE IRC AND IBC (BY REFERENCE TO ASCE 24) REQUIRE FLOOD
 OPENINGS ON DIFFERENT SIDES OF EACH ENCLOSED AREA (IRC
 R322.2.2.1) AND ?IN AT LEAST TWO WALLS OF EACH ENCLOSED
 AREA? (ASCE 24, SECTION 2.7.3).
  
 4.SUBMIT THE FOLLOWING THREE (3) ELEVATION CERTIFICATES
 AS REQUIRED:
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
 5. PROVIDE A SITE DRAINAGE PLAN PER FBC R401.3
 IT SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED BOUNDARY LINE SURVEY.
 FBC R401.3 SITE DRAINAGE
  
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD.
 LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM
 FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6
 INCHES WITHIN THE FIRST 10 FEET.
  
 6. PROVIDE A SOILS REPORT.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 7. REF. WINDOW SCHEDULE ON PLAN PAGE A550 FOR THE
 FOLLOWING COMMENT:
 PROVIDE WINDOW TYPE TO LEGEND.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 8. PROVIDE PRODUCT APPROVALS FOR EXT. DOORS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 9. DESIGNER SPECIFIES CEILING INSULATION SHALL BE
 ICYNENE SPRAY FOAM INSULATION WITH A VALUE OF R-30.
 (PLAN PAGE A302). ENERGY SUBMITTAL USES A CEILING
 R-VALUE OF R-20. PLEASE CLARIFY?
 R402.1.2INSULATION AND FENESTRATION CRITERIA.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE R402.1.2, BASED ON THE CLIMATE
 ZONE SPECIFIED IN CHAPTER 3.
  
 10. DESIGNER SPECIFIES CMU WALL INSULATION SHALL HAVE A
 R-VALUE OF R-11. (PLAN PAGE A303). ENERGY SUBMITTAL
 USES A CMU WALL R-VALUE OF R-20. PLEASE CLARIFY?
 R402.1.2INSULATION AND FENESTRATION CRITERIA.
 THE BUILDING THERMAL ENVELOPE SHALL MEET THE
 REQUIREMENTS OF TABLE R402.1.2, BASED ON THE CLIMATE
 ZONE SPECIFIED IN CHAPTER 3.
  
 11. PROVIDE THE ICC-ES REPORT FOR THE ICYNENE SPRAY
 FOAM INSULATION.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-06-29 Cont ID  
Sent By cthroop Date 2022-06-29 Time 13:22 Rev Time 0.00
Received By cthroop Date 2022-06-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-06 Cont ID  
Sent By cthroop Date 2022-04-06 Time 16:55 Rev Time 0.00
Received By cthroop Date 2022-03-31 Time 14:14 Sent To  
Notes
2022-04-06 14:57:16 
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By cthroop Date 2021-12-29 Time 09:23 Rev Time 0.00
Received By cthroop Date 2021-12-27 Time 10:33 Sent To  
Notes
2021-12-29 09:24:52ELECTRICAL PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.AN ELECTRICAL SU-PERMIT IS REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2.THE LOAD CALCULATIONS ON PAGE E100 SHOW A TOTAL LOAD
 OF 165 AMPS. THE TOTAL LOAD OF PANELBOARDS A & B ON
 PAGE E102 IS 245 AMPS. PLEASE CLARIFY?
 PROVIDE ACCURATE LOAD CALCULATIONS INCLUDING ALL LOADS
 FOR THE SERVICE AS WELL AS THE LOAD CALCULATIONS FOR
 THE INDIVIDUAL PANELS. NEC 220; FBC RE 3602.2.
  
 3.LUMINAIRES
 R404.1LIGHTING EQUIPMENT (MANDATORY).
 NOT LESS THAN 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR NOT LESS THAN 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY
 HIGH-EFFICACY LAMPS.
 EXCEPTION: LOW-VOLTAGE LIGHTING.
 A NOTE ON THE PLAN WILL SUFFICE. FBC EC R404.1
  
 4. PROVIDE OUTLET AT FRONT OF UNIT.
 E3901.7 OUTDOOR OUTLETS.
 NOT LESS THAN ONE RECEPTACLE OUTLET THAT IS READILY
 ACCESSIBLE FROM GRADE LEVEL AND LOCATED NOT MORE THAN 6
 FEET, 6 INCHES (1981 MM) ABOVE GRADE, SHALL BE
 INSTALLED OUTDOORS AT THE FRONT AND BACK OF EACH
 DWELLING UNIT HAVING DIRECT ACCESS TO GRADE LEVEL.
  
 5. PROVIDE SMOKE ALARM AND C/O DETECTOR AT 1ST FLOOR
 STAIRS.
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 R315.1 CARBON MONOXIDE PROTECTION.
  
 6. KITCHEN OUTLETS SHALL BE GFCI PROTECTED.
 E3902.6 KITCHEN RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE RECEPTACLES
 THAT SERVE COUNTERTOP SURFACES SHALL HAVE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL.
 [210.8(A)(6)]
  
 7. DISHWASHER OUTLET SHALL BE GFCI PROTECTED.
 E3902.10 KITCHEN DISHWASHER BRANCH CIRCUIT.
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION SHALL BE
 PROVIDED FOR OUTLETS THAT SUPPLY DISHWASHERS IN
 DWELLING UNIT LOCATIONS. [210.8(D)]
  
 8. PROVIDE OUTLETS FOR OHD OPENERS IN GARAGE.
 E3902.2 GARAGE AND ACCESSORY BUILDING RECEPTACLES.
 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE RECEPTACLES
 INSTALLED IN GARAGES AND GRADE-LEVEL PORTIONS OF
 UNFINISHED ACCESSORY BUILDINGS USED FOR STORAGE OR WORK
 AREAS SHALL HAVE GROUND-FAULT CIRCUIT-INTERRUPTER
 PROTECTION FOR PERSONNEL. [210.8(A)(2)]
  
 9. R322.1.6PROTECTION OF MECHANICAL, PLUMBING AND
 ELECTRICAL SYSTEMS.
 ELECTRICAL SYSTEMS, EQUIPMENT AND COMPONENTS; HEATING,
 VENTILATING, AIR CONDITIONING; PLUMBING APPLIANCES AND
 PLUMBING FIXTURES; DUCT SYSTEMS; AND OTHER SERVICE
 EQUIPMENT SHALL BE LOCATED AT OR ABOVE THE ELEVATION
 REQUIRED IN SECTION R322.2 OR R322.3. IF REPLACED AS
 PART OF A SUBSTANTIAL IMPROVEMENT, ELECTRICAL SYSTEMS,
 EQUIPMENT AND COMPONENTS; HEATING, VENTILATING, AIR
 CONDITIONING AND PLUMBING APPLIANCES AND PLUMBING
 FIXTURES; DUCT SYSTEMS; AND OTHER SERVICE EQUIPMENT
 SHALL MEET THE REQUIREMENTS OF THIS SECTION. SYSTEMS,
 FIXTURES, AND EQUIPMENT AND COMPONENTS SHALL NOT BE
 MOUNTED ON OR PENETRATE THROUGH WALLS INTENDED TO BREAK
 AWAY UNDER FLOOD LOADS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-04-07 Cont ID  
Sent By cthroop Date 2022-04-07 Time 11:49 Rev Time 0.00
Received By cthroop Date 2022-03-31 Time 14:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By cthroop Date 2021-12-29 Time 14:13 Rev Time 0.00
Received By cthroop Date 2021-12-27 Time 10:33 Sent To  
Notes
2021-12-29 14:14:00PLAN REVIEW FUEL GAS
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2014 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: A GAS SUB-PERMIT IS REQUIRED.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
 2. SUBMIT APPLICABLE GAS TABLES.
  
 3. SUBMIT MANUFACTURERS SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
  
 4. SUBMIT GAS REGULATOR SPECIFICATIONS. 2020 FBC FUEL
 GAS SEC.305.1 OR 2020 FBC FUEL GAS RES. SEC. G2408.1.
  
 5. REGULATORS SHALL HAVE A UNION INSTALLED WITHIN 1
 FOOT OF EITHER SIDE OF THE REGULATOR FBC FG 410.2
  
 6. SUBMIT A COPY OF A HOUSE PLAN SHOWING THE LOCATION
 OF ALL PROPOSED GAS APPLIANCES. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1. INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 7. SUBMIT COMBUSTION AIR CALCULATIONS FOR THE PROPOSED
 GAS APPLIANCES. WHERE IS COMBUSTION AIR PROVIDED BY THE
 BUILDINGS MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2020 FGC
 SEC.304.9.3 OR 2020 FBC R G2407.9.3. COMBINED
 COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2022-07-15 Cont ID  
Sent By aoliver Date 2022-07-15 Time 10:24 Rev Time 0.00
Received By aoliver Date 2022-07-13 Time 09:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2022-06-29 Cont ID  
Sent By lmarchan Date 2022-06-29 Time 17:01 Rev Time 0.00
Received By lmarchan Date 2022-06-28 Time 13:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2022-06-27 Cont ID  
Sent By lmarchan Date 2022-06-27 Time 17:08 Rev Time 0.00
Received By lmarchan Date 2022-06-23 Time 09:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2022-06-24 Cont ID  
Sent By shill Date 2022-06-23 Time 09:18 Rev Time 0.00
Received By shill Date 2022-06-21 Time 17:31 Sent To  
Notes
2022-06-22 15:58:55NEW SITE PLAN, CIVILS
 B, E, P, R, M, NFIP

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2022-04-07 Cont ID  
Sent By cthroop Date 2022-04-07 Time 11:50 Rev Time 0.00
Received By cthroop Date 2022-03-28 Time 06:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-03-24 Cont ID  
Sent By medwards Date 2022-03-24 Time 07:01 Rev Time 0.00
Received By medwards Date 2022-03-18 Time 07:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-02-28 Cont ID  
Sent By medwards Date 2022-02-28 Time 15:06 Rev Time 0.00
Received By medwards Date 2022-02-24 Time 08:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-28 Cont ID  
Sent By shill Date 2022-02-24 Time 08:31 Rev Time 0.00
Received By shill Date 2022-02-03 Time 11:04 Sent To  
Notes
2022-02-07 12:22:16ZONING PASSED ON 12/1/21. ON 2/3, MULTIPLE NEW SHEETS
 WERE UPLOADED INCLUDING MECHANICAL, ELEVATIONS. ROUTED
 BACK TO ZONING SH
 SOME EXAMPLES - CVR, A000, A100,A101
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-29 Cont ID  
Sent By cthroop Date 2021-12-29 Time 14:25 Rev Time 0.00
Received By cthroop Date 2021-12-06 Time 13:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-02 Cont ID  
Sent By dbattles Date 2021-12-02 Time 13:59 Rev Time 0.00
Received By dbattles Date 2021-11-09 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-03 Cont ID  
Sent By shill Date 2021-09-03 Time 15:27 Rev Time 0.00
Received By shill Date 2021-08-26 Time 10:35 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2022-07-29 Time   Rev Time 0.00
Received By lmarchan Date 2022-04-08 Time 10:02 Sent To  
Notes
2022-07-29 13:23:14RECEIPT MU-2022-016012 - $2404.37 PAID
2022-04-08 10:02:304/8/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-08-16 Cont ID  
Sent By shill Date 2021-08-16 Time 13:01 Rev Time 0.00
Received By shill Date 2021-08-16 Time 13:01 Sent To  
Notes
2021-08-16 13:01:49PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-06-29 Cont ID  
Sent By cthroop Date 2022-06-29 Time 13:19 Rev Time 0.00
Received By cthroop Date 2022-06-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-04-06 Cont ID  
Sent By cthroop Date 2022-04-06 Time 14:10 Rev Time 0.00
Received By cthroop Date 2022-03-31 Time 14:14 Sent To  
Notes
2022-04-06 14:37:07PLAN REVIEW MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. NOTICE ONLY: A MECHANICAL SUB-PERMIT IS REQUIRED.
  
  
 2. CORRECTED
  
  
 3. CORRECTED
  
  
 4. PROVIDE THE KITCHEN EXHAUST HOOD SPECIFICATIONS.
 (NOT SUBMITTED FOR REVIEW)
  
  
 5. NOTICE ONLY: MECH. EQUIPMENT IN FLOOD ZONES. (SEE
 ELEVATION CERTIFICATE SECTION C2E)
  
  
 6. CORRECTED
  
  
 7. THE BUILDING DESIGNER SPECIFIES CEILING INSULATION
 VALUE TO BE R-30 AND THE EXT. CMU WALL INSULATION VALUE
 TO BE R-11. THE ENERGY SUBMITTAL USES A CEILING R-VALUE
 OF R-20 AND A CMU WALL R-VALUE OF R-4.1. PLEASE
 CLARIFY?
 (NOT CORRECTED)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By cthroop Date 2021-12-29 Time 08:10 Rev Time 0.00
Received By cthroop Date 2021-12-27 Time 10:33 Sent To  
Notes
2021-12-29 08:49:55PLAN REVIEW MECHANICAL
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. A MECHANICAL SUB-PERMIT IS REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. FS 471.003 (H): THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ALONG WITH THE MECHANICAL SYSTEM DESIGN
 MUST BE DESIGNED BY A FLORIDA LICENSED ENGINEER OR THE
 MECHANICAL CONTRACTOR THAT HOLDS THE PERMIT FOR THE
 SPECIFIC PROJECT WHICH HE OR SHE INSTALLS.
 PLEASE, HAVE EITHER A LICENSED ENGINEER, PROVIDE A
 SIGNED AND SEALED MECHANICAL EQUIPMENT SIZING
 CALCULATION AND A SIGNED AND SEALED MECHANICAL DRAWING,
 OR
 THE MECHANICAL CONTRACTOR INSTALLING THE SYSTEM SHALL
 PROVIDE THE EQUIPMENT SIZING CALCULATIONS AND A CODE
 COMPLIANT DESIGN. CONTRACTOR SHALL INCLUDE HIS OR HER
 PRINTED NAME AND SIGNATURE PER 2017 WPB AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, SECTION 107.2.1.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 3. M1411.8 LOCKING ACCESS PORT CAPS.
 REFRIGERANT CIRCUIT ACCESS PORTS LOCATED OUTDOORS SHALL
 BE FITTED WITH LOCKING-TYPE TAMPER-RESISTANT CAPS OR
 SHALL BE OTHERWISE SECURED TO PREVENT UNAUTHORIZED
 ACCESS.
  
 4. PROVIDE THE KITCHEN EXHAUST HOOD SPECIFICATIONS.
 M1503.3 KITCHEN EXHAUST RATES.
 WHERE DOMESTIC KITCHEN COOKING APPLIANCES ARE EQUIPPED
 WITH DUCTED RANGE HOODS OR DOWN-DRAFT EXHAUST SYSTEMS,
 THE FANS SHALL BE SIZED IN ACCORDANCE WITH SECTION
 M1507.4.
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE
 MECHANICALLY OR NATURALLY PROVIDED WITH MAKEUP AIR AT A
 RATE APPROXIMATELY EQUAL TO THE EXHAUST AIR RATE.
  
 5. MECH. EQUIPMENT IN FLOOD ZONES
 CONDENSER SHALL BE INSTALLED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE).
 FBC R M1401.5 AND FBC R 322.1.6
 M1401.5 FLOOD HAZARD.
 IN FLOOD HAZARD AREAS AS ESTABLISHED BY TABLE
 R301.2(1), HEATING AND COOLING EQUIPMENT AND APPLIANCES
 SHALL BE LOCATED OR INSTALLED IN ACCORDANCE WITH
 SECTION R322.1.6.
  
 6. THE BUILDERS SIGNATURE IS REQUIRED ON THE ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD.
 FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 7. THE BUILDING DESIGNER SPECIFIES CEILING INSULATION
 VALUE TO BE R-30 AND THE EXT. CMU WALL INSULATION VALUE
 TO BE R-11. THE ENERGY SUBMITTAL USES A CEILING R-VALUE
 OF R-20 AND A CMU WALL R-VALUE OF R-4.1. PLEASE
 CLARIFY?
 ENERGY CALC?S - ALL PHYSICAL BUILDING DATA LISTED ON
 THE FLORIDA ENERGY EFFICIENCY FORM R405-2020 NEEDS TO
 BE CONFIRMED ON NEW BUILDING PLANS- SECTION 107.2.1
 WPB.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 5 Status P Date 2022-07-15 Cont ID  
Sent By cthroop Date 2022-07-15 Time 06:22 Rev Time 0.00
Received By cthroop Date 2022-07-14 Time 16:39 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status F Date 2022-07-06 Cont ID  
Sent By cthroop Date 2022-07-06 Time 11:24 Rev Time 0.00
Received By cthroop Date 2022-07-06 Time 06:57 Sent To  
Notes
2022-07-06 11:34:49NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 4TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC)
 COMMENTS PER FB107.
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 8. C2G) HIGHEST ADJACENT GRADE (HAG). REQUIRED. (DATA
 ENTERED APPEARS TO BE INCORRECT. PLEASE REFERENCE SITE
 DRAINAGE PLAN PAGE C-1 FOR DATA)
 (HAG APPEARS TO BE 6.00').
  
  
 11. C2B) DATA MISSING.
 (THIS IS A 2 STORY STRUCTURE. 1ST FLOOR FF EL. IS 8'0"
 NAVD. 2ND FLOOR EL. IS +12'0". C2(B) SHOULD BE 20'0"
 NAVD).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2022-06-27 Cont ID  
Sent By cthroop Date 2022-06-27 Time 15:53 Rev Time 0.00
Received By cthroop Date 2022-06-25 Time 11:42 Sent To  
Notes
2022-06-27 16:05:06NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC)
 COMMENTS PER FB107.
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 1. SECTION AA) GARAGE SQUARE FOOTAGE STATES 575SF. PLAN
 PAGE A100. STATES GARAGE IS 667SF.
 (PLAN REVIEW COMMENTS BY CARLOS CORDEO-LUZA STATES THE
 GARAGE IS 647. ENTER CORRECT DATA ON LINE A9A) OF EC)
  
 2. SECTION A9B) NUMBER OF FLOOD OPENINGS STATES N/A.
 PLAN PAGE AOOO SHOWS 2 FLOOD OPENINGS. (NOT CORRECTED)
  
 3. A9C) TOTAL NET AREA STATES N/A. THIS DATA WILL BE
 FROM THE TYPE OF FLOOD VENTS INSTALLED. ENGINEERED OR
 NON-ENGINEERED. (NOT CORRECTED)
  
 4. SECTION A9D) ENGINEERED FLOOD OPENINGS STATES NO. IF
 NON-ENGINEERED FLOOD OPENINGS ARE INSTALLED, PROVIDE A
 DETAIL BY A QUALIFIED DESIGN PROFESSIONAL, SIGNED AND
 SEALED. (INCORRECT DATA STILL ENETERD)
  
 5. SECTION C2D) TOP OF GARAGE FLOOR STATES 7.7FT. PLAN
 PAGE A100 STATES 6.6FT. (INCORRECT DATA STILL ENETERD)
  
 6. C2E) LOWEST ELEVATION OF MACHINERY STATES N/A.
 MACHINERY SERVICING THE BUILDING SHALL BE AT OR ABOVE
 THE DFE OF 8.0FT NAVD. (ENTER CORRECT DATA)
  
 7. C2F) LOWEST ADJACENT GRADE. REQUIRED. (DATA ENTERED
 APPEARS TO BE INCORRECT. PLEASE REFERENCE SITE DRAINAGE
 PLAN PAGE C-1 FOR DATA)
  
 8. C2G) HIGHEST ADJACENT GRADE. REQUIRED. (DATA ENTERED
 APPEARS TO BE INCORRECT. PLEASE REFERENCE SITE DRAINAGE
 PLAN PAGE C-1 FOR DATA)
  
 9. SECTION D COMMENTS: TYPE OF EQUIPMENT AND LOCATION
 REQUIRED. (SEE DIRECTIONS IN COMMENTS NARRATIVE BLOCK)
 (NOT ADDRESSED)
  
 10.
  
 PROVISO: PLAN PAGE S1 - UNDER CONSTRUCTION EC REQUIRED
 AT PLACEMENT OF 1ST FLOOR.
  
 C/O HOLD: FINISHED CONSTRUCTION EC REQUIRED PRIOR TO
 C/O.
  
 NEW COMMENT:
  
 11. C2B) DATA MISSING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-04-06 Cont ID  
Sent By cthroop Date 2022-04-06 Time 13:38 Rev Time 0.00
Received By cthroop Date 2022-03-31 Time 14:15 Sent To  
Notes
2022-04-06 13:56:09NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE (EC)
 COMMENTS PER FB107.
  
 1. SECTION AA) GARAGE SQUARE FOOTAGE STATES 575SF. PLAN
 PAGE A100. STATES GARAGE IS 667SF.
 2. SECTION A9B) NUMBER OF FLOOD OPENINGS STATES N/A.
 PLAN PAGE AOOO SHOWS 2 FLOOD OPENINGS.
 3. A9C) TOTAL NET AREA STATES N/A. THIS DATA WILL BE
 FROM THE TYPE OF FLOOD VENTS INSTALLED. ENGINEERED OR
 NON-ENGINEERED.
 4. SECTION A9D) ENGINEERED FLOOD OPENINGS STATES NO. IF
 NON-ENGINEERED FLOOD OPENINGS ARE INSTALLED, PROVIDE A
 DETAIL BY A QUALIFIED DESIGN PROFESSIONAL, SIGNED AND
 SEALED.
 5. SECTION C2D) TOP OF GARAGE FLOOR STATES 7.7FT. PLAN
 PAGE A100 STATES 6.6FT.
 6. C2E) LOWEST ELEVATION OF MACHINERY STATES N/A.
 MACHINERY SERVICING THE BUILDING SHALL BE AT OR ABOVE
 THE DFE OF 8.0FT NAVD.
 7. C2F) LOWEST ADJACENT GRADE. REQUIRED DATA NOT
 AVAILABLE. SITE DRAINAGE PLAN HAS NOT BEEN SUBMITTED
 FOR REVIEW.
 8. C2G) HIGHEST ADJACENT GRADE. REQUIRED DATA NOT
 AVAILABLE. SITE DRAINAGE PLAN HAS NOT BEEN SUBMITTED
 FOR REVIEW.
 9. SECTION D COMMENTS: TYPE OF EQUIPMENT AND LOCATION
 REQUIRED. (SEE DIRECTIONS IN COMMENTS NARRATIVE BLOCK)
 10. ELEVATION CERTIFICATE IS MISSING PAGES 5 AND 6.
 (PHOTOS). FEMA REQUIRES A COMPLETE EC. NOTE: NO PHOTOS
 ARE REQUIRED FOR THE CONSTRUCTION DRAWING EC.
  
 PROVISO: PLAN PAGE S1 - UNDER CONSTRUCTION EC REQUIRED
 AT PLACEMENT OF 1ST FLOOR.
  
 C/O HOLD: FINISHED CONSTRUCTION EC REQUIRED PRIOR TO
 C/O.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-12-28 Cont ID  
Sent By cthroop Date 2021-12-28 Time 09:19 Rev Time 0.00
Received By cthroop Date 2021-12-27 Time 10:32 Sent To  
Notes
2021-12-28 09:25:16NFIP PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16 AND NO. 4729-17
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE FLOOD ZONE DESIGNATION FOR THIS SITE
 IS AE WITH A BASE FLOOD ELEVATION (BFE) OF 6?0? NAVD.
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE NO.
 4729-17) REQUIRES AN ADDITIONAL 24 INCHES OF FREEBOARD.
 THE DESIGN FLOOD ELEVATION (DFE) SHALL BE AT OR ABOVE
 8?0? NAVD.
  
 CITY OF WEST PALM BEACH, FLORIDA ORDINANCE NO. 4729-17
 SECTION 4: THE CODE OF ORDINANCES IS HEREBY AMENDED AT
 CHAPTER 18, BUILDINGS AND BUILDING REGULATIONS, ARTICLE
 II, BUILDING CODE, TO ADD SECTION 18-33, TECHNICAL
 AMENDMENTS TO FLORIDA BUILDING CODE, RESIDENTIAL, WHICH
 SHALL READ AS FOLLOWS:
 SEC. 18-33 - TECHNICAL AMENDMENTS TO FLORIDA BUILDING
 CODE, RESIDENTIAL.
 R322.2.1 ELEVATION REQUIREMENTS.
 1. BUILDINGS AND STRUCTURES IN FLOOD HAZARD AREAS NOT
 DESIGNATED AS COASTAL A ZONES SHALL HAVE THE LOWEST
 FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD ELEVATION
 PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, WHICHEVER
 IS HIGHER.
  
 2.SUBMIT THE FOLLOWING THREE (3) ELEVATION CERTIFICATES
 AS REQUIRED.
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-06-29 Cont ID  
Sent By cthroop Date 2022-06-29 Time 13:11 Rev Time 0.00
Received By cthroop Date 2022-06-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-07 Cont ID  
Sent By cthroop Date 2022-04-07 Time 11:50 Rev Time 0.00
Received By cthroop Date 2022-03-31 Time 14:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By cthroop Date 2021-12-29 Time 13:28 Rev Time 0.00
Received By cthroop Date 2021-12-27 Time 10:33 Sent To  
Notes
2021-12-29 14:13:09PLAN REVIEW PLUMBING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: A PLUMBING SUB-PERMIT IS REQUIRED.
  
 1. CORRECT BUILDING CODE REFERENCE ON PLAN PAGE P102
 FROM FBC 2017 TO FBC 2020.
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2. PROVIDE SHOWER PAN DETAIL.
 P2709.1 SHOWER PAN CONSTRUCTION. FBC 107.2.1
 P2709.3 SHOWER PAN LINING INSTALLATION.
  
 3. MASTER BATH GROUP IS ON A CLOSED VENT SYSTEM.
 P3101.2.1VENTING REQUIRED.
 EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
 P3108.2.2VERTICAL WET VENT.
 THE DRY-VENT CONNECTION FOR A VERTICAL WET-VENT SYSTEM
 SHALL BE AN INDIVIDUAL VENT OR COMMON VENT FOR THE MOST
 UPSTREAM FIXTURE DRAIN.
 P3102.2INSTALLATION.
 THE REQUIRED VENT SHALL BE A DRY VENT THAT CONNECTS TO
 THE BUILDING DRAIN OR AN EXTENSION OF A DRAIN THAT
 CONNECTS TO THE BUILDING DRAIN. SUCH VENT SHALL NOT BE
 AN ISLAND FIXTURE VENT AS PERMITTED BY SECTION P3112.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 9 Status P Date 2022-07-20 Cont ID  
Sent By dbattles Date 2022-07-20 Time 16:22 Rev Time 0.00
Received By dbattles Date 2022-07-20 Time 16:22 Sent To  
Notes
2022-07-21 16:49:54REVISED AFFIDAVIT RECEIVED, ADDED AND APPROVED.
2022-07-21 08:35:15PLAN COMPLIANCE AFFIDAVIT
 WHERE IT SAYSFINAL ELEVATION CERTIFICATE COULD YOU
 PLEASE HAVE THAT SAY CONSTRUCTION DRAWINGS ELEVATION
 CERTIFICATE.
2022-07-20 16:22:57ADDED AFFIDAVIT WITH EC

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 8 Status P Date 2022-07-15 Cont ID  
Sent By cthroop Date 2022-07-15 Time 09:43 Rev Time 0.00
Received By cthroop Date 2022-07-14 Time 16:39 Sent To  
Notes
2022-07-15 09:45:50PRIVATE PROVIDER SHALL SUBMIT A CORRECTED AFFIDAVIT
 UPON APPROVAL OF THE CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE, PER BUILDING OFFICIAL (RB). CT

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 7 Status P Date 2022-06-29 Cont ID  
Sent By cthroop Date 2022-06-29 Time 12:53 Rev Time 0.00
Received By cthroop Date 2022-06-29 Time 11:26 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 6 Status F Date 2022-06-27 Cont ID  
Sent By cthroop Date 2022-06-25 Time 11:41 Rev Time 0.00
Received By cthroop Date 2022-06-24 Time 16:43 Sent To  
Notes
2022-06-27 15:16:15PROVITE PROVIDER AFFIDAVIT REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 6TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: AFFIDAVIT SUBMITTED ON 6/21/22 HAS ONLY THOSE
 DOC'S THAT ADDRESS THE BLDG., MECH., AND NFIP REVIEW
 COMMENTS.
  
 CORRECTION:
  
 1. AFFIDAVITS MAY BE MULTIPLE DOC'S PER STATUTE. SEE
 7TH REVIEW.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date   Cont ID  
Sent By   Date 2022-03-29 Time   Rev Time 0.00
Received By   Date 2022-03-29 Time   Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2022-03-24 Cont ID  
Sent By medwards Date 2022-03-24 Time 06:05 Rev Time 0.00
Received By medwards Date 2022-03-24 Time 06:05 Sent To  
Notes
2022-03-24 07:00:47PRIVATE PROVIDER AFFIDAVIT AUDIT-
 THE AFFIDAVIT HAS THE FOLLOWING MISTAKES- M-2 IS DATED
 07/09/2021 AND HAS NOT HAD A REVISION 1 AS SHOWN ON THE
 AFFIDAVIT; THERE IS NO SHEET A1000 2ND REVISION DATED
 1/12/2022, THERE IS A SHEET A100 WITH THIS DATE.
 PLEASE SUBMIT THE CORRECTED AFFIDAVIT PER F.S. 553.791

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2022-02-28 Cont ID  
Sent By medwards Date 2022-02-28 Time 14:53 Rev Time 0.00
Received By medwards Date 2022-02-28 Time 14:53 Sent To  
Notes
2022-02-28 15:06:12THE PRIVATE PROVIDER AFFIDAVIT SHOULD INCLUDE
 EVERYTHING THAT IS SUBMITTED. THE PRIVATE PROVIDER
 AFFIDAVIT IS A SWORN TESTIMONY THAT THEY HAVE REVIEWED
 THE ENTIRE PROJECT. EACH TIME THERE IS A CHANGE IN THE
 SUBMITTALS AND A NEW AFFIDAVIT IS REQUIRED IT WILL TAKE
 THE PLACE OF THE PREVIOUS VERSION OF THE AFFIDAVIT AND
 SHOULD LIST EVERYTHING THAT HAS BEEN REVIEWED FOR THE
 PROJECT INCLUDING PIECES OF THE SUBMITTALS THAT HAVE
 NOT CHANGED AND THE REVISED DOCUMENTS. THE DATES OF
 EACH DOCUMENT AND THE REVISION NUMBERS SHOULD ALWAYS BE
 INCLUDED. THE FINAL AFFIDAVIT SHOULD BE A STAND ALONE
 DOCUMENT THAT SHOWS THE HISTORY OF THE SUBMITTAL.
 PLEASE INCLUDE THE FOLLOWING DOCUMENTS WITH DATES AND
 REVISIONS TO YOUR AFFIDAVIT:
  
 ENERGY CALCULATIONS
  
 MECHANICAL EQUIPMENT SIZING CALCULATIONS
  
 ELEVATION CERTIFICATE
  
 ARCHITECTURAL SHEETS: A102, A300, A301, A304, A305,
 A500, A501, A550, A551,
  
 STRUCTURAL SHEETS; S1, S2, S3, S4, S5, S6, S7, S8
  
 PLUMBING SHEETS: P101, P103, P104, P105, P106
  
 ELECTRICAL: E102
  
 SURVEY SHEET
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status P Date 2021-12-06 Cont ID  
Sent By dbattles Date 2021-12-06 Time 12:46 Rev Time 0.00
Received By dbattles Date 2021-12-06 Time 12:46 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-12-02 Cont ID  
Sent By dbattles Date 2021-12-02 Time 13:59 Rev Time 0.00
Received By dbattles Date 2021-12-02 Time 13:48 Sent To  
Notes
2021-12-03 16:48:23553.791, F.S. PRIVATE PROVIDER PLAN REVIEW COMPLIANCE
 AFFIDAVIT.
 PLEASE PROVIDE UPDATED PLAN REVIEW COMPLIANCE AFFIDAVIT
 TO INCLUDE ALL DOCUMENTS REVIEWED INCLUDING PRODUCT
 APPROVALS, ENERGY CALCS AND ANY REVIEWED DOCUMENTS.
 THE CITY OF WPB WILL BE PERFORMING AUDIT ONLY SO WE
 NEED TO SEE THAT PRIVATE PROVIDER DID THE REVIEWS.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-06-29 Cont ID  
Sent By cthroop Date 2022-06-29 Time 12:53 Rev Time 0.00
Received By cthroop Date 2022-06-29 Time 12:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-04-06 Cont ID  
Sent By cthroop Date 2022-04-06 Time 11:48 Rev Time 0.00
Received By cthroop Date 2022-03-31 Time 14:15 Sent To  
Notes
2022-04-06 11:49:36ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1ST REVIEW COMMENTS HAVE NOT BEEN ADDRESSED. SEE BELOW.
  
 1. ROOFING SUB-PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE INSTALLATION INSTRUCTIONS FOR FL14317-R12,
 ROOFING UNDERLAYMENTS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. ONLY THE COVER SHEETS WERE SUBMITTED FOR FL7849-R14,
 ROOFING TILES.
 DESIGNER SHALL SELECT THE MODEL, NAME OR NUMBER OF TILE
 TO BE INSTALLEED. PROVIDE INSTALLATION INSTRUCTIONS FOR
 TILE SELECTED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By cthroop Date 2021-12-27 Time 15:29 Rev Time 0.00
Received By cthroop Date 2021-12-27 Time 10:32 Sent To  
Notes
2021-12-27 15:37:01ROOFING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING SUB-PERMIT REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 2. PROVIDE INSTALLATION INSTRUCTIONS FOR FL14317-R12,
 ROOFING UNDERLAYMENTS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. ONLY THE COVER SHEETS WERE SUBMITTED FOR FL7849-R14,
 ROOFING TILES.
 DESIGNER SHALL SELECT THE MODEL, NAME OR NUMBER OF TILE
 TO BE INSTALLEED. PROVIDE INSTALLATION INSTRUCTIONS FOR
 TILE SELECTED.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 7 Status N Date 2022-07-15 Cont ID  
Sent By cthroop Date 2022-07-15 Time 09:42 Rev Time 0.00
Received By cthroop Date 2022-07-14 Time 16:39 Sent To  
Notes
2022-07-15 09:43:13DIGITAL SIGNATURE AND SEAL BY SURVEYOR IS NOT REQUUIRED
 ON A CONSTRUCTION DRAWING EC. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status F Date 2022-07-06 Cont ID  
Sent By cthroop Date 2022-07-06 Time 11:20 Rev Time 0.00
Received By cthroop Date 2022-07-06 Time 10:00 Sent To  
Notes
2022-07-06 11:22:51SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ELEVATION CERTIFICATE SHALL HAVE A VALID DIGITAL
 SIGNATURE OF THE SURVEYOR.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-06-27 Cont ID  
Sent By pvalenti Date 2022-06-27 Time 09:17 Rev Time 0.00
Received By pvalenti Date 2022-06-25 Time 11:42 Sent To  
Notes
2022-06-27 09:23:39PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 SIGNATURE REVIEW:
  
 (3) SETS OF PAPER PLAN SHEETS: A-000, A-100, A-201,
 A-300, A-302, A-303, A-304, A-305, P-100, P-103, E-100,
 & S-1 HAVE BEEN SUBMITTED WITH ORIGINAL HAND SIGNATURES
 BY REGISTERED ARCHITECT ANGELO DAVILA. THESE PAPER PLAN
 SHEETS HAVE BEEN ROUTED TO RECORDS RETENTION SPECIALIST
 (C.D.) FOR STORAGE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-02-07 Cont ID  
Sent By medwards Date 2022-02-07 Time 13:47 Rev Time 0.00
Received By medwards Date 2022-02-07 Time 13:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-22 Cont ID  
Sent By mpeterso Date 2021-11-22 Time 16:45 Rev Time 0.00
Received By mpeterso Date 2021-11-22 Time 16:45 Sent To  
Notes
2021-11-22 16:46:19REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED,
 ROUTED TO STORAGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-12 Cont ID  
Sent By lcrespo Date 2021-11-12 Time 16:18 Rev Time 0.00
Received By lcrespo Date 2021-11-12 Time 16:18 Sent To  
Notes
2021-11-12 16:20:26PLANS WHERE SUBMITED WITH A WET SEAL FRO VERSION TWO
 AND ONLY A000, A200, A201 AND A202 HAS BEEN APPROVED
 ALL OTHER PAGES NEED A SIGNATURE OR SEAL IN ACCORDANCE
 WITH FLORIDA ADMINISTRATIVE CODE PER 61G15-23.001,
 FLORIDA STATUTE 471.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-12 Cont ID  
Sent By lcrespo Date 2021-11-12 Time 16:06 Rev Time 0.00
Received By lcrespo Date 2021-11-12 Time 16:06 Sent To  
Notes
2021-11-12 16:17:45ALL PAGES WITH NO ELECTRONIC SIGNATURE, A COPY OF THE
 SIGNATURE OR SEAL IS NOT IN ACCORDANCE WITH FLORIDA
 ADMINISTRATIVE CODE PER 61G15-23.001,

Review Stop Z ZONING
Rev No 4 Status P Date 2022-06-23 Cont ID  
Sent By eschneid Date 2022-06-23 Time 17:05 Rev Time 0.50
Received By eschneid Date 2022-06-23 Time 17:05 Sent To  
Notes
2022-06-23 17:05:52ADDITIONAL SEPARATE PERMITS ARE REQUIRED FOR THE
 FOLLOWING ITEMS:
  
 A. POOL, INCLUDING POOL EQUIPMENT.
 B. DRIVEWAY, INCLUDING APPROACH.
 C. LANDSCAPE AND IRRIGATION.
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2022-02-24 Cont ID  
Sent By eschneid Date 2022-02-24 Time 16:55 Rev Time 0.25
Received By eschneid Date 2022-02-24 Time 16:42 Sent To  
Notes
2022-02-24 16:58:29ADDITIONAL SEPARATE PERMITS ARE REQUIRED FOR THE
 FOLLOWING ITEMS:
  
 A. POOL, INCLUDING POOL EQUIPMENT.
 B. DRIVEWAY, INCLUDING APPROACH.
 C. LANDSCAPE AND IRRIGATION.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-12-01 Cont ID  
Sent By eschneid Date 2021-12-01 Time 12:52 Rev Time 0.50
Received By eschneid Date 2021-11-19 Time 11:21 Sent To  
Notes
2021-11-19 12:07:24ADDITIONAL SEPARATE PERMITS ARE REQUIRED FOR THE
 FOLLOWING ITEMS:
  
 A. POOL, INCLUDING POOL EQUIPMENT. PLEASE NOTE THAT THE
 POOL EQUIPMENT "BOX" AS SHOWN IS ENCROACHING INTO THE
 CORNER SIDE SETBACK. THE FURTHEST PROJECTION OF THE
 EQUIPMENT AND/OR PAD MAY BE NO CLOSER THAN 8.5 FEET
 FROM THE CORNER SIDE PROPERTY LINE.
 B. DRIVEWAY, INCLUDING APPROACH.
 C. LANDSCAPE AND IRRIGATION.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-03 Cont ID  
Sent By eshneide Date 2021-09-03 Time 13:15 Rev Time 1.00
Received By eschneid Date 2021-09-03 Time 11:18 Sent To  
Notes
2021-09-03 13:15:42FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A
 SEPARATE LANDSCAPE PERMIT AND AN IRRIGATION PERMIT MUST
 BE SUBMITTED TO THE BUILDING DIVISION.
  
 2) SUBMIT A CURRENT SURVEY, LESS THAT A YEAR OLD, OF
 THE PROPERTY. THE SITE PLAN DIMENSIONS SHALL MATCH THE
 SURVEY DIMENSIONS.
  
 3) THE LOT IS SHOWN WITH A CURVE AT THE CORNER OF
 GREGORY AND ARLINGTON. THE FRONT SETBACK FOLLOWS THE
 CURVE AS THE IT IS MEASURED FROM THE PROPERTY LINE TO
 THE CLOSEST POINT TO THE HOUSE. THE NORTHWEST CORNER OF
 THE HOUSE IS CLOSER THAN 25 FEET TO THE CURVED PORTION
 OF THE FRONT PROPERTY LINE, WHICH IS NOT PERMITTED.
  
 4) PLEASE PROVIDE THE BUILDING HEIGHT AS DEFINED BY THE
 CITY OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS - BUILDING, HEIGHT OF, MEANS THE VERTICAL
 DISTANCE FROM THE MEAN GRADE OF A LOT AT THE FRONTAGE
 OF THE BUILDING TO THE HIGHEST POINT OF THE TOP OF THE
 STRUCTURE OF A FLAT ROOF, OR TO THE DECK LINE OF A
 MANSARD ROOF, OR TO THE MID-HEIGHT LEVEL BETWEEN EAVES
 AND RIDGE FOR GABLE, HIP, AND GAMBREL ROOFS. YOU HAVE
 ONLY PROVIDED THE HEIGHT FROM THE FINISHED FLOOR.
  
 5) ADDITIONAL SEPARATE PERMITS ARE REQUIRED FOR THE
 FOLLOWING ITEMS:
  
 A. POOL, INCLUDING POOL EQUIPMENT.
 B. DRIVEWAY, INCLUDING APPROACH.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446