Plan Review Details - Permit 21080730
Plan Review Stops For Permit 21080730
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-02-17 Cont ID  
Sent By jgomez Date 2022-02-17 Time 16:31 Rev Time 0.00
Received By jgomez Date 2022-02-17 Time 15:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-11 Cont ID  
Sent By jgomez Date 2022-01-11 Time 11:07 Rev Time 0.00
Received By jgomez Date 2022-01-11 Time 09:00 Sent To  
Notes
2022-01-11 11:08:29RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080730
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ****ALL DRAWINGS NEED TO BE PROPERLY SIGNED AND SEALED
 BEFORE PROVISO.
  
  
 ORIGINAL COMMENT:
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 SUBMIT DRAWINGS ELECTRONICALLY WITH
 ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE
 HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 RESPONSE:
 THE FOLLOWING DRAWINGS WERE NOT SIGNED & SEALED: C-01,
 SP-01, A-00, A-02, A-03, A-04, S1, S3, S4, S5.
  
 2- OK.
 3- OK.
 4- OK.
  
 5-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)OK.
  
 ORIGINAL COMMENT:
 B)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY
 MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE
 PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL
 SUBMITTED.
  
 RESPONSE:
 NOT SUBMITTED.
  
 ORIGINAL COMMENT:
 C)ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY MARK
 WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED. SEE
 SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL
 SUBMITTED.
 THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM
 SEC. 5.8.3.1 IS GOING TO BE INSTALLED.
  
 RESPONSE:
 STILL NOT CLEAR WHICH ASSEMBLY TO BE USED. TABLE 2 ON
 PAGE 4 OF 6 OF PRODUCT APPROVAL WAS MARKED, BUT IT
 DOESN'T CLARIFY IF USING ASTM D226 TYPE II FELT OR
 CITADEL PLUS AS THE SUBSTRATE. I F USING ASTM D226 FELT
 , THEN PROVIDE FRSA/TRI PRESCRIPTIVE METHOD USED. IF
 USING CITADEL PLUS , THEN CIRCLE WHICH ASSEMBLY IS
 GOING TO BE USED. SEE SEC. 5.8.2 OF PRODUCT APPROVAL
 SUBMITTED.
  
 6- OK.
 7- OK.
 8- OK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By jgomez Date 2021-10-14 Time 13:53 Rev Time 0.00
Received By jgomez Date 2021-10-13 Time 14:02 Sent To  
Notes
2021-10-14 13:53:43RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080730
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 NOTE:
 SEC. 606 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 SUBMIT DRAWINGS ELECTRONICALLY WITH
 ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE
 HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 2-LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 3- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807
 FBC-RESIDENTIAL.
  
 4- SPECIFY ROOF SHEATHING NAIL TYPE, SIZE AND SPACING
 AS REQUIRED BY SEC. R803.2 FBC-RESIDENTIAL.
 NOTE: ROOF SHEATHING ATTACHMENT DETAIL 1/S2 DOESN'T
 PROVIDE THIS INFORMATION.
  
 5-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)FRENCH DOOR AS SHOWN ON PLANS.
 NOTE: NOA FRENCH DOOR FL34006.4 UPLOADED TO PROJECTDOX
 SHOWS WINDOW MULLION PRODUCT APPROVAL NOT FRENCH DOOR.
  
 B)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY
 MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE
 PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL
 SUBMITTED.
  
 C)ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY MARK
 WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED. SEE
 SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL
 SUBMITTED.
 THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM
 SEC. 5.8.3.1 IS GOING TO BE INSTALLED.
  
 6- ADDITION IS DESIGNED WITH UNVENTED ATTIC. ARCHITECT
 IS SPECIFYING R-20 ICYNENE SPRAY INSULATION. PROVIDE
 ICC EVALUATION REPORT FOR THE ICYNENE R-20 INSULATION
 TO VERIFY COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 7- DETAIL 4/A-05 AND DETAIL 5 ON SHEET A-05: REVISE THE
 SIZE OF THE STRUCTURAL BUCK SPECIFIED. STRUCTURAL BUCK
 NEEDS TO PROVIDE FULL SUPPORT TO THE DOOR FRAME AND
 NEED TO EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW
 OR DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL. 2X4 BUCK IS SMALLER THAN THE DOOR
 FRAME. REVISE AS REQUIRED.
  
 8-PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR NEW
 AFIREWATER FIREPLACE. SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-12 Cont ID  
Sent By jleahy Date 2022-01-12 Time 16:33 Rev Time 0.00
Received By jleahy Date 2022-01-12 Time 16:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 13:35 Rev Time 0.00
Received By jleahy Date 2021-09-27 Time 13:31 Sent To  
Notes
2021-09-27 13:38:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 220.16 LOADS FOR ADDITIONS TO EXISTING INSTALLATIONS.
  
 (A) DWELLING UNITS. LOADS ADDED TO AN EXISTING DWELLING
 UNIT(S) SHALL COMPLY WITH THE FOLLOWING AS APPLICABLE:
  
 (1) LOADS FOR STRUCTURAL ADDITIONS TO AN EXISTING
 DWELLING UNIT
 OR FOR A PREVIOUSLY UNWIRED PORTION OF AN EXISTING
 DWELLING
 UNIT, EITHER OF WHICH EXCEEDS 46.5 M2 (500 FT2), SHALL
 BE CALCULATED IN ACCORDANCE WITH 220.12 AND 220.14.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-25 Cont ID  
Sent By vbroglia Date 2022-02-25 Time 14:31 Rev Time 0.00
Received By vbroglia Date 2022-02-25 Time 14:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-18 Cont ID  
Sent By vbroglia Date 2022-02-18 Time 10:00 Rev Time 0.00
Received By vbroglia Date 2022-02-18 Time 10:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-12 Cont ID  
Sent By jleahy Date 2022-01-12 Time 16:33 Rev Time 0.00
Received By jleahy Date 2021-12-13 Time 16:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-14 Cont ID  
Sent By jgomez Date 2021-10-14 Time 14:54 Rev Time 0.00
Received By jgomez Date 2021-08-20 Time 15:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-02-28 Cont ID  
Sent By lmarchan Date 2022-02-28 Time 09:03 Rev Time 0.00
Received By lmarchan Date 2022-02-23 Time 15:35 Sent To  
Notes
2022-02-27 07:40:45RECEIPT MU-2022-008441 - $22.46 PAID
2022-02-23 15:35:342/23/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By jgomez Date 2021-10-14 Time 14:47 Rev Time 0.00
Received By jgomez Date 2021-10-14 Time 14:46 Sent To  
Notes
2021-10-14 14:48:00IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-08-30 Cont ID  
Sent By medwards Date 2021-08-30 Time 13:02 Rev Time 0.00
Received By medwards Date 2021-08-30 Time 13:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-12-17 Cont ID  
Sent By lcrespo Date 2021-12-17 Time 13:20 Rev Time 0.00
Received By lcrespo Date 2021-12-17 Time 13:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-09-10 Cont ID  
Sent By lcrespo Date 2021-09-10 Time 10:50 Rev Time 0.00
Received By lcrespo Date 2021-09-10 Time 10:50 Sent To  
Notes
2021-09-10 10:50:2409/10/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-02-17 Cont ID  
Sent By jgomez Date 2022-02-17 Time 16:50 Rev Time 0.00
Received By jgomez Date 2022-02-17 Time 16:33 Sent To  
Notes
2022-02-17 16:33:20SEE SUPPORTING DOCUMENTS FOR APPROVED ROOFING PRODUCTS.
 JG.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-01-11 Cont ID  
Sent By jgomez Date 2022-01-11 Time 11:14 Rev Time 0.00
Received By jgomez Date 2022-01-11 Time 11:08 Sent To  
Notes
2022-01-11 11:14:12SECOND ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY
 MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE
 PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL
 SUBMITTED.
  
 RESPONSE:
 NOT SUBMITTED.
  
 B) ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY
 MARK WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED.
 SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL
 SUBMITTED.
 THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM
 SEC. 5.8.3.1 IS GOING TO BE INSTALLED.
  
 RESPONSE:
 STILL NOT CLEAR WHICH ASSEMBLY TO BE USED. TABLE 2 ON
 PAGE 4 OF 6 OF PRODUCT APPROVAL WAS MARKED, BUT IT
 DOESN'T CLARIFY IF USING ASTM D226 TYPE II FELT OR
 CITADEL PLUS AS THE SUBSTRATE. I F USING ASTM D226 FELT
 , THEN PROVIDE FRSA/TRI PRESCRIPTIVE METHOD USED. IF
 USING CITADEL PLUS , THEN CIRCLE WHICH ASSEMBLY IS
 GOING TO BE USED. SEE SEC. 5.8.2 OF PRODUCT APPROVAL
 SUBMITTED.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By jgomez Date 2021-10-14 Time 14:48 Rev Time 0.00
Received By jgomez Date 2021-10-14 Time 14:48 Sent To  
Notes
2021-10-14 14:51:36ROOFING REVIEW:
  
 1-PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)HIP & RIDGE METAL SUPPORT TO BE USED. AND, CLEARLY
 MARK SPECIFIC METAL CHANNEL TO BE INSTALLED. SEE
 PERFORMANCE LIMITATIONS TABLES ON PRODUCT APPROVAL
 SUBMITTED.
  
 B) ROOF UNDERLAYMENT FL14317-R12 SUBMITTED: CLEARLY
 MARK WHICH TESTED ASSEMBLY IS GOING TO BE INSTALLED.
 SEC. 5.8.2 AND SEC. 5.8.3 OF PRODUCT APPROVAL
 SUBMITTED.
 THERE ARE 6 ASSEMBLIES. SPECIFY WHICH ASSEMBLY FROM
 SEC. 5.8.3.1 IS GOING TO BE INSTALLED.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-02-23 Cont ID  
Sent By jgomez Date 2022-02-23 Time 08:43 Rev Time 0.00
Received By jgomez Date 2022-02-23 Time 08:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-02-17 Cont ID  
Sent By jgomez Date 2022-02-17 Time 16:53 Rev Time 0.00
Received By jgomez Date 2022-02-17 Time 16:53 Sent To  
Notes
2022-02-17 16:56:12SIGNATURE REVIEW:
  
 1- DRAWING C-01 STILL NOT SIGNED AND SEALED.
 CHAPTER 481 F.S.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-11 Cont ID  
Sent By jgomez Date 2022-01-11 Time 11:17 Rev Time 0.00
Received By jgomez Date 2022-01-11 Time 11:16 Sent To  
Notes
2022-01-11 11:16:45SIGNATURE REVIEW:
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 SUBMIT DRAWINGS ELECTRONICALLY WITH
 ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE
 HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 RESPONSE:
 THE FOLLOWING DRAWINGS WERE NOT SIGNED & SEALED: C-01,
 SP-01, A-00, A-02, A-03, A-04, S1, S3, S4, S5.
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By jgomez Date 2021-10-14 Time 14:52 Rev Time 0.00
Received By jgomez Date 2021-10-14 Time 14:51 Sent To  
Notes
2021-10-14 14:52:32SIGNATURE REVIEW:
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEER OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 SUBMIT DRAWINGS ELECTRONICALLY WITH
 ARCHITECT'S/ENGINEER'S DIGITAL SIGNATURE OR PROVIDE
 HARD COPY PLANS WITH ARCHITECT'S ORIGINAL SEAL AND
 SIGNATURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2022-02-25 Cont ID  
Sent By vbroglia Date 2022-02-25 Time 14:30 Rev Time 0.00
Received By vbroglia Date 2022-02-25 Time 14:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-02-18 Cont ID  
Sent By vbroglia Date 2022-02-18 Time 09:17 Rev Time 0.00
Received By vbroglia Date 2022-02-18 Time 09:17 Sent To  
Notes
2022-02-18 10:00:162/18/2022 FAILED-
  
 PLEASE APPLY FOR LANDSCAPE PERMIT THAT OBTAINS A PERMIT
 NUMBER. PLEASE APPLY FOR A TREE ALTERATION PERMIT
  
 PERMITS MUST BE APPLIED FOR TO ALLOW STAFF TO MOVE
 FOWARD.
  
 IF YOU HAVE ANY QUESTIONS REGARDING LANDSCAPE PLEASE
 CONTACT RAY CARANCI AT [email protected]
  
 VALENTINA BROGLIA
 ASSOICATA PLANNER
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2022-01-03 Cont ID  
Sent By ajones Date 2022-01-03 Time 12:13 Rev Time 0.00
Received By ajones Date 2022-01-03 Time 12:13 Sent To  
Notes
2022-01-03 13:38:471/3/22- FAILED. SINCE VALUE OF THE PERMIT EXCEED 50% OF
 THE VALUE OF THE EXISTING HOME (PBCPA), THAN THE SITE
 MUST MEET THE APPROVED LANDSCAPE PLAN (18050615). IN
 ADDITION, IT APPEARS THAT LANDSAPING WILL BE REMOVED TO
 CONSTRUCT THE ADDITION. IF THIS IS THE CASE THAN A TREE
 ALTERATION PERMIT IS REQUIRED.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-09-03 Cont ID  
Sent By awooten Date 2021-09-03 Time   Rev Time  
Received By awooten Date 2021-09-03 Time   Sent To  
Notes
2021-09-03 16:29:08******************ZONING
 REVIEW*************************
  
 PROJECT VALUE TRIGGERS THE LANDSCAPE CODE.
  
 SHOW THE FOLLOWING ON A SEPARATE LANDSCAPE PLAN.
  
 RESIDENTIAL LANDSCAPE REQUIREMENTS CITY OF WEST PALM
 BEACH
 SECTION 94-442(C)(2)A. SINGLE FAMILY DWELLING UNITS
  
 O GROSS LOT SQUARE FOOTAGE MINUS
 O BUILDING FOOTPRINT SQUARE FOOTAGE EQUALS
 O OPEN SPACE SQUARE FOOTAGE (ALL NON-BUILDING AREA)
 O ONE TREE REQUIRED FOR EACH 1,000 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
 O ONE SHRUB REQUIRED FOR EACH 500 SQ FT OF OPEN SPACE
 OR PORTION THEREOF
  
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]