| 2021-09-03 17:37:49 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21080665 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | 1- REVISE SHUTTERS INSTALLATION SCHEDULE: SHUTTER SPAN |
| | FOR OPENINGS 15 AND 16 IS 133". NEED TO REVISE THE |
| | ANCHOR SPACING. SEE PAGE 13 OF 17 OF SHUTTERS PRODUCT |
| | APPROVAL SUBMITTED. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | NOTE: |
| | MINIMUM EDGE DISTANCE SHOWN. CLEARLY SPECIFY IF THE |
| | EDGE DISTANCE SHOWN INCLUDES THE STUCCO THICKNESS OR |
| | NOT. THIS IS IMPORTANT BECAUSE IN THE FIELD THE ACTUAL |
| | EDGE DISTANCE NEED TO BE LARGER THAN THE ONE SHOWN ON |
| | THE SCHEDULE (TYPICALLY 1/2 MORE TO INCLUDE THE |
| | STUCCO). |
| | |
| | 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR |
| | PROVIDE COPY OF SIGNED CONTRACTS FOR BUILDING OFFICIAL |
| | CONSIDERATION. |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |