Plan Review Details - Permit 21080661
| Plan Review Stops For Permit 21080661 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-09-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-09-08 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-09-08 |
Time |
13:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-08-21 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-08-21 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2021-08-21 11:14:04 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO | | | [email protected]. THE INFORMATION SHOULD BE IN | | | PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE | | | INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT | | | LINE. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-09-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-09-08 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-09-08 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-08-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-08-21 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-08-21 |
Time |
11:14 |
Sent To |
|
|
| Notes |
| 2021-08-21 11:16:45 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. AN INTERIOR DEMO PERMIT SHOULD INCLUDE ONLY INTERIOR | | | ELEMENTS. IF YOU WISH TO DEMOLISH EXTERIOR ELEMENTS, TO | | | PRESERVE THE BUILDING ENVELOPE YOU NEED TO SUBMIT | | | APPLICATION FOR A COMMERCIAL REMODEL AND INCLUDE | | | DETAILS AS TO HOW THE EXTERIOR WILL BE RESTORED TO A | | | WATERTIGHT CONDITION, FBC 107. | | | FOR THIS INTERIOR DEMO PERMIT, REMOVE ALL WORK PROPOSED | | | TO THE BUILDING EXTERIOR. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-08-30 |
Time |
18:58 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-08-26 |
Time |
20:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-09-17 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-09-17 |
Time |
16:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2021-08-24 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-08-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-08-24 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2021-08-24 12:14:05 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) THERE ARE INDICATIONS OF HIGHLIGHTES AREA AS WELL AS | | | NON-HIGHLIGHTED AREAS. THE APPLICATION STATES INTERIOR | | | DEMO. | | | | | | FOR CLARIFICATION PURPOSES WHAT IS THE ACTUAL EXTENT OF | | | THE PROPOSED DEMO WORK. | | | | | | | | | 1A) THERE ARE NO INDICATIONS OF EXISTING FIRE | | | SPRINKLERS OR FIRE ALARM EQUIPMENT. | | | | | | ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO, | | | SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. | | | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-08-30 |
Time |
18:59 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-08-19 |
Time |
08:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-08-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-21 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-21 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-08-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-21 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-21 |
Time |
10:39 |
Sent To |
|
|
| Notes |
|
|
|