Plan Review Details - Permit 21080643
Plan Review Stops For Permit 21080643
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-09 Cont ID  
Sent By rmcphers Date 2021-12-09 Time 07:43 Rev Time 0.00
Received By rmcphers Date 2021-12-09 Time 07:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-04 Cont ID  
Sent By rmcphers Date 2021-11-04 Time 07:48 Rev Time 0.00
Received By rmcphers Date 2021-11-04 Time 07:48 Sent To  
Notes
2021-11-04 07:50:28OFFICE BUILD OUT REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE OVERHEAD DOOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-18 Cont ID  
Sent By rmcphers Date 2021-10-18 Time 09:05 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 09:05 Sent To  
Notes
2021-10-18 09:05:57OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE OVERHEAD
 DOOR. ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE DESIGNER OF RECORD FBC 107.3.4

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 11:04 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 10:56 Sent To  
Notes
2021-08-30 11:04:30OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DOORS NUMBER 1 AND 2 ARE PART OF A FIRE RATED WALL -
 ARE THE DOOR TO BE FIRE RATED? - IF SO, PLEASE SHOW THE
 HOURLY FIRE RATING AND SELF CLOSING ON THE DOOR
 SCHEDULE PER FBC 716
 2) PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE OVERHEAD
 DOOR. ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE DESIGNER OF RECORD FBC 107.3.4

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-23 Cont ID  
Sent By jleahy Date 2021-09-23 Time 14:43 Rev Time 0.00
Received By jleahy Date 2021-09-23 Time 14:36 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 08:56 Rev Time 0.00
Received By jleahy Date 2021-09-27 Time 08:56 Sent To  
Notes
2021-09-27 08:57:31VOICE AND DATA ONLY JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-17 Cont ID  
Sent By pleduc Date 2021-08-17 Time   Rev Time 0.00
Received By pleduc Date 2021-08-17 Time 11:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-09 Cont ID  
Sent By rmcphers Date 2021-12-09 Time 07:45 Rev Time 0.00
Received By rmcphers Date 2021-12-03 Time 08:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-04 Cont ID  
Sent By rmcphers Date 2021-11-04 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2021-10-29 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-10-20 Time   Rev Time 0.00
Received By aoliver Date 2021-10-06 Time 07:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-23 Cont ID  
Sent By jleahy Date 2021-09-23 Time 14:43 Rev Time 0.00
Received By jleahy Date 2021-08-16 Time 09:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-12-06 Cont ID  
Sent By medwards Date 2021-12-06 Time 07:08 Rev Time 0.00
Received By medwards Date 2021-12-06 Time 07:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-11-01 Cont ID  
Sent By medwards Date 2021-11-01 Time 13:17 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 13:17 Sent To  
Notes
2021-11-01 13:21:121) SHEET M1.1: THE OUTDOOR AIR CALCULATIONS FOR THE
 MEETING/CONFERENCE ROOM IS LOW. PLEASE PROVIDE OUTDOOR
 AIR CALCULATIONS FOR THIS USE OF SPACE ACCORDING TO FBC
 M 403.3.1.1 AND TABLE 403.3.1.1. THE CORRECT OUTDOOR
 AIR FOR THIS SPACE IS 601 CFM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-10-15 Cont ID  
Sent By medwards Date 2021-10-15 Time 11:28 Rev Time 0.00
Received By medwards Date 2021-10-15 Time 10:42 Sent To  
Notes
2021-10-15 11:28:492ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21080643
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE IN THIS PROJECT, NOT GROUPING DIFFERENT USES
 INTO THE SQUARE FOOTAGE OF THE ENTIRE AREA. I WILL NEED
 THE USE OF SPACE AND THE SQUARE FOOTAGE ALONG WITH THE
 USE OF SPACE BASED ON THE OCCUPANCY IN TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-27 Cont ID  
Sent By medwards Date 2021-08-27 Time 10:08 Rev Time 0.00
Received By medwards Date 2021-08-27 Time 09:40 Sent To  
Notes
2021-08-27 10:08:361ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080643
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR EACH USE
 OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 2) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR NEW RTU-34. FBC EC C403.2.1
  
 3) SHEET M1.1: THE MEETING ROOM APPEARS TO HAVE RATED
 WALLS. RTU-24 APPEARS TO BE SPLIT BY THE NEW RATED
 WALL. PLEASE SHOW A DETAIL OF HOW THIS INSTALLATION IS
 GOING TO WORK. FBC M 607
  
 4) THERE ARE SEVERAL DUCTS PENETRATING THE NEW RATED
 WALLS OF THE MEETING ROOM. PLEASE SHOW HOW THE
 PENETRATION OF THE DUCT AT THESE WALLS WILL BE
 PROTECTED. FBC M 607
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By ccole Date 2021-10-20 Time 13:41 Rev Time 0.00
Received By ccole Date 2021-10-20 Time 12:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-09 Cont ID  
Sent By ccole Date 2021-09-09 Time 08:20 Rev Time 0.00
Received By ccole Date 2021-09-08 Time 17:12 Sent To  
Notes
2021-09-09 08:20:391ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21080643
 9/9/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P0.1 & P1.1. PROVIDE A PLUMBING FIXTURE
 SCHEDULE THAT INCLUDES THE MOP SINK, BREAKROOM SINK,
 FAUCETS, WASHING MACHINE- SECTIONS 406, 418, & 424 FBC
 P.
  
 2) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER
 HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY
 LINES TO THE REFRIGERATOR ICE MAKERS IN THE BREAKROOM,
 AND THE ICE MACHINE IN THE EXISTING WAREHOUSE- SECTIONS
 604.9 & 608.3 FBC P. CLARIFY IF WALL BOXES WILL BE
 INSTALLED AT THE REFRIGERATOR LOCATIONS- SECTION
 107.2.1 WPB.
  
 3) ) P0.1 & P1.1: SHOW THE LOCATIONS OF REQUIRED WATER
 HAMMER ARRESTORS AND BACKFLOW PREVENTERS ON SUPPLY
 LINES TO THE WASHING MACHINE IN THE EXISTING WAREHOUSE-
 SECTIONS 604.9 FBC P. CLARIFY IF A WALL BOXES WILL BE
 INSTALLED AT THE MACHINE LOCATION- SECTION 107.2.1 WPB.
  
 4) P0.1 & P1.1: PROVIDE AN INTERCEPTOR FOR THE WASHING
 MACHINE DISCHARGE- SECTION 1003.6 FBC P. PLEASE NOTE AN
 INTERCEPTOR IS NOT AN INTEGRAL FILTER.
  
 5) P0.1 & P1.1: PLEASE REVIEW AND SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS FOR THE ICE MACHINE TO
 VERIFY A FLOOR DRAIN IS NOT REQUIRED TO CONVEY ICE
 DRAINAGE OR CONDENSATION FROM THE MACHINE- SECTION
 314.2.1 FBC P.
  
 6) P1.1: SHOW A 2-INCH STANDPIPE CONNECTIONG TO A
 3-INCH STACK AT THE WASHING MACHINE- SECTION 406.1 FBC
 P.
  
 7) A3.0: PAINTED GWB IS NOT APPROVED FOR INSTALLATION
 ON THE WALLS SURROUNDING THE MOP SINK. A SMOOTH, HARD,
 NONABSORBENT SURFACE MATERIAL IS REQUIRED TO BE
 INSTALLED TO A HEIGHT OF NOT LESS THAN 4 FT. ABOVE THE
 FLOOR- SECTION 1210.2.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-12-09 Cont ID  
Sent By rmcphers Date 2021-12-09 Time 07:45 Rev Time 0.00
Received By rmcphers Date 2021-12-09 Time 07:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-11-04 Cont ID  
Sent By rmcphers Date 2021-11-04 Time 07:53 Rev Time 0.00
Received By rmcphers Date 2021-11-04 Time 07:53 Sent To  
Notes
2021-11-04 07:53:41SIGNATURE REVIEW
  
 DRAWINGS BELOW AS LABELED IN PROJECTDOX DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 012 P0.1 PLUMBING NOTES.PDF V3
 013 P1.1 PLUMBING PLAN.PDF V3
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-10-18 Cont ID  
Sent By rmcphers Date 2021-10-18 Time 09:12 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 09:12 Sent To  
Notes
2021-10-18 09:09:07SIGNATURE REVIEW
  
 DRAWINGS BELOW AS LABELED IN PROJECTDOX DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 009 M1.1 MECHANICAL PLAN.PDF V3
 012 P0.1 PLUMBING NOTES.PDF V3
 013 P1.1 PLUMBING PLAN.PDF V3
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-27 Cont ID  
Sent By medwards Date 2021-08-27 Time 10:13 Rev Time 0.00
Received By medwards Date 2021-08-27 Time 10:13 Sent To  
Notes
***NONE***