Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-09-22 Cont ID  
Sent By medwards Date 2021-09-22 Time 10:03 Rev Time 0.00
Received By medwards Date 2021-09-22 Time 10:03 Sent To  
Notes
2021-09-22 10:03:50MINISPLIT FOR THE CASITA ONLY. ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-24 Cont ID  
Sent By medwards Date 2021-08-24 Time 06:25 Rev Time 0.00
Received By medwards Date 2021-08-24 Time 06:20 Sent To  
Notes
2021-08-24 06:34:331) DRAWING MUST HAVE A DETAIL SHOWING THE ANCHORING OF
 THE CONDENSING UNIT FOR THE CASITA. FBC RES M1307.2
  
 2) PLEASE SHOW THE CONDENSATE TERMINATION LOCATION. FBC
 RES M1411.3
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER