Plan Review Details - Permit 21080603
Plan Review Stops For Permit 21080603
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-09-14 Cont ID  
Sent By jwitmer Date 2021-09-14 Time 07:51 Rev Time 0.00
Received By jwitmer Date 2021-09-14 Time 07:51 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 15:21 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 15:21:39TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-05 Cont ID  
Sent By jwitmer Date 2021-10-05 Time 09:16 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 15:22 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 15:20:04WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21080603
 ADD: 1200 S. FLAGLER DR. # 506
 CONT: SBL CONTRACTING GROUP
 TEL: 561-676-6060
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 01/2021
 ACTION: DENIED
 1) FLOOR PLAN WITH CUT SECTION OF DROPPED CEILING.
 PLANS INDICATE TO USE RC-1 RESILIENT SOUND CHANNEL TO
 DROP THE CEILING APPROXIMATELY 7/8 OF AN INCH.
  
 1A) THE PLAN DOES NOT INDICATE HOW THE RC-1 CHANNEL IS
 GOING TO BE ATTACHED TO THE EXISTING CONCRETE CEILING
 AND THE FREQUENCY OF THE FASTENERS. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 1B) THE CUT SECTION FOR THE DROPPED CEILING SHOWS THE
 USE OF RC-1 RESILIENT SOUND CHANNEL (APPROXIMATELY 7/8
 INCH IN HEIGHT). WHAT TYPE OF HIGH HATS ARE GOING TO
 FIT IN THE SPACE CREATED BY THE HIGH HAT/ RC-1 CHANNEL?
 PLEASE SUPPLY A MANUFACTURERS SPEC FOR THIS PRODUCT.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. THE
 ELECTRICAL SHEET INDICATES 3 INCH LED HIGH HATS.
  
 1C) THE CUT SECTION FOR THE DROPPED CEILING SHOWS THE
 USE OF RC-1 RESILIENT SOUND CHANNEL AND NOTATION
 DRYWALL CEILING, THE THICKNESS OF THE DRYWALL IS NOT
 GIVEN? 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 1D) THE OVERALL HEIGHT OF THE DROPPED CEILING IS NOT
 GIVEN, WILL NEED TO SHOW COMPLIANCE WITH 2020 FBC-B
 SECTION 1208.2 MINIMUM CEILING HEIGHTS FOR HABITABLE
 ROOMS SHALL HAVE A CEILING NOT LESS THAN 7 FEET 6
 INCHES FROM FINISH FLOOR.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By fgiaquin Date 2021-10-20 Time 20:11 Rev Time 0.00
Received By fgiaquin Date 2021-10-20 Time 19:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-09-27 Cont ID  
Sent By fgiaquin Date 2021-09-27 Time 06:29 Rev Time 0.00
Received By fgiaquin Date 2021-09-24 Time 18:55 Sent To  
Notes
2021-09-27 06:29:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. A CGC IS NOT PERMITTED TO DRAW/DESIGN/SIGN AN
 ELECTRICAL DRAWING. ELECTRICAL PLAN IS REQUIRED TO BE
 DESIGNED AND SIGNED/SEALED BY A DESIGN PROFESSIONAL OR
 SIGNED BY THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-09-29 Cont ID  
Sent By cwalker Date 2021-09-29 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-24 Cont ID  
Sent By cwalker Date 2021-08-24 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-20 Cont ID  
Sent By fgiaquin Date 2021-10-20 Time 20:12 Rev Time 0.00
Received By fgiaquin Date 2021-09-28 Time 09:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-27 Cont ID  
Sent By fgiaquin Date 2021-09-27 Time 06:29 Rev Time 0.00
Received By fgiaquin Date 2021-08-20 Time 12:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-05 Cont ID  
Sent By jwitmer Date 2021-10-05 Time 09:16 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 15:22 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 15:27:37THE GENERAL CONTRACTOR CAN NOT DRAW PLANS FOR
 ELECTRICAL WORK UNLESS THEY ARE LICENSED IN THAT TRADE
 AND DOING THE WORK AS ANLICENSED ELECTRICAL CONTRACTOR.
 CERTIFICATION BY CONTRACTOR. 107.3.4.3. THE CONTRACTOR
 (QUALIFIER) THAT CREATED / DREW THE SET OF PLANS WILL
 NEED TO IDENTIFY THEMSELVES AS THE AUTHOR OF THE PLANS.
 PLEASE PRINT YOUR NAME, SIGN YOUR NAME AND LICENSE
 NUMBER FOR THE TRADE YOU ARE LICENSED IN AND PLANS
 DRAWN.
 107.3.4.3 CERTIFICATION BY CONTRACTOR. PLEASE NOTE THE
 EXCEPTION TO ENGINEERED PLANS UNDER 471.003(H)
 ELECTRICAL/ PLUMBING/ MECHANICAL, 481.229(1)(C)
 (BUILDING) REQUIRES THE CONTRACTOR FOR THAT TRADE THAT
 WILL BE LICENSED IN THAT TRADE, WILL ALSO BE THE
 CONTRACTOR THAT DESIGNS THE SYSTEM UNDER THAT TRADE.
 THE CONTRACTOR (QUALIFIER) THAT CREATED / DREW THE SET
 OF PLANS WILL NEED TO IDENTIFY THEMSELVES AS THE AUTHOR
 OF THE PLANS. PLEASE PRINT YOUR NAME, SIGN YOUR NAME
 AND LICENSE NUMBER FOR THE TRADE YOU ARE LICENSED IN
 AND PLANS DRAWN.
 FOR EACH TRADE THE CONTRACTOR RESPONSIBLE FOR THE
 DESIGN UNDER THE TRADE LICENSED IN MUST PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER, NOTE THESE
 PLANS APPEAR TO BE DRAWN BY ONE INDUVIAL, THEY WOULD
 HAVE TO BE LICENSED AS A BUILDING, ELECTRICAL AND
 PLUMBING CONTRACTOR TO SUBMIT ALL THESE TRADES UNDER
 ONE SHEET.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  