Plan Review Details - Permit 21080581
Plan Review Stops For Permit 21080581
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-08-13 Cont ID  
Sent By cpuell Date 2021-08-13 Time 12:04 Rev Time 0.00
Received By cpuell Date 2021-08-13 Time 12:04 Sent To  
Notes
2021-08-13 12:04:45PLANS IDENTIFY TENANT SPACE OF 366 S ROSEMARY AVE
 UPDATED PERMIT TO REFLECT THE TENANT ADDRESS.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 13:34 Rev Time 0.00
Received By lcrespo Date 2021-08-26 Time 13:34 Sent To  
Notes
2021-08-26 13:35:5508/26/21 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 16:15 Rev Time 0.00
Received By jesmith Date 2022-08-09 Time 16:45 Sent To  
Notes
2021-08-17 16:15:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080581 366 S ROSEMARY AVE
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 IT APPEARS THAT THIS PERMIT IS BEING APPLIED FOR TO
 ALLOW A BASIC FUEL GAS LINE TO BE INSTALLED FOR FUTURE
 USE.
  
 1.PER WPB FBC 107.2.1, PROVIDE A NOTE ON THE PLANS
 STATING THE WORK IS FOR PROVISION OF GAS PIPING FOR
 FUTURE TENANT USE. A SEPARATE PERMIT AND PLANS WILL BE
 REQUIRED FOR ANY FUTURE WORK AND THE INFORMATION ON
 THESE PLANS SHALL BE INCORPORATED INTO THE FUTURE WORK.
  
 2.PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING
 INFORMATION
 ?A)SPECIFY THE FUEL TYPE; NATURAL GAS OR LIQUIFIED
 PETROLEUM
 ?B)SPECIFY THE DELIVERY PRESSURE FROM THE
 METER/REGULATOR
 ?C)PROVIDE THE DEVELOPED LENGTH OF EACH SERVICE FROM
 THE METER TO POINT OF TERMINATION
 ?D)PROVIDE THE TABLE(S) NOTING PRESSURE AND MATERIAL
 TYPE FROM FBC FG 402.4 THAT FUTURE CALCULATIONS FOR
 SIZING SHALL BE BASED UPON.
  
 3.PLAN SHEET FG0.1: GENERAL GAS NOTES 16 AND 17
 INDICATE LPG; FUEL GAS SYMBOL LEGEND AND ABBREVIATIONS
 INDICATE NATURAL GAS. PER WPB FBC 107.2.1, CLARIFY.
  
 4.PLAN SHEET FG0.1: GENERAL GAS NOTES 2 AND 3 APPEAR TO
 ALLOW PIPING MATERIALS OTHER THAN SCHEDULE 40
 GALVANIZED STEEL PIPE. FG1.1; FUEL GAS KEYNOTE F02
 SPECIFICALLY CALLS FOR SCHEDULE 40 GALVANIZED STEEL
 PIPE. PER WPB FBC 107.2.1, CLARIFY. IF YOU ARE ALLOWING
 OTHER TYPES OF MATERIAL THEN PER WPB FBC 107.2.1,
 PROVIDE TABLE FROM FBC FG 402.4 FOR EACH TYPE OF
 MATERIAL ALLOWED. (SEE COMMENT 2D ABOVE)
  
 5.PLAN SHEET FG1.1: FUEL GAS KEYNOTE F02; PER WPB FBC
 107.2.1, ADD AFTER ?PROVIDE SHUT OFF VALVE? THE WORDS
 ?AND CAP? TO COMPLY WITH FBC FG 404.15.
  
 6.PLAN SHEET FG1.2: PER WPB FBC 107.2.1, PROVIDE A CAP
 AT END OF EACH LINE WHERE TERMINATES AT THE TENANT
 SPACE TO COMPLY WITH FBC FG 404.15.
  
 7. PER WPB FBC 107.2.1, PROVIDE A HANGER DETAIL FOR
 HORIZONTAL SUSPENDED PIPING.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 13:35 Rev Time 0.00
Received By lcrespo Date 2021-08-25 Time 12:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 16:58 Rev Time 0.00
Received By pvalenti Date 2021-08-12 Time 14:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 13:34 Rev Time 0.00
Received By lcrespo Date 2021-08-26 Time 13:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 16:58 Rev Time 0.00
Received By pvalenti Date 2021-08-17 Time 12:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-08-26 Cont ID  
Sent By lcrespo Date 2021-08-26 Time 13:35 Rev Time 0.00
Received By lcrespo Date 2021-08-26 Time 13:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-17 Cont ID  
Sent By pvalenti Date 2021-08-17 Time 13:28 Rev Time 0.00
Received By pvalenti Date 2021-08-17 Time 13:25 Sent To  
Notes
***NONE***