| Plan Review Stops For Permit 21080553 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-30 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-30 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-08-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-17 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-17 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2021-08-17 15:37:05 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-30 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-30 |
Time |
08:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-08-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-17 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-17 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2021-08-17 15:48:56 | BUILDING SHELL ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE SHOW THE FIRE RATED WALLS AS "FIRE WALLS", | | | "FIRE BARRIERS" OR "FIRE PARTITIONS" PER FBC 706, 707, | | | 708 (DRAWINGS REFER TO "DEMISING WALLS" WHICH ARE NOT | | | DEFINED IN THE FBC). | | | 2) PLEASE SHOW IF TERMITE TREATMENT IS REQUIRED ON | | | DRAWING S-300 DETAIL 3 "TRENCHED SLAB IN GRADE INFILL" | | | FBC 1816.1.2 | | | IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE | | | PREVENTION, SOIL AREA DISTURBED AFTER INITIAL CHEMICAL | | | SOIL TREATMENT SHALL BE RETREATED WITH A CHEMICAL SOIL | | | TREATMENT, INCLUDING SPACES BOXED OR FORMED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-09-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-04 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-09-04 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-08-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-20 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-20 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2021-08-20 15:45:57 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | WEST PALM BEACH PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | | APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL | | | PERMIT APPLICATION TO [email protected] AND | | | [email protected] SO WE RECEIVE IT ALSO. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-09-03 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-09-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2021-09-02 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2021-09-02 13:10:02 | OVERHEAD FIRE DOOR MANUFACTURERS SHEET FROM "FIREKING" | | | RECEIVED, INCLUDING DOOR DETAIL, LISTING/RATING FOR | | | RATED FIRE DOOR ASSEMBLY TO BE INSTALLED IN SPECIFIED | | | PENETRATION IN 3 HOUR RATED FIRE WALL. | | | | | | ANY AND ALL WORK ON FIRE ALARM AND SPRINKLER SYSTEMS | | | SHALL BE DONE BY A FIRE ALARM CONTRACTOR UNDER SEPARATE | | | PERMITS. SEPARATE SHOP DRAWINGS ARE REQUIRED TO BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION | | | BUREAU PRIOR TO ANY INSTALLATION. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-09-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-09-04 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-27 |
Time |
07:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-08-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-08-20 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-08-13 |
Time |
07:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-08-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-08-19 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-08-19 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-30 |
Time |
08:09 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-30 |
Time |
08:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-08-17 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-08-17 |
Time |
16:03 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-08-17 |
Time |
16:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-08-19 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2021-08-19 |
Time |
16:41 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2021-08-19 |
Time |
16:41 |
Sent To |
|
|
| Notes |
|
|