| Plan Review Stops For Permit 21080543 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-10-28 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-10-28 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-10-28 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2021-10-28 15:07:20 | PLANS NO LONGER REFERENCE GUEST HOUSE, INSTEAD | | | REFERENCE STORAGE BUILDING, NO ADDITIONAL ADDRESS | | | NEEDED. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-09-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-09-08 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-09-08 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2021-09-08 16:42:43 | EXISTING GUEST HOUSE - PLEASE COORDINATE WITH | | | [email protected] FOR THE LIVABLE SPACE TO BE GIVEN AN | | | ADDRESS. ALL ACCESSORY RESIDENTIAL/COMMERCIAL UNITS AND | | | OR OTHER HABITABLE STRUCTURES WILL BE ISSUED A UNIQUE | | | SECONDARY ADDRESS NUMBER PER CITY'S ADDRESSING POLICY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-11-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-11-29 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-29 |
Time |
12:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-10-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-12 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-10-12 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2021-10-12 10:40:04 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. THERE ARE MULTIPLE PLAN PAGES WITH THE SAME NAME BUT | | | WITH A DIFFERENT SCOPE OF WORK (SOW). | | | I.E. SP-1 (4), D-1, D-2, A-1, A-2, S-1 (2 EACH) | | | UPLOAD PLANS USING THE REQUIRED NAMING CONVENTION. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. INCORRECT DESIGN CODE REFERENCE ON PLAN E-3, NOTES | | | 2, 3 & 4. CURRENT DESIGN SHALL BE BY THE 2020 FBC RES. | | | AND NEC 2017. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-11-16 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-11-16 |
Time |
23:48 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-11-16 |
Time |
23:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-09-20 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-09-20 |
Time |
22:15 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-09-20 |
Time |
21:25 |
Sent To |
|
|
| Notes |
| 2021-09-20 22:15:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. NOTES ON PLAN REFERENCE APPLICABLE BUILDING CODE AS | | | 2014 FBC, CURRENT ADOPTED CODE IS FBC 2020 7TH EDITION. | | | PROVIDE CORRECTION. | | | | | | 2. NOTES ON PLAN REFERENCE APPLICABLE ELECTRICAL CODE | | | AS 2014 NEC, CURRENT ADOPTED CODE IS NEC 2017 PROVIDE | | | CORRECTION. | | | | | | 3. RECEPTACLES REQUIRED ON BOTH FRONT AND REAR OF | | | DWELLING OUTSIDE. NEC 210.52E1 | | | | | | 4. EQUIPMENT GROUND IS SHOWN FROM METER-CAN TO SERVICE | | | RATED ATS. EQUIPMENT GROUND ORGINATES AT SERVICE | | | DISCONNECTING MEANS (ATS). REMOVE EQUIPMENT GROUND FROM | | | METERCAN TO ATS. NEC 250. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-11-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-11-02 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-11-02 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-09-17 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-17 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-10-22 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-10-22 |
Time |
09:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2021-12-10 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-12-10 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-12-10 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-08 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-07 |
Time |
08:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-11-30 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-11-30 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-10-28 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-22 |
Time |
15:04 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-08-23 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-08 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-08 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2021-10-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-10-29 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-10-29 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2021-10-29 08:27:33 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21080543 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-1: PLEASE SHOW THE RETURN AIR PATH FROM THE | | | DEN AND THE DINING ROOM BACK TO THE AHU. FBC RES | | | M1602.3 | | | | | | 2) PLEASE SHOW THE REQUIRED BATHROOM EXHAUST FAN FOR | | | THE SHOWER AREA OF THE MASTER BATH. FBC RES M1507.4 | | | | | | 3) PLEASE SHOW THE CONDENSATE PIPING, SIZE, MATERIAL | | | AND TERMINATION LOCATION. FBC RES M1411.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2021-09-17 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2021-09-17 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2021-09-17 09:23:27 | NO AIR CONDITIONING PLAN SUBMITTED. HM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2021-11-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-11-02 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-11-02 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-09-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-09-17 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-09-17 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2021-11-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-11-29 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-29 |
Time |
12:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-10-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-12 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-10-12 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2021-10-12 10:57:19 | ROOFING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | 2017 NEC | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ROOFING PERMIT REQUIRED. | | | PERMITS - 105.1 REQUIRED. | | | | | | 2. IDENTIFY TYPE OF UNDERLAYMENT FOR PROPOSED ROOFING. | | | (BARREL TILE SUBMITTED FOR REVIEW) | | | R905.1.1 | | | PROVIDE PRODUCT APPROVALS OF UNDERLAYMENT. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD | | | | | | 3. DESIGNER SHALL INDICATE ATTACHMENT METHOD OF ROOF | | | COVERING IN NOA. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 3. IF ATTACHMENT METHOD SELECTED IS ADHESIVE, PROVIDE | | | PRODUCT APPROVALS FOR TYPE OF ADHESIVE. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 4. ROOF HAS AREAS OF PITCHED ROOFING AND FLAT ROOFING. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 4. PROVIDE A ROOF PLAN. IDENTIFY ROOF AREAS TO RECEIVE | | | ROOFING. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5. IF FLAT ROOF IS TO BE RE-COVERED, PROVIDE PRODUCT | | | APPROVALS FOR FLAT ROOFING. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 6. WILL ACCESSORY STRUCTURE RECEIVE REPLACEMENT | | | ROOFING? (FLAT) | | | INDICATE ON SITE PLAN. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2021-12-10 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-12-10 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-12-10 |
Time |
13:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2021-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-07 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-07 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2021-12-07 14:19:53 | SIGNATURE REVIEW | | | | | | DOCUMENT LABELED "PRODUCT APPROVAL_ARCHITECTURAL LETTER | | | OF NOAS PRODUCT APPROVAL.PDF" IN PROJECTDOX DOES NOT | | | SHOW AS DIGITALLY SIGNED IN ADOBE READER - | | | | | | ALL OTHER DRAWINGS = ORIGINAL SIGNED AND SEALED | | | DRAWINGS WERE PROVIDED AND TAKEN TO FILE. | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-11-29 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-11-29 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-11-29 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2021-11-29 14:12:19 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-10-12 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-10-12 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-10-12 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2021-10-12 10:32:40 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2021-11-30 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-11-30 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-11-30 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2021-10-22 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2021-10-22 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|