Plan Review Details - Permit 21080535
Plan Review Stops For Permit 21080535
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-22 Cont ID  
Sent By rmcphers Date 2022-06-22 Time 13:41 Rev Time 0.00
Received By rmcphers Date 2022-06-22 Time 13:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By rmcphers Date 2022-04-11 Time 13:16 Rev Time 0.00
Received By rmcphers Date 2022-04-11 Time 13:16 Sent To  
Notes
2022-04-11 13:17:16REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ACCESSIBLE RESTROOM = PLEASE SHOW THE MIRROR
 DIMENSION FROM THE FLOOR TO THE BOTTOM OF THE
 "REFLECTIVE SURFACE" TO COMPLY WITH FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 06:52 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 06:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-21 Cont ID  
Sent By jleahy Date 2022-04-21 Time 16:07 Rev Time 0.00
Received By mpeterso Date 2022-04-21 Time 16:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-03-29 Cont ID  
Sent By pleduc Date 2022-03-29 Time   Rev Time 0.00
Received By pleduc Date 2022-03-29 Time 13:39 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2022-04-12 Cont ID  
Sent By fmittner Date 2022-04-12 Time 11:45 Rev Time 0.00
Received By amhamilt Date 2022-04-12 Time 11:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 08:41 Rev Time 0.00
Received By rwbrown Date 2022-06-02 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-21 Cont ID  
Sent By mpeterso Date 2022-04-21 Time 16:07 Rev Time 0.00
Received By mpeterso Date 2022-03-28 Time 12:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-15 Cont ID  
Sent By medwards Date 2022-06-15 Time 06:41 Rev Time 0.00
Received By medwards Date 2022-06-15 Time 06:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-04-11 Cont ID  
Sent By medwards Date 2022-04-11 Time 16:46 Rev Time 0.00
Received By medwards Date 2022-04-11 Time 16:46 Sent To  
Notes
2022-04-11 16:50:501) THE MECHANICAL EQUIPMENT SIZING CALCULATION STATES
 STYX ALLEY & 7TH STREET LOT 6, THERE ARE 2 STRUCTURES
 ON LOT 6. THE SUBMITTED DRAWINGS INDICATE THEY ARE FOR
 LOT 6A. PLEASE LABEL THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE CORRECT STRUCTURE ON THE LOT.
  
 2) THIS APPEARS TO BE A REVISION TO A SHELL PERMIT?
 THERE WAS NO MECHANICAL SUBMITTED FOR THE SHELL PERMIT
 19120512. PROVIDE THE ENERGY CALCULATIONS AND THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS NEW
 BUILDING. FBC 107.2.1
  
 3) THE REVISION FORM DOES NOT INCLUDE THE VALUE OF THIS
 REVISION. THERE CLEARLY IS A VALUE TO THIS MECHANICAL
 SYSTEM THAT WAS NOT INCLUDED IN THE SHELL PERMIT.
 PLEASE SHOW THE ACCURATE VALUE FOR THIS MECHANICAL
 SYSTEM.
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-07-11 Cont ID  
Sent By rwbrown Date 2022-07-11 Time 10:16 Rev Time 0.00
Received By rwbrown Date 2022-07-11 Time 10:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 08:41 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 07:52 Sent To  
Notes
2022-06-29 08:40:552ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND ? 107.3 - REQUIRED PERMITS - THE
 BACKFLOW AND INTERCEPT PERMITS ARE REQUIRED BEFORE
 ISSUANCE OF THIS PERMIT. ). YOU CAN SUBMIT AN
 APPLICATION ?TBD? (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
  
  
 WHEN YOU HAVE THE PERMIT NUMBERS, REPSOND TO THIS
 COMMENT.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-04-14 Cont ID  
Sent By jesmith Date 2022-04-14 Time 13:20 Rev Time 0.00
Received By jesmith Date 2022-04-14 Time 08:23 Sent To  
Notes
2022-04-14 13:18:53CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080535 622 7TH ST
 MASTER 19120504 LOT 7A REVISION
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 GENERAL COMMENT: DUE TO A CHANGE IN PROCESS, THE
 BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMITS ARE
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ***A) PROVIDE DIMENSIONS OF CLEARANCE AROUND A WATER
 CLOSET; SHALL BE 60 INCHES MINIMUM MEASURED
 PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES DEEP
 MINIMUM FOR WALL HUNG WATER CLOSETS AND 59 INCHES DEEP
 MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED
 PERPENDICULAR TO THE REAR WALL PER FBC ACC 604.3.1 AND
 604.8.1.1.
 ***B) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ***C) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 ?REFLECTING? SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND PER FBC ACC 603.3.
 ***D) FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
  
 2.SHOW TOE AND KNEE CLEARANCE FOR THE LAVATORY AS
 REQUIRED BY FBC ACC 306.2 AND 306.3
  
 3. A1.1A: PLUMBING FIXTURE SCHEDULE DOES NOT SHOW
 DRINKING FOUNTAIN AS A REQUIRED FIXTURE. PER WPB FBC
 107.2.1 AND, PROVIDE A NOTE STATING "IN ACCORDANCE WITH
 FBC PL 410.4, THIS RESTAURANT WILL PROVIDE DRINKING
 WATER IN A FLAT BOTTOM CONTAINER FREE OF CHARGE."
  
 4. P701/SANITARY RISER: PER FBC PL 1002.1, PROVIDE A
 WATER SEAL TRAP FOR THE MOP SINK.
  
 5. P801: REGARDING THE PLUMBING FIXTURE SCHEDULE
 COMMENT REFERRING TO ARCHITECT, OWNERSHIP OR INTERIOR
 DESIGN FOR SELECTION OF ALL FIXTURES AND ACCESSORIES,
 PER WPB FBC 107.2.1, SUBMIT MANUFACTURER"S
 SPECIFICATION/INSTALLATION MANUALS FOR ALL SCHEDULED
 PLUMBING FIXTURES AND ACCESSORIES.
  
 6. RE: P701/DETAIL 5; WATER HEATER DETAIL. DETAIL
 INDICATES CONCRETE ANCHORS FOR WALL MOUNTED WATER
 HEATER SUPPORT. A2.0B ENLARGED FLOOR PLANS INDICATE
 METAL FRAMED PARTITIONS, NOT CONCRETE WALLS. PER WPB
 FBC 107.2.1, CLARIFY AND CORRECT AS NECESSARY.
  
 7.P701/DETAIL 5 NOTES PAN DRAIN TO THE MOP SINK;
 P801/WATER HEATER SCHEDULE NOTE 3 CALLS FOR PAN DRAIN
 TO NEAREST FLOOR DRAIN. PER WPB FBC 107.2.1, PLEASE
 CLARIFY AND RECONCILE; IT IS NOTED THAT THERE IS NO
 FLOOR DRAIN ON THE PLANS.
  
 8.P701/DETAIL 5 SHOWS T&P RELIEF VALVE DISCHARGE
 INDIRECTLY TO THE MOP SINK BUT SHOWS IT DISCHARGING TO
 THE PAN DRAIN THROUGH AN AIR GAP. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND RECONCILE; IT IS NOTED THAT THERE IS
 NO FLOOR DRAIN ON THE PLANS. PLEASE NOTE THAT ANY
 DISCHARGE TO A RECEPTACLE WILL REQUIRE AN AIR GAP PER
 FBC PL 504.2.
  
 9. N/A
  
 10. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 11. GREASE INTERCEPTOR: PLEASE NOTE THAT PER FBC PL
 301.7 AND 303.2, THE INSTALLATION OF THE SCHIER GB-75
 GREASE INTERCEPTOR SHALL CONFORM TO A MINIMUM OF THE
 MANUFACTURER'S RECOMMENDATIONS. IN ACCORDANCE WITH THE
 GB-75 INSTALLATION GUIDE PAGE 8, 9 AND 10 OF 10, A
 TWO-WAY CLEANOUT IS REQUIRED ON BOTH THE INLET AND
 OUTLET SIDE OF THE GREASE INTERCEPTOR.
  
 12. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TIEDOWN OF
 GREASE INTERCEPTOR. PROVIDE DETAIL OF BURIED TANK.
 PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF
 EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE
 FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. SEE THE
 FOLLOWING:
 ***A) PLEASE NOTE THAT PER FBC PL 301.7 AND 303.2, THE
 INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR
 SHALL CONFORM TO A MINIMUM OF THE MANUFACTURER'S
 RECOMMENDATIONS.
 ***B) TO BE CLEAR, PROVIDE A DETAIL FOR THE UNDERGROUND
 INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR.
 PLEASE REFER TO THE SCHIER GB-75 INSTALLATION GUIDE
 PAGE 3, 8, 9 AND 10 OF 10 FOR DETAILS. PLEASE NOTE THE
 REFERENCE TO TIE DOWNS AND MAKE A FINAL DETERMINATION
 AS TO THE APPLICABILITY TO THIS PROJECT.
 ***C) PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF
 EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE
 FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7.
  
 13. REGARDING THE SAMPLING POINT INSTALLED UPSTREAM OF
 THE GB-75:
 ***A) IN ACCORDANCE WITH THE SCHIER SV-10 INSTALLATION
 GUIDE (SEE FBC PL 301.7 AND 303.2), THE SAMPLING POINT
 SHALL BE DOWNSTREAM OF THE INTERCEPTOR.
 ***B) PER WPB FBC 107.2.1, PLEASE SPECIFY THE SAMPLING
 POINT DEVICE TO BE INSTALLED (SCHIER PRODUCT IS SV-10)
 ***C) PLEASE NOTE THAT THE JURISDICTION ACCEPTS A
 TWO-WAY CLEANOUT FOR USE AS A SAMPLING POINT
  
 14. PER FBC PL 606.2(2), PROVIDE A SHUT-OFF VALVE ON
 THE WATER SUPPLY PIPE TO EACH SILLCOCK/HOSE BIB.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 06:52 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 06:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-11 Cont ID  
Sent By rmcphers Date 2022-04-11 Time 13:25 Rev Time 0.00
Received By rmcphers Date 2022-04-11 Time 13:25 Sent To  
Notes
2022-04-14 09:19:31SIGNATURES FOR PLUMBING: SELECTED CERTIFICATE PATH HAS
 ERRORS; NOT TIME VALID. CORRECTIONS NEEDED. JS

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-16 Cont ID  
Sent By ckimmerl Date 2022-06-16 Time 13:56 Rev Time 0.00
Received By ckimmerl Date 2022-06-16 Time 13:54 Sent To  
Notes
2022-06-16 13:55:071. PROVISO: ANY GROUND-MOUNTED MECHANICAL EQUIPMENT
 INCLUDING BUT NOT LIMITED TO AC UNITS, WATER METERS,
 BACKFLOW PREVENTERS, TRANSFORMERS, ETC. SHALL BE
 SCREENED FROM VIEW WITH LANDSCAPE HEDGES.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-07 Cont ID  
Sent By aabdalla Date 2022-04-07 Time 11:57 Rev Time 0.00
Received By ckimmerl Date 2022-04-07 Time 11:43 Sent To  
Notes
2022-04-07 11:44:401. PROVISO: PLEASE UPDATE COVER SHEET WITH MINOR
 CORRECTIONS:
 A. COMMISSIONERS: DISTRICT 1: CATHLEEN WARD
 B. RICK GREEN IS THE DEVELOPMENT SERVICES DIRECTOR
 C. CHRIS ROOG IS THE CRA EXECUTIVE DIRECTOR
  
  
 2. PROVISO: ANY GROUND-MOUNTED MECHANICAL EQUIPMENT
 INCLUDING BUT NOT LIMITED TO AC UNITS, WATER METERS,
 BACKFLOW PREVENTERS, TRANSFORMERS, ETC. SHALL BE
 SCREENED FROM VIEW WITH LANDSCAPE HEDGES.
  