| 2022-04-14 13:18:53 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1 |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 21080535 622 7TH ST |
| | MASTER 19120504 LOT 7A REVISION |
| | |
| | 1ST REVIEW |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | GENERAL COMMENT: DUE TO A CHANGE IN PROCESS, THE |
| | BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMITS ARE |
| | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| | PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN |
| | APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE |
| | A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT |
| | APPLICATION TO [email protected] . YOU WILL |
| | RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU |
| | MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE |
| | APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT |
| | YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER |
| | YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL |
| | AND I WILL CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1.PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS |
| | FOR NEW TOILET ROOM INDICATING THE FOLLOWING: |
| | ***A) PROVIDE DIMENSIONS OF CLEARANCE AROUND A WATER |
| | CLOSET; SHALL BE 60 INCHES MINIMUM MEASURED |
| | PERPENDICULAR FROM THE SIDE WALL AND 56 INCHES DEEP |
| | MINIMUM FOR WALL HUNG WATER CLOSETS AND 59 INCHES DEEP |
| | MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED |
| | PERPENDICULAR TO THE REAR WALL PER FBC ACC 604.3.1 AND |
| | 604.8.1.1. |
| | ***B) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER |
| | SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT. |
| | ***C) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | ?REFLECTING? SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND PER FBC ACC 603.3. |
| | ***D) FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| | AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| | WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| | SIDE OF THE WATER CLOSET PER FBC ACC 604.6 |
| | |
| | 2.SHOW TOE AND KNEE CLEARANCE FOR THE LAVATORY AS |
| | REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | |
| | 3. A1.1A: PLUMBING FIXTURE SCHEDULE DOES NOT SHOW |
| | DRINKING FOUNTAIN AS A REQUIRED FIXTURE. PER WPB FBC |
| | 107.2.1 AND, PROVIDE A NOTE STATING "IN ACCORDANCE WITH |
| | FBC PL 410.4, THIS RESTAURANT WILL PROVIDE DRINKING |
| | WATER IN A FLAT BOTTOM CONTAINER FREE OF CHARGE." |
| | |
| | 4. P701/SANITARY RISER: PER FBC PL 1002.1, PROVIDE A |
| | WATER SEAL TRAP FOR THE MOP SINK. |
| | |
| | 5. P801: REGARDING THE PLUMBING FIXTURE SCHEDULE |
| | COMMENT REFERRING TO ARCHITECT, OWNERSHIP OR INTERIOR |
| | DESIGN FOR SELECTION OF ALL FIXTURES AND ACCESSORIES, |
| | PER WPB FBC 107.2.1, SUBMIT MANUFACTURER"S |
| | SPECIFICATION/INSTALLATION MANUALS FOR ALL SCHEDULED |
| | PLUMBING FIXTURES AND ACCESSORIES. |
| | |
| | 6. RE: P701/DETAIL 5; WATER HEATER DETAIL. DETAIL |
| | INDICATES CONCRETE ANCHORS FOR WALL MOUNTED WATER |
| | HEATER SUPPORT. A2.0B ENLARGED FLOOR PLANS INDICATE |
| | METAL FRAMED PARTITIONS, NOT CONCRETE WALLS. PER WPB |
| | FBC 107.2.1, CLARIFY AND CORRECT AS NECESSARY. |
| | |
| | 7.P701/DETAIL 5 NOTES PAN DRAIN TO THE MOP SINK; |
| | P801/WATER HEATER SCHEDULE NOTE 3 CALLS FOR PAN DRAIN |
| | TO NEAREST FLOOR DRAIN. PER WPB FBC 107.2.1, PLEASE |
| | CLARIFY AND RECONCILE; IT IS NOTED THAT THERE IS NO |
| | FLOOR DRAIN ON THE PLANS. |
| | |
| | 8.P701/DETAIL 5 SHOWS T&P RELIEF VALVE DISCHARGE |
| | INDIRECTLY TO THE MOP SINK BUT SHOWS IT DISCHARGING TO |
| | THE PAN DRAIN THROUGH AN AIR GAP. PER WPB FBC 107.2.1, |
| | PLEASE CLARIFY AND RECONCILE; IT IS NOTED THAT THERE IS |
| | NO FLOOR DRAIN ON THE PLANS. PLEASE NOTE THAT ANY |
| | DISCHARGE TO A RECEPTACLE WILL REQUIRE AN AIR GAP PER |
| | FBC PL 504.2. |
| | |
| | 9. N/A |
| | |
| | 10. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| | BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| | 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| | STATING THE SAME. |
| | |
| | 11. GREASE INTERCEPTOR: PLEASE NOTE THAT PER FBC PL |
| | 301.7 AND 303.2, THE INSTALLATION OF THE SCHIER GB-75 |
| | GREASE INTERCEPTOR SHALL CONFORM TO A MINIMUM OF THE |
| | MANUFACTURER'S RECOMMENDATIONS. IN ACCORDANCE WITH THE |
| | GB-75 INSTALLATION GUIDE PAGE 8, 9 AND 10 OF 10, A |
| | TWO-WAY CLEANOUT IS REQUIRED ON BOTH THE INLET AND |
| | OUTLET SIDE OF THE GREASE INTERCEPTOR. |
| | |
| | 12. PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TIEDOWN OF |
| | GREASE INTERCEPTOR. PROVIDE DETAIL OF BURIED TANK. |
| | PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| | EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| | FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. SEE THE |
| | FOLLOWING: |
| | ***A) PLEASE NOTE THAT PER FBC PL 301.7 AND 303.2, THE |
| | INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR |
| | SHALL CONFORM TO A MINIMUM OF THE MANUFACTURER'S |
| | RECOMMENDATIONS. |
| | ***B) TO BE CLEAR, PROVIDE A DETAIL FOR THE UNDERGROUND |
| | INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR. |
| | PLEASE REFER TO THE SCHIER GB-75 INSTALLATION GUIDE |
| | PAGE 3, 8, 9 AND 10 OF 10 FOR DETAILS. PLEASE NOTE THE |
| | REFERENCE TO TIE DOWNS AND MAKE A FINAL DETERMINATION |
| | AS TO THE APPLICABILITY TO THIS PROJECT. |
| | ***C) PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF |
| | EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE |
| | FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. |
| | |
| | 13. REGARDING THE SAMPLING POINT INSTALLED UPSTREAM OF |
| | THE GB-75: |
| | ***A) IN ACCORDANCE WITH THE SCHIER SV-10 INSTALLATION |
| | GUIDE (SEE FBC PL 301.7 AND 303.2), THE SAMPLING POINT |
| | SHALL BE DOWNSTREAM OF THE INTERCEPTOR. |
| | ***B) PER WPB FBC 107.2.1, PLEASE SPECIFY THE SAMPLING |
| | POINT DEVICE TO BE INSTALLED (SCHIER PRODUCT IS SV-10) |
| | ***C) PLEASE NOTE THAT THE JURISDICTION ACCEPTS A |
| | TWO-WAY CLEANOUT FOR USE AS A SAMPLING POINT |
| | |
| | 14. PER FBC PL 606.2(2), PROVIDE A SHUT-OFF VALVE ON |
| | THE WATER SUPPLY PIPE TO EACH SILLCOCK/HOSE BIB. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |