Plan Review Details - Permit 21080534
Plan Review Stops For Permit 21080534
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-22 Cont ID  
Sent By rmcphers Date 2022-06-22 Time 15:23 Rev Time 0.00
Received By rmcphers Date 2022-06-22 Time 15:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By rmcphers Date 2022-03-31 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2022-03-30 Time 17:23 Sent To  
Notes
2022-03-30 17:28:09REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A6.0 - DOOR PRODUCT APPROVAL NOA 18-0129.06
 DOES NOT MEET IMPACT REQUIREMENTS ( PLEASE PROVIDE THE
 REQUIRED SHUTTER PRODUCT APPROVAL) FBC
  
 2) DRAWING A6.0 - STOREFRONT WINDOW PRODUCT APPROVAL
 NOA 17-1218.09 DOES NOT MEET IMPACT REQUIREMENTS (
 PLEASE PROVIDE THE REQUIRED SHUTTER PRODUCT APPROVAL)
 FBC
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-20 Cont ID  
Sent By rmcphers Date 2021-09-20 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2021-09-20 Time 10:30 Sent To  
Notes
2021-09-20 10:34:03REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
  
 1) DOOR OUT SWING SHOWN IN THE CORRIDOR BETWEEN THE
 BUILDINGS ON DRAWINGS A1.1, A1.0, A1.0A AND A2.0
 APPEARS TO BLOCK EGRESS PER FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 2) WALLS AROUND THE MOP SINK NEED TO COMPLY WITH FBC
 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND EXCEPT FOR
 STRUCTURAL ELEMENTS, THE MATERIALS USED IN SUCH WALLS
 SHALL BE OF A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 07:09 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 07:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-14 Cont ID  
Sent By jleahy Date 2022-04-14 Time 14:39 Rev Time 0.00
Received By jleahy Date 2022-04-14 Time 14:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 11:27 Rev Time 0.00
Received By jleahy Date 2021-09-27 Time 11:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-25 Cont ID  
Sent By pleduc Date 2021-08-25 Time   Rev Time 0.00
Received By pleduc Date 2021-08-25 Time 11:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 08:52 Rev Time 0.00
Received By rwbrown Date 2022-06-02 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-14 Cont ID  
Sent By jleahy Date 2022-04-14 Time 14:40 Rev Time 0.00
Received By jleahy Date 2022-03-18 Time 09:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-08 Cont ID  
Sent By aoliver Date 2022-03-08 Time 11:01 Rev Time 0.00
Received By aoliver Date 2022-03-08 Time 07:57 Sent To  
Notes
2022-03-08 11:02:353/8/22 LACHIVENISE ST. HILAIRE REQ TO PULL FROM REVIEW
 TO ADD MORE DOCUMENTS AO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-27 Cont ID  
Sent By jleahy Date 2021-09-27 Time 11:28 Rev Time 0.00
Received By jleahy Date 2021-08-19 Time 17:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-04-05 Cont ID  
Sent By medwards Date 2022-04-05 Time 11:13 Rev Time 0.00
Received By medwards Date 2022-04-05 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-08-30 Cont ID  
Sent By medwards Date 2021-08-30 Time 11:30 Rev Time 0.00
Received By medwards Date 2021-08-30 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-07-11 Cont ID  
Sent By rwbrown Date 2022-07-11 Time 10:14 Rev Time 0.00
Received By rwbrown Date 2022-07-11 Time 10:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-06-29 Cont ID  
Sent By rwbrown Date 2022-06-29 Time 08:51 Rev Time 0.00
Received By rwbrown Date 2022-06-29 Time 08:45 Sent To  
Notes
2022-06-29 08:51:013RD PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND ? 107.3 - REQUIRED PERMITS - THE
 BACKFLOW AND INTERCEPT PERMITS ARE REQUIRED BEFORE
 ISSUANCE OF THIS PERMIT. ). YOU CAN SUBMIT AN
 APPLICATION ?TBD? (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
  
  
 WHEN YOU HAVE THE PERMIT NUMBERS, REPSOND TO THIS
 COMMENT.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By jesmith Date 2022-03-31 Time 12:46 Rev Time 0.00
Received By jesmith Date 2022-03-29 Time 14:58 Sent To  
Notes
2022-03-31 12:42:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080534 620 7TH ST
 MASTER PERMIT 19120500 LOT 5B REVISION
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 1. NEW COMMENT: DUE TO A CHANGE IN PROCESS, THE
 BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMITS ARE
 REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE
 PRIMARY PERMIT (AS APPLICABLE). YOU CAN SUBMIT AN
 APPLICATION "TBD" (TO BE DETERMINED) IF YOU DO NOT HAVE
 A CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2.NEW COMMENT: GREASE INTERCEPTOR; PLEASE NOTE THAT PER
 FBC PL 301.7 AND 303.2, THE INSTALLATION OF THE SCHIER
 GB-75 GREASE INTERCEPTOR SHALL CONFORM TO A MINIMUM OF
 THE MANUFACTURER'S RECOMMENDATIONS. IN ACCORDANCE WITH
 THE GB-75 INSTALLATION GUIDE PAGE 8, 9 AND 10 OF 10, A
 TWO-WAY CLEANOUT IS REQUIRED ON BOTH THE INLET AND
 OUTLET SIDE OF THE GREASE INTERCEPTOR.
  
 3.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE DETAIL
 FOR TIEDOWN OF TANK. PROVIDE DETAIL OF BURIED TANK.
 PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF
 EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE
 FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7. SEE THE
 FOLLOWING:
 ***A) PLEASE NOTE THAT PER FBC PL 301.7 AND 303.2, THE
 INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR
 SHALL CONFORM TO A MINIMUM OF THE MANUFACTURER'S
 RECOMMENDATIONS.
 ***B) TO BE CLEAR, PROVIDE A DETAIL FOR THE UNDERGROUND
 INSTALLATION OF THE SCHIER GB-75 GREASE INTERCEPTOR.
 PLEASE REFER TO THE SCHIER GB-75 INSTALLATION GUIDE
 PAGE 3, 8, 9 AND 10 OF 10 FOR DETAILS. PLEASE NOTE THE
 REFERENCE TO TIE DOWNS AND MAKE A FINAL DETERMINATION
 AS TO THE APPLICABILITY TO THIS PROJECT.
 ***C) PROVIDE INFORMATION SHOWING THAT BOTTOM EDGE OF
 EXCAVATION WILL NOT ADVERSELY AFFECT OR UNDERMINE THE
 FOOTERS. SEE FBC PL 307.5 AND FBC 1803.5.7.
  
 4.NEW COMMENT: REGARDING THE SAMPLING POINT INSTALLED
 UPSTREAM OF THE GB-75;
 ***A) IN ACCORDANCE WITH THE SCHIER SV-10 INSTALLATION
 GUIDE (SEE FBC PL 301.7 AND 303.2), THE SAMPLING POINT
 SHALL BE DOWNSTREAM OF THE INTERCEPTOR.
 ***B) PER WPB FBC 107.2.1, PLEASE SPECIFY THE SAMPLING
 POINT DEVICE TO BE INSTALLED (SCHIER PRODUCT IS SV-10)
 ***C) PLEASE NOTE THAT THE JURISDICTION ACCEPTS A
 TWO-WAY CLEANOUT FOR USE AS A SAMPLING POINT
  
  
 END OF COMMENTS.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21080534 620 7TH ST
 MASTER PERMIT 19120500 LOT 5B REVISION
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-02 Cont ID  
Sent By jesmith Date 2021-09-02 Time 13:55 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 14:46 Sent To  
Notes
2021-09-02 13:56:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21080534 620 7TH ST
 MASTER PERMIT 19120500 LOT 5B REVISION
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 A.MASTER PERMIT 19120500 IS FOR THE SHELL CONSTRUCTION
 OF SIDE B ONLY WITH FUTURE TENANT IMPROVEMENT TO BE
 UNDER A SEPARATE PERMIT. HOWEVER, B AS PRESENTED IS
 INTEGRAL WITH SIDE A. THE PROVIDED ARCHITECTURAL PLANS
 INDICATE ONLY UNIT B ON LOT 5 IS UNDER CONSIDERATION.
 THE PLUMBING PLANS ADDRESS UNITS A AND B. IF THE REVIEW
 IS TO BE FOR BOTH SIDES A AND B, THEN ARCHITECTURAL
 PAGES ADDRESSING SIDE A AS WELL AS SIDE B SHALL BE
 SUBMITTED. IN ORDER TO PROPERLY ASSESS THE PROJECT,
 SIDES A AND B NEED TO BE COMBINED AND SUBMITTED AS ONE
 (1) ENTITY. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 WHEN SUBMITTING THE COMBINED SIDES AS A SINGLE ENTITY,
 PER WPB FBC 107.2.1 THE FOLLOWING SHALL BE CONSIDERED
  
 1. PROVIDE THE SQUARE FOOTAGE AND THE OCCUPANCY LOAD OF
 COMBINED SIDES A AND B. THIS IS REQUIRED TO BE ABLE TO
 DETERMINE THE MINIMUM REQUIRED FACILITIES IN FBC PC
 403.
  
 2. PER WPB FBC 107.2.1, PROVIDE A PLUMBING FIXTURE
 SCHEDULE NOTING THE REQUIRED MINIMUM TOILET FACILITIES
 AS REQUIRED BY FBC PL 403.3.
  
 3. IF A DRINKING FOUNTAIN IS REQUIRED, COMPLY WITH FBC
 ACC 211.1, WHERE DRINKING FOUNTAINS ARE PROVIDED ON AN
 EXTERIOR SITE, ON A FLOOR, OR WITHIN A SECURED AREA
 THEY SHALL BE PROVIDED IN ACCORDANCE WITH 211. PER
 211.1, NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1
 THROUGH 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 4. PER WPB FBC 107.2.1, SHOW/PROVIDE THE FOLLOWING
 INFORMATION:
 ....A)RE: 2.0A; THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2.
 ....B)MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE40 INCHES (1015 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
 ....C)FLUSH CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY
 WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN
 SIDE OF THE WATER CLOSET PER FBC ACC 604.6
 ....E)TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 ....F)THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION PER FBC ACC 604.4.
 ....G) SHOW TOE AND KNEE CLEARANCE FOR THE LAVATORIES
 AS REQUIRED BY FBC ACC 306.2 AND 306.3
  
  
 5. PER WPB FBC 107.2.1, SHOW PROVIDE WALL FINISH FOR
 THE MOP SINK SHOWING COMPLIANCE WITH FBC PL 310.3 AND
 FBC 1210.2.2. WALLS AND PARTITIONS WITHIN 2 FEET (610
 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE. PLEASE NOTE THAT FBC 1210.2.2
 STIPULATES THAT THE MATERIAL BE "HARD." THE INTENT OF
 THIS SECTION IS THAT THE SURROUNDING MATERIAL SHOULD
 NOT BE OF A TYPE THAT IS EASILY DAMAGED SUCH THAT THE
 MATERIAL COULD BECOME ABSORBENT AND THUS, NOT READILY
 CLEANABLE AND SANITIZED. PAINTED DRYWALL, EVEN WHEN
 COATED WITH HIGHLY DURABLE PAINTS SUCH AS EPOXY, DOES
 NOT MEET THE INTENT OF SECTION 1210.2.2. THE TYPICAL
 MATERIALS USED FOR THIS APPLICATION ARE CERAMIC TILE,
 FIBERGLASS REINFORCED PLASTIC (FRP) PANELS, PHENOLIC
 PANELS, LAMINATED PLASTIC PANELS, PAINTED STEEL AND
 STAINLESS STEEL.
  
 6. RE: A2.0A; ONLY ADDRESSES TYPE A UNIT. PER WPB FBC
 107.2.1, PROVIDE TYPE B DRAWING ENLARGED PLAN THAT
 PROPERLY ADDRESSES THE WORK TO BE DONE ON THE B SIDE.
  
 7. RE: P000 PLUMBING GENERAL NOTE 30; CODE REFERENCE
 FBC-P 6017.1 IS NOT VALID. REFERENCE SHOULD BE FBC-P
 607.1, 607.1.1 AND 607.1.2; TEXT SHOULD INCLUDE A
 REFERENCE TO FBC-P 424.3 REQUIRING INDIVIDUAL SHOWER
 AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED-PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016/ASME A112.1016/CSA
 B125.16 OR ASME A112.18.1/CSA B125.1 AND SHALL BE
 INSTALLED AT THE POINT OF USE. PER WPB FBC 107.2.1,
 PLEASE REVISE THE NOTE ACCORDINGLY.
  
 8. RE: P301 (AND P401) PLUMBING NOTE 8; PER WPB FBC
 107.2.1, PROVIDE SPECIFICATION AND DETAIL FOR NOTED
 FIRE BLOCKING FOR PIPES PASSING THROUGH NOTED WALLS AND
 FLOOR. (NOTED THAT STRUCTURE IS WOOD FRAMED)
  
 9. PER WPB FBC 107.2.1, PROVIDE DETAIL AND
 SPECIFICATION FOR RODENT PROOFING OF FLOOR PIPE AND
 OTHER PLUMBING PENETRATIONS THROUGH THE FLOOR. SEE FBC
 PL 301.1 THROUGH 304.4.
  
 10. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 SHOWING HOW PIPING WILL BE HUNG FROM WOODEN FLOOR
 JOISTS AND ROOF RAFTERS WITH A NOTE STATING,
 "HORIZONTAL PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH
 FBC PL TABLE 308.5."
  
 11. WATER HEATER SCHEDULE & DETAIL- PROVIDE DETAIL OF
 WATER HEATER SHOWING HEATER W/STORAGE CAPACITY, PIPING
 INCLUDING CW, HW, VALVES (INCLUDING VACUUM RELIEF VALVE
 IF APPLICABLE FBC PL 504.2) , THERMAL EXPANSION CONTROL
 DEVICE (INCLUDING SIZE), T&P DISCHARGE (INCLUDING
 TERMINATION) AND WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL
 607.3, 503.1, 504.1, 504.4, 504.4.1, 504.5, 504.6,
 504.7, 504.7.1 AND 504.7.2. RE: P701/DETAIL 5; WATER
 HEATER DETAIL. PROVIDE THERMAL EXPANSION DEVICE
 COMPLYING WITH FBC PL 607.3
 ?.A)EXPANSION TANK IS SCHEDULED WITH INSTRUCTIONS FOR
 INSTALLATION ON P801.
 ?.B)PER WPB FBC 107.2.1, PLEASE AMEND NOTE A IN THE
 EXPANSION TANK SCHEDULE TO NOTE ?EXPANSION TANK SHALL
 BE CONNECTED TO THE WATER HEATER COLD WATER SUPPLY PIPE
 AT A POINT THAT IS DOWNSTREAM OF ALL CHECK VALVES,
 PRESSURE REDUCING VALVES AND BACKFLOW PREVENTERS?,
 COMPLYING WITH FBC PL 607.3.
 ?.C) PER WPB FBC 107.2.1, SHOW LOCATION OF SCHEDULED
 EXPANSION TANK. THIS MAY EASILY BE ACCOMPLISHED BY
 SHOWING IT ON P701/DETAIL 5; WATER HEATER DETAIL.
  
 12. RE: P701/DETAIL 5; WATER HEATER DETAIL. DETAIL
 INDICATES CONCRETE ANCHORS FOR WALL MOUNTED WATER
 HEATER SUPPORT. A2.0B ENLARGED FLOOR PLANS INDICATE
 METAL FRAMED PARTITIONS, NOT CONCRETE WALLS. PER WPB
 FBC 107.2.1, CLARIFY AND CORRECT AS NECESSARY.
  
 13. P701 DETAILS INDICATE CONCRETE SLAB ON GRADE.
 ACTUAL STRUCTURE IS WOOD FRAMED JOISTS AND BEAMS. PER
 WPB FBC 107.2.1, PROVIDE DETAIL(S) FOR INTERIOR
 PENETRATIONS THAT REFLECT THE ACTUAL CONSTRUCTION.
 PLEASE NOTE, ECOS NOTED ON P301 AND P601 ARE SHOWN AS
 FLOOR CLEANOUTS, NOT WALL CLEANOUTS AS INDICATED FOR
 INTERIOR CLEANOUT DETAIL. PER WPB FBC 107.2.1, PROVIDE
 A DETAIL FOR ECO AND INCLUDE IN PLUMBING SCHEDULE.
  
 14.RE: A1.1. FULL LOT PLAN IS INDICATED AS LOT 5.
 PARTIAL LOT 6 DOES NOT ADDRESS THE DETAILS THAT LOT 5
 DOES. PER WPB FBC 107.2, ADD TO LOT 5, LOT 6 SIMILAR.
  
 15. A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTER. PER WPB FBC 107.2.1, PROVIDE WITH PERMIT
 APPLICATION, ON THE PLANS, CALCULATIONS FOR SIZING OF
 THE GREASE INTERCEPTOR AND A DETAIL FOR TIEDOWN OF
 TANK. PROVIDE DETAIL OF BURIED TANK. PROVIDE
 INFORMATION SHOWING THAT BOTTOM EDGE OF EXCAVATION WILL
 NOT ADVERSELY AFFECT OR UNDERMINE THE FOOTERS. SEE FBC
 PL 307.5 AND FBC 1803.5.7.
  
  
  
 END OF COMMENTS.
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A
 RESPONSE NARRATIVE ADDRESSING THE GAS/PLUMBING COMMENTS
 FROM THE PRIOR REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21080534 620 7TH ST
 MASTER PERMIT 19120500 LOT 5B REVISION

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 07:09 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 07:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-31 Cont ID  
Sent By rmcphers Date 2022-03-31 Time 07:54 Rev Time 0.00
Received By rmcphers Date 2022-03-31 Time 07:54 Sent To  
Notes
2022-03-31 10:16:18SIGNATURES FOR PLUMBING: SELECTED CERTIFICATE HAS
 ERRORS; NOT TIME VALID. CORRECTIONS NEEDED. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-30 Cont ID  
Sent By medwards Date 2021-08-30 Time 11:37 Rev Time 0.00
Received By medwards Date 2021-08-30 Time 11:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-06-16 Cont ID  
Sent By ckimmerl Date 2022-06-16 Time 13:50 Rev Time 0.00
Received By ckimmerl Date 2022-06-16 Time 13:49 Sent To  
Notes
2022-06-16 13:50:01PROVISO: ANY OUTDOOR MECHANICAL EQUIPMENT, INCLUDING
 BUT NOT LIMITED TO TRANSFORMERS, AC UNITS, ETC. SHALL
 BE SCREENED FROM VIEW WITH LANDSCAPING HEDGES.

Review Stop Z ZONING
Rev No 2 Status P Date 2022-03-25 Cont ID  
Sent By ckimmerl Date 2022-03-25 Time 12:10 Rev Time 0.00
Received By ckimmerl Date 2022-03-25 Time 12:07 Sent To  
Notes
2022-03-25 12:07:01PROVISO: ANY OUTDOOR MECHANICAL EQUIPMENT, INCLUDING
 BUT NOT LIMITED TO TRANSFORMERS, AC UNITS, ETC. SHALL
 BE SCREENED FROM VIEW WITH LANDSCAPING HEDGES.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-03 Cont ID  
Sent By aaponte Date 2021-09-03 Time 10:40 Rev Time 0.00
Received By ckimmerl Date 2021-09-03 Time 10:40 Sent To  
Notes
2021-09-03 10:27:47PROVISO: ANY OUTDOOR MECHANICAL EQUIPMENT, INCLUDING
 BUT NOT LIMITED TO TRANSFORMERS, AC UNITS, ETC. SHALL
 BE SCREENED FROM VIEW WITH LANDSCAPING HEDGES.