| 2021-09-17 09:44:47 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21080533 |
| | 9/17/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE IDENTIFY THE PROPOSED USES OF THE SHELL |
| | SPACES- SECTION 107.2.1 WPB. |
| | |
| | 2) SHEET P301: PLEASE NOTE THAT INSTALLATION OF THE |
| | GREASE INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT AND |
| | WILL REQUIRE A SEPARATE PRIMARY PERMIT APPLICATION AND |
| | PLAN SUBMITTALS- SECTION 105.1 & 107.2.1 WPB. FOR THE |
| | PURPOSES OF THIS REVIEW, AND IN ACCORDANCE WITH |
| | SECTIONS 1003.3.1- 1003.3.4 FBC P PLEASE PROVIDE: |
| | A) INTERCEPTOR SIZING CALCULATIONS. |
| | C) THE LOCATION OF THE SAMPLING PORT AND PROVIDE AN |
| | INSTALLATION DETAIL. |
| | D) APPROVED TRAFFIC LID SPECIFICATIONS TO PROTECT THE |
| | INTERCEPTOR, SAMPLING PORT ACCESS, AND CLEANOUT ACCESS |
| | FROM VEHICLE DAMAGE. |
| | |
| | 3) P301 & P401: PLEASE PROVIDE THE CIVIL PLANS FOR |
| | WATER SERVICE AND SANITARY SEWER CONTINUATIONS AS |
| | REFERENCED IN THE NOTES- SECTION 107.2.1 WPB. |
| | |
| | 4) P301: PLEASE NOTE THAT INDIVIDUAL SEPARATE PERMITS |
| | ARE REQUIRED FOR INSTALLATION OF THE POTABLE WATER |
| | SERVICE BACKFLOW PREVENTER, AND THE IRRIGATION SYSTEM |
| | BACKFLOW PREVENTER. A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN SEPARATE PERMITS FOR INSTALLATION OF THE |
| | DEVICES IN ACCORDANCE WITH SECTION 105.1WPB AND SEC. |
| | 90-33 WPB CODE OF ORDINANCES. THE DEVICES SHALL BE |
| | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | 5) P401 & P601: INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDED TO THE LAVATORIES- SECTION 419.5 FBC P. |
| | |
| | 6) P401 & P401: REFER TO TABLE C404.5.1 FBC EC- THE |
| | MAXIMUM PIPING LENGTH OF 2 FT. FROM THE HEATED WATER |
| | SOURCE TO THE LAVATORIES IS EXCEEDED WHICH WILL REQUIRE |
| | INSTALLATION OF A RECIRCULATION PUMP OR POINT OF USE |
| | WATER HEATERS AT THE LAVS. |
| | |
| | 7) A2.0A: PLEASE SEE THE FBC ACC CODE SECTIONS BELOW |
| | AND REVISE THE DRAWINGS ACCORDINGLY. |
| | |
| | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | WATER CLOSETS- SECTION 604.3. |
| | |
| | B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | |
| | C) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | LAVATORIES- SECTION 606.2. |
| | |
| | D) TURNING SPACE DIAMETERS- SECTION 304.3. |
| | |
| | E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| | FIGURES 604.5.1 & 604.5.2. THE REAR GRAB BAR POSITION |
| | SHALL BE DEPICTED IN COMPLIANCE WITH FIGURE 604.5.2. |
| | |
| | F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - |
| | SECTION 604.6. |
| | |
| | G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| | FIGURE 604.7. |
| | |
| | H) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| | THE REFLECTIVE SURFACES- SECTION 603.3 |
| | |
| | I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | |
| | 7) A2.0A: DETAIL 9 SHOWS THE MOP SINK WALL SURROUND TO |
| | BE PAINTED DRYWALL WHICH IS NOT IN COMPLIANCE WITH |
| | SECTION 1210.2.2 FBC P. |
| | |
| | 8) P701: REVISE THE WATER HEATER DETAIL TO INCLUDE THE |
| | LOCATION OF THE REQUIRED THERMAL EXPANSION TANK- |
| | SECTION 607.3 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |