Plan Review Details - Permit 21080460
Plan Review Stops For Permit 21080460
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-01 Cont ID  
Sent By dbattles Date 2022-06-01 Time 16:34 Rev Time 0.00
Received By dbattles Date 2022-06-01 Time 16:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-27 Cont ID  
Sent By jgomez Date 2022-01-27 Time 16:47 Rev Time 0.00
Received By jgomez Date 2022-01-27 Time 16:47 Sent To  
Notes
2022-01-27 16:49:23RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080460
  
 ORIGINAL COMMENT:
 (1)- THIS BUILDING WAS FLAGGED AS AN UNSAFE BUILDING.
 ALSO, THERE IS ALSO A RED-TAG FOR FULL GUT REMODEL
 WITHOUT PERMITS. NEED TO PROVIDE AN ENGINEERING
 ANALYSIS ESTABLISHING THE STRUCTURAL ADEQUACY OF THE
 ALTERED BUILDING AND PROVIDE COMPLETE SET OF PLANS
 SHOWING ALL THE SCOPE OF WORK. PROVIDE COMPLETE SET OF
 PLANS SHOWING ALL THE STRUCTURAL DETAILS AND
 SPECIFICATIONS. COMPLETE PLANS WITH ALL ROOMS
 DIMENSIONS, ETC.
 PLANS NEED TO BE SIGNED AND SEALED BY THE REGISTERED
 DESIGN PROFESSIONAL AS REQUIRED BY SEC. 907
 FBC-EXISTING BUILDING.
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 907 FBC-EXISTING BUILDING. SEC. 901.2 FBC-EXISTING
 BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 RESPONSE:
 (1)(A)WALL SECTION DETAIL 4/A-1 ON SHEET A-0 SUBMITTED
 NEEDS TO BE REVISED:
 1-WALL SECTION SHOWS ONLY ONE TOP PLATE. THIS IS AN
 EXTERIOR BEARING WALL. TYPICALLY, WOOD FRAME BEARING
 WALLS HAVE DOUBLE TOP PLATE. ENGINEER TO REVISE DETAIL
 OR PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING WHY
 ONLY ONE TOP PLATE IS ADEQUATE. SEC. R301.1
 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2-WALL SECTION DOESN'T SHOW THE LOAD PATH SHOWING HOW
 THE LOADS ARE TRANSFERED FROM THE ROOF TO THE
 FOUNDATION TO SHOW COMPLIANCE WITH FBC-RESIDENTIAL
 (2020). ENGINEER FAILED TO SPECIFY THE ROOF TO WALL
 HURRICANE CONNECTION, 2X4 STUDS TOP AND BOTTOM
 HURRICANE CONNECTIONS AND 2X4 STUDS SPACING.
 SEC. R601.2 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 3- BASED ON ENGINEER'S STRUCTURAL INSPECTION REPORT
 SUBMITTED, THERE ARE NO "EXISTING WOOD TRUSSES" IN THIS
 HOUSE. PHOTOS SUBMITTED SHOW CONVENTIONAL ROOF JOISTS
 AND ROOF RIDGE CONSTRUCTION. REVISE DETAIL AS REQUIRED
 TO MATCH ACTUAL CONDITIONS. AND, ENGINEER TO PROVIDE
 HURRICANE CONNECTION OF ROOF JOIST TO ROOF RIDGE. SEC.
 R601.2 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 (1)(B)ENGINEER'S STRUCTURAL REPORT STATES ON THE FRONT
 PAGE CONCLUSIONS& RECOMMENDATIONS THAT THE HOME DOESN'T
 HAVE ANY STRUCTURAL DEFICIENCIES AND THE HOME IS
 SUITABLE FOR ITS INTENDED OCCUPANCY. THE PHOTOS OF THE
 EXTERIOR WALL AND THE ROOF SHOWN ON THE SAME REPORT
 DON'T SHOW ANY HURRICANE STRUCTURAL CONNECTIONS BETWEEN
 THE STRUCTURAL FRAMING MEMBERS SHOWING THE LOAD PATH.
 ALSO, THE EXTERIOR WALL PHOTO SHOWS NO BASE PLATE AT
 THE BOTTOM OF THE WALL BEARING WOOD STUDS. ENGINEER OF
 RECORD TO CLARIFY AND PROVIDE COMPLETE ANALYSIS SHOWING
 HOW THIS STRUCTURE IS STRUCTURALLY SOUND TO RESIST ALL
 LOADS, INCLUDING WINDLOADS. SEC. R301.2.1
 FBC-RESIDENTIAL AND SEC. 107.2.1.2 CITY AMENDMENTS.
  
 (1)(C)DELETE FASTENING SCHEDULE TABLE R602.3(1) SOWN ON
 SHEET A-0. THIS TABLE NO LONGER EXIST ON CURRENT CODE
 FBC-RESIDENTIAL(2020).
  
  
 NOTE:
 BASED ON PHOTOS SHOWN ON THE ENGINEER'S STRUCTURAL
 INSPECTION REPORT SUBMITTED, THE EXTERIOR WALL DOESN'T
 HAVE STRUCTURAL ANY STRAPS AND THERE IS NO BOTTOM
 PLATE. CONNECTIONS WILL NEED TO BE INSPECTED ONCE
 ENGINEER OF RECORD CLARIFIES CONNECTIONS
 AND PERMIT IS ISSUED.
 SAME COMMENT APPLIES TO ROOF JOISTS TO ROOF RIDGE
 CONNECTIONS.
  
 (2)- OK.
  
 ORIGINAL COMMENT:
 (3)- DESIGN PROFESSIONAL OF RECORD TO SPECIFY ROOF
 SHEATHING NAIL TYPE, SIZE AND SPACING AS REQUIRED BY
 SEC. R803.2 FBC-RESIDENTIAL.
 NOTE: SPECIFICATIONS SUBMITTED ARE INCORRECT.
  
 RESPONSE:
 DESIGN PROFESSIONAL TO REVISE SPECIFICATIONS ON SHEET
 A-0.
 REVISE ROOF SHEATHING NAILING TYPE, SIZE AND SPACING.
 NEED TO USE RING SHANK NAILS AND ROOF SHEATHING NEEDS
 TO BE NAILED WITH AT 4 INCHES O.C. IN THE FIELD AND
 EDGES AS REQUIRED BY SEC. R803.2.3.1 AND TABLE
 R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: REVISE SPECIFICATIONS ON ALL PLANS AND WALL
 SECTIONS TO AVOID CONFLICTS/DELAYS.
  
 ORIGINAL COMMENT:
 (4)- WINDOW REPLACEMENT: SPECIFY SIZE AND TYPE OF
 EXISTING WINDOW AND SIZE AND TYPE OF PROPOSED WINDOWS
 TO VERIFY COMPLIANCE WITH THE BEDROOM EGRESS
 REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING.
  
 RESPONSE:
 NONE OF THE BEDROOM WINDOWS SHOWN ON SHEET A-0 COMPLY
 WITH THE EMERGENCY ESCAPE WINDOW REQUIREMENTS. EACH
 BEDROOM NEEDS TO HAVE AT LEAST ONE WINDOW OR ESCAPE
 OPENING COMPLYING WITH THIS CODE SECTION. REVISE AS
 REQUIRED.
 NOTE: ORIGINAL HOUSE HAD ONLY ONE BEDROOM. THIS HOUSE
 WAS GUTTED AND LAYOUT IS NEW. BEDROOM WINDOWS NEED TO
 COMPLY. LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING
 BUILDING. SEC. 907 FBC-EXISTING BUILDING. SEC. 901.2
 FBC-EXISTING BUILDING. SEC. 801.3 FBC-EXISTING
 BUILDING. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
  
 (5)- OK.
 (6)- OK.
 (7)- OK.
  
 ORIGINAL COMMENT:
 (8)- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COPY OF SIGNED CONTRACTS INCLUDING DESIGN
 PROFESSIONAL FEES.
  
 RESPONSE:
 TOTAL VALUE OF $23,200 IS TOO LOW FOR ALL THE SCOPE OF
 WORK SHOWN ON PLANS. REVISE VALUE TO REFLECT ACTUAL
 INDUSTRY COSTS FOR ALL LABOR, MATERIALS AND DESIGN
 PROFESSIONAL FEES. OTHERWISE, VALUATION WILL BE
 ESTIMATED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By jgomez Date 2021-10-27 Time 14:09 Rev Time 0.00
Received By jgomez Date 2021-10-27 Time 11:04 Sent To  
Notes
2021-10-27 14:10:13RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21080460
  
 (1)- THIS BUILDING WAS FLAGGED AS AN UNSAFE BUILDING.
 ALSO, THERE IS ALSO A RED-TAG FOR FULL GUT REMODEL
 WITHOUT PERMITS. NEED TO PROVIDE AN ENGINEERING
 ANALYSIS ESTABLISHING THE STRUCTURAL ADEQUACY OF THE
 ALTERED BUILDING AND PROVIDE COMPLETE SET OF PLANS
 SHOWING ALL THE SCOPE OF WORK. PROVIDE COMPLETE SET OF
 PLANS SHOWING ALL THE STRUCTURAL DETAILS AND
 SPECIFICATIONS. COMPLETE PLANS WITH ALL ROOMS
 DIMENSIONS, ETC.
 PLANS NEED TO BE SIGNED AND SEALED BY THE REGISTERED
 DESIGN PROFESSIONAL AS REQUIRED BY SEC. 907
 FBC-EXISTING BUILDING.
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 907 FBC-EXISTING BUILDING. SEC. 901.2 FBC-EXISTING
 BUILDING. SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 (2)- ROOFING WORK:
 (A) NEED SEPARATE ROOFING SUB-PERMIT APPLICATION. SEC.
 105.1 CITY AMENDMENTS.
  
 (B) FLAT ROOF NOA 16-1206.02 SUBMITTED: SELECTED SYSTEM
 ON PAGE 17 OF 18 DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES. SEC. R301.2.1 FBC-RESIDENTIAL. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
  
 (C)PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH
 THE NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001
  
 (3)- DESIGN PROFESSIONAL OF RECORD TO SPECIFY ROOF
 SHEATHING NAIL TYPE, SIZE AND SPACING AS REQUIRED BY
 SEC. R803.2 FBC-RESIDENTIAL.
 NOTE: SPECIFICATIONS SUBMITTED ARE INCORRECT.
  
 (4)- WINDOW REPLACEMENT: SPECIFY SIZE AND TYPE OF
 EXISTING WINDOW AND SIZE AND TYPE OF PROPOSED WINDOWS
 TO VERIFY COMPLIANCE WITH THE BEDROOM EGRESS
 REQUIREMENTS OF SEC. 702.5 FBC-EXISTING BUILDING.
  
 (5)-PROVIDE ALL THE WIND DESIGN CRITERIA AS REQUIRED BY
 SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE ULTIMATE AND
 NOMINAL WIND LOAD, BUILDING EXPOSURE, BUILDING MEAN
 ROOF HEIGHT. ALSO, SPECIFY THE COMPONENTS AND CLADDING
 DESIGN PRESSURES FOR DOORS AND WINDOWS.
 NOTE: INFORMATION SUBMITTED IS INCORRECT.
  
 (6)- SHUTTERS PRODUCT APPROVAL SUBMITTED: NEED TO
 PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 (7)- PRODUCT APPROVALS: DESIGNER OF RECORD TO REVIEW
 AND APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL L
 PRODUCT APPROVALS SUBMITTED AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 (8)- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS OR
 PROVIDE COPY OF SIGNED CONTRACTS INCLUDING DESIGN
 PROFESSIONAL FEES.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-04-27 Cont ID  
Sent By mpeterso Date 2022-04-27 Time 08:38 Rev Time 0.00
Received By mpeterso Date 2022-04-27 Time 08:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-22 Cont ID  
Sent By fgiaquin Date 2022-01-22 Time 19:23 Rev Time 0.00
Received By fgiaquin Date 2022-01-22 Time 18:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-26 Cont ID  
Sent By jleahy Date 2021-10-26 Time 12:43 Rev Time 0.00
Received By jleahy Date 2021-10-26 Time 12:35 Sent To  
Notes
2021-10-26 12:45:10ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WOR SHOWN FOR FULL REMODEL AS STATED IN
 PAPER WORK.
  
 PLEASE SHOW ALLNEW ELECTRICAL WORK DONE ON PREMISES.
2021-10-25 16:18:57FBC 105.1 FULL GUT REMODEL WITHOUT PERMITS 4X FEE RED
 TAG STOP WORK ORDER ISSUED.
 ROOF, WINDOWS, DOORS, ELECTRICAL, PLUMBING, MECHANICAL,
 BUILDING.
 SEE FRANK GIAQUINTO'S REDTAG.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-01 Cont ID  
Sent By dbattles Date 2022-06-01 Time 16:34 Rev Time 0.00
Received By dbattles Date 2022-04-11 Time 06:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-27 Cont ID  
Sent By jgomez Date 2022-01-27 Time 16:58 Rev Time 0.00
Received By jgomez Date 2022-01-03 Time 13:59 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-27 Cont ID  
Sent By jgomez Date 2021-10-27 Time 14:16 Rev Time 0.00
Received By jgomez Date 2021-09-07 Time 12:11 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-04-20 Cont ID  
Sent By hmoser Date 2022-04-20 Time 14:13 Rev Time 0.00
Received By hmoser Date 2022-04-20 Time 14:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-01-05 Cont ID  
Sent By medwards Date 2022-01-05 Time 07:29 Rev Time 0.00
Received By medwards Date 2022-01-05 Time 07:29 Sent To  
Notes
2022-01-05 07:31:31PLEASE RESPOND TO ST CYCLE COMMENTS BELOW.
  
 PLEASE PROVIDE THE ENERGY CALCULATIONS.
 PLEASE PROVIDE A MECHANICAL DRAWING SHOWING A CODE
 COMPLIANT INSTALLATION INCLUDING THE SPECS. FOR THE
 MECHANICAL SYSTEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-26 Cont ID  
Sent By medwards Date 2021-10-26 Time 07:41 Rev Time 0.00
Received By medwards Date 2021-10-26 Time 07:36 Sent To  
Notes
2021-10-26 07:41:12THERE IS NO MECHANICAL SCOPE OF WORK OR MECHANICAL
 DRAWINGS SUBMITTED. NOTE IN PROJECT STATES THAT A NEW
 MECHANICAL SYSTEM WAS INSTALLED WITHOUT PERMITS. PLEASE
 SUBMIT THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND A MECHANICAL DRAWING
 SHOWING THE MECHANICAL SYSTEM AND DUCT WORK ALONG WITH
 THE CONDENSING UNIT LOCATION AND THE APPLIANCE TIE DOWN
 DOCUMENTATION. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
2021-10-25 16:19:15FBC 105.1 FULL GUT REMODEL WITHOUT PERMITS 4X FEE RED
 TAG STOP WORK ORDER ISSUED.
 ROOF, WINDOWS, DOORS, ELECTRICAL, PLUMBING, MECHANICAL,
 BUILDING.
 SEE FRANK GIAQUINTO'S REDTAG.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-04 Cont ID  
Sent By lcrespo Date 2022-01-04 Time 09:00 Rev Time 0.00
Received By lcrespo Date 2022-01-04 Time 08:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-10-26 Cont ID  
Sent By lcrespo Date 2021-10-26 Time 06:53 Rev Time 0.00
Received By lcrespo Date 2021-10-26 Time 06:44 Sent To  
Notes
2021-10-25 16:19:23FBC 105.1 FULL GUT REMODEL WITHOUT PERMITS 4X FEE RED
 TAG STOP WORK ORDER ISSUED.
 ROOF, WINDOWS, DOORS, ELECTRICAL, PLUMBING, MECHANICAL,
 BUILDING.
 SEE FRANK GIAQUINTO'S REDTAG.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By jgomez Date 2022-01-27 Time 16:50 Rev Time 0.00
Received By jgomez Date 2022-01-27 Time 16:50 Sent To  
Notes
2022-01-27 16:55:19ROOFING REVIEW:
  
 1) GAF FLAT ROOF NOA 16-1206.02.
  
 2) GAF SHINGLES NOA 18-0123.06
  
 3) UNDERLAYMENT: 2 LAYERS OF 30# FELT.
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By jgomez Date 2021-10-27 Time 14:14 Rev Time 0.00
Received By jgomez Date 2021-10-27 Time 14:14 Sent To  
Notes
2021-10-27 14:16:09ROOFING REVIEW:
  
 1- ROOFING WORK:
 A) NEED SEPARATE ROOFING SUB-PERMIT APPLICATION. SEC.
 105.1 CITY AMENDMENTS.
  
 B) FLAT ROOF NOA 16-1206.02 SUBMITTED: SELECTED SYSTEM
 ON PAGE 17 OF 18 DOESN'T MEET THE DESIGN PRESSURES FOR
 ALL ROOF ZONES. SEC. R301.2.1 FBC-RESIDENTIAL. NEED TO
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA.
  
 C)PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE
 NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001
  
 2- PRODUCT APPROVALS: DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITING (NOT SIGNING AND SEALING) ALL L
 PRODUCT APPROVALS SUBMITTED AS REQUIRED BY SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-01 Cont ID  
Sent By dbattles Date 2022-06-01 Time 16:34 Rev Time 0.00
Received By dbattles Date 2022-06-01 Time 16:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By jgomez Date 2022-01-27 Time 16:56 Rev Time 0.00
Received By jgomez Date 2022-01-27 Time 16:55 Sent To  
Notes
2022-01-27 16:58:28DRAWINGS AND STRUCTURAL REPORT HAVE ENGINEER'S VALID
 DIGITAL SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-19 Cont ID  
Sent By mpeterso Date 2021-10-19 Time 12:18 Rev Time 0.00
Received By mpeterso Date 2021-10-19 Time 12:17 Sent To  
Notes
2021-10-19 12:19:00PLANS ANSD DRAWINGS BY OWNER SIGNATURE NOT REQUIRED