Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-26 Cont ID  
Sent By jwitmer Date 2021-10-26 Time 13:32 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 13:20 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 13:20:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21080420
 ADD: 600 OKEECHOBEE BLVD.
 CONT: AWNINGS OF HOLLYWOOD, INC.
 TEL: 954-963-7717
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. SEPT. 01/2021
 ACTION: DENIED
 1) THE SITE PLAN AOH1 DOES NOT INDICATE WHERE THE
 RETRACTABLE ROOF SYSTEM IS TO BE INSTALLED. THE PERMIT
 APPLICATION STATES AT THE MANOR RESTAURANT NOT MARKED
 ON THE PLAN. IT IS NOT CLEAR AS IF THE RETRACTABLE ROOF
 SYSTEM IS OVER THE FIRE PIT AREA OR WHERE THE FABRIC
 CANOPY OVER THE BAR TERRACE. SHEET AOH12 SHOWS WHAT
 APPEARS TO BE THE OUTSIDE BAR AREA BUT THE INTERIOR OF
 THE BUILDING IS NOT IDENTIFIED THE LAYOUT LOOKS
 BACKWARDS? 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) SHEET AOH13 IN THE LEFT HAND CORNER SHOWS 2 FOOTINGS
 ONE 2FEET WIDE THE OTHER 2FEET 6 INCHES WIDE JUST TO
 THE RIGHT DETAIL B1-2 INDICATING AN UPPER AND LOWER MAT
 OF STEEL RE-BAR, THE SIZE NOR SPACING IS GIVEN.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET AOH12 SHOWS F1 & F2 FOOTINGS WITH THE COLUMNS
 OFF CENTER PLEASE PROVIDE PLEASE INDICATE HOW CLOSE TO
 THE EDGE OF THE CONCRETE FOOTING THE ? INCH X 4 INCH
 REDHEAD TRUBOLTS WEDGE ANCHORS ARE TO BE INSTALLED,
 CONCERNED WITH SHEERING OF THE CONCRETE BEING TO CLOSE
 TO THE EDGE. 107.2.1.2. PLEASE PROVIDE MANUFACTURES
 SPEC.
  
 4) COMPLIED SHEET AOH16. SHEET AOH14 SHOW THE FABRIC ON
 THE RETRACTABLE SYSTEM AS FERRARI V2 FABRIC. PLEASE
 PROVIDE COMPLIANCE WITH THE 2020 FBC-BUILDING CODE
 SECTION 3105.3.4.1. FABRIC COVERED FRAMES SHALL MEET
 THE FLAME PROPAGATION PERFORMANCE CRITERIA OF NFPA 701
 OR HAVE A FLAME SPREAD INDEX NOT GREATER THAN 25 WHEN
 TESTED IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
 5) SHEET AOH8 SHOWS AS DOES OTHER SHEETS BOLTED
 CONNECTIONS, PLEASE SHOW COMPLIANCE WITH WELDED OR
 BOLTED CONNECTIONS
 THIS BUILDING CONTAINS EITHER BOLTED AND OR WELDED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD
 AT 561-805-6666.
  
 6) CALCULATIONS- DESIGN WIND LOADING CANOPY PAGE 2/32
 THE V= 45MPH. PLEASE PROVIDE HOW COMPLIANCE IS MET FOR
 SECTION 3105.4 DESIGN. IT WOULD APPEAR THAT THE 45MPH
 DOES NOT MEET ANY OF THE WIND DESIGN CRITERIA.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-19 Cont ID  
Sent By pleduc Date 2021-10-19 Time   Rev Time 0.00
Received By pleduc Date 2021-10-18 Time 14:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-08-12 Cont ID  
Sent By pleduc Date 2021-08-12 Time   Rev Time 0.00
Received By pleduc Date 2021-08-12 Time 16:03 Sent To  
Notes
2021-08-12 16:14:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS NO INDICATION OF WHAT THE PROPOSED USE OF
 THE PROPOSED CANOPY IS FOR.
  
 PLEASE PROVIDE A DETAILED NARRATIVE OF WHAT THIS CANOPY
 WILL BE USED FOR.
  
  
 1A) THE SITE PLAN INDICATES THAT THE PROPOSED CANOPY IS
 LOCATED DIRECTLY OUTSIDE EXIT DOORS FROM THE HOTEL.
  
 BASED ON # 1 WHAT IS THE PROPOSED FLOOR PLAN UNDER THE
 CANOPY THAT ENSURES A CLEAR EXIT PATH.
  
 PROVIDE A DETAILED LIFE SAFETY PLAN, INCLUDING THE
 OCCUPANY LOEAD, EXIT TRAVEL PATHS AND
 EQUIPMENT/TABLE/SEATING PLAN.
  
  
 1B) BASED ON # 1 & 2 ABOVE, WHAT IS THE PROPOSED
 ELECTIRCAL PLAN, LIGHTING, EMERGENCY LIGHTING, EXIT
 SIGNAGE, ETC.
  
 PLEASE PROVIDE ELECTRICAL DETAILS INCLUDING HOW THE
 CANOPY BE OPENED/CLOSED/OPERATE
  
  
 2) THE COVER SHEET INDICATES THE 6TH ED OF THE FFPC
 WITH 2015 LSC. THE CURRENT ED IS THE 7TH WITH 2018 LSC.
  
 PLEASE REVIE, CORRECT AND ENSURE COMPLIANCE.
  
  
  
 3) THERE IS AN INDICATION OF FIRE SPRINKLER TO BE
 SUBMITTED.
  
 ALL FS WORK INCLUDING DEMO SHALL BE SUBMITTED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE THIS ADDITIONAL NOTE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-10-26 Time 13:34 Rev Time 0.00
Received By aoliver Date 2021-10-15 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-22 Cont ID  
Sent By lmarchan Date 2021-09-22 Time 09:41 Rev Time 0.00
Received By lmarchan Date 2021-08-11 Time 15:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 15:59 Rev Time 0.00
Received By mpeterso Date 2021-10-25 Time 15:59 Sent To  
Notes
2021-10-25 16:00:43ENGINEERS DIGITAL SIGNATURE AUTHORIZED BY IDENT TRUST
 GLOBAL

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-09-01 Cont ID  
Sent By jwitmer Date 2021-09-01 Time 13:45 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-09-01 13:45:34THE DIGITAL SIGNATURE FOR THE PLANS & CALCULATIONS DOES
 NOT SHOW THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY.
 61G15023.004(2) (2) A PROFESSIONAL ENGINEER UTILIZING A
 DIGITAL SIGNATURE TO ELECTRONICALLY SIGN AND SEAL
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS SHALL HAVE THEIR IDENTITY AUTHENTICATED BY A
 CERTIFICATION AUTHORITY AND SHALL ASSURE THAT THE
 DIGITAL SIGNATURE IS:
 (A) UNIQUE TO THE PERSON USING IT;
 (B) CAPABLE OF VERIFICATION;
 (C) UNDER THE SOLE CONTROL OF THE PERSON USING IT; AND,
 (D) LINKED TO A DOCUMENT IN SUCH A MANNER THAT THE
 DIGITAL SIGNATURE AND CORRESPONDINGLY THE DOCUMENT IS
 INVALIDATED IF ANY DATA IN THE DOCUMENT IS CHANGED.
  
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-09-21 Cont ID  
Sent By eshneide Date 2021-09-21 Time 17:21 Rev Time 0.25
Received By eschneid Date 2021-09-21 Time 17:21 Sent To  
Notes
***NONE***