| 2021-08-31 14:32:37 | 08/31/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET G-001, SOME HEIGHTS FOR ACCESSIBILITY NEED |
| | TO BE ADJUSTED FOR THE TYPICAL MOUNTING HEIGHTS; |
| | |
| | A. THE GRAB BAR ON THE BACK THE SIX INCHES, NOT |
| | REQUIRED AS THE TOILET MAY BE ONE FOOT FOUR INCHES TO |
| | ONE FOOT SIX INCHES PER THE 20230 FBC SEC. 604.2 |
| | LOCATION. |
| | |
| | B. THE GRAB BAR FROM THE SIDE FROM THE BACK CALLS FOR |
| | 12 INCHES PER THE 2020 FBC SEC. 604.5.1 SIDE WALL. |
| | |
| | C. GRAB BAR FOR THE SIDEWALL IS INSTALLED IN A VERTICAL |
| | POSITION AND SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION PER THE 2020 FBC ACC SEC. 609.4. |
| | |
| | D. THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE 40 |
| | INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. |
| | 603.3. |
| | |
| | 2. ON SHEET A100, THERE SEEMS TO BE A SINK; IS IT A |
| | BREAK ROOM? IF SO, CAN YOU PLEASE LABEL IT AND SHOW THE |
| | DETAIL AND LABEL IT AS WELL PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. ON SHEET A101, THERE SEEMS TO BE A SINK; IS IT A |
| | BREAK ROOM? IF SO, CAN YOU PLEASE LABEL IT AND SHOW THE |
| | DETAIL AND LABEL IT AS WELL PER THE WPB AMENDMENTS TO |
| | THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. ON SHEET A400; |
| | |
| | A. ON DETAIL 1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE AND DIMENSIONS IN FROM OF THE SINK PER THE 2020 |
| | FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | B. ON DETAIL 2, WOULD YOU PLEASE SHOW THE CLEAR FLOOR |
| | SPACE AND DIMENSIONS OF THE SINK PER THE 2020 FBC ACC |
| | SEC. 606.2. 2 CLEAR FLOOR SPACE. |
| | |
| | C. ON DETAIL 4, IT LOOKS LIKE THIS RESTROOM IS AN |
| | ACCESSIBLE RESTROOM. IF SO WOULD YOU, PLEASE LABEL AND |
| | SHOW THE CLEAR FLOOR SPACE FOR THE LABORATORY PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | D. ON DETAIL 10, THE GRAB BAR SHALL BE A MINIMUM OF 42 |
| | INCHES AND NOT SHOWN. WOULD YOU PLEASE SHOW PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | E. ON THAT SAME DETAIL, IT SHOWS THE CENTER GRAB BARS, |
| | AND THEY SHALL BE MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE PER THE 2017 FBC ACC SEC. 609.4. |
| | |
| | F. ON DETAIL 14, THE CENTER OF THE TOILET IS NOT SHOWN. |
| | WOULD YOU PLEASE PROVIDE PER THE 2020 FBC SEC. 604.2 |
| | LOCATION. THE CENTERLINE OF THE WATER CLOSET SHALL BE |
| | 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE |
| | SIDEWALL OR PARTITION. |
| | |
| | G. ON THAT SAME DETAIL, IT DOES NOT SHOW THE DIMENSION |
| | HEIGHT OF THE MIRROR 40 INCHES TO THE BOTTOM OF THE |
| | REFLECTIVE, BOTTOM OF LAV 27 INCHES, GRAB BARS TO THE |
| | TOP OF THE GRIPPING SURFACE AT 36 INCHES. THE GRAB BAR |
| | FROM THE WALL, THE SIX INCHES IS NOT ACCURATE DUE TO |
| | THE DEVIANCE OF THE TOILET; IT SHOULD BE PER FIGURE |
| | 604.5.2 REAR WALL GRAB BAR WATER CLOSETS. |
| | |
| | I. ON DETAIL 15 AND 21, THE GRAB BAR ON THE REAR SHOW |
| | BE AS FIGURE 604.5.2 REAR WALL GRAB BAR WATER CLOSETS. |
| | SHOW THE DIMENSION HEIGHT OF THE MIRROR 40 INCHES TO |
| | THE BOTTOM OF THE REFLECTIVE. THE BOTTOM OF THE LAV |
| | NEEDS TO SHOW 27 INCHES. |
| | |
| | J. ON THAT SAME DETAIL, THE PARTITION HEIGHT IS NOT |
| | GREATER THAN 12 INCHES FROM THE FINISHED FLOOR SURFACE |
| | PER THE 2020 FBC P 405.3.5 URINAL PARTITIONS. |
| | |
| | K. ON DETAIL 16, THE GRAB BAR NEEDS TO BE A MIN OF 42 |
| | INCHES WHICH IS NOT SHOWN PER THE 2020 FBC ACC SEC. |
| | 604.5.1 SIDE WALL. THE BOTTOM OF THE LAV MUST BE 27 |
| | INCHES, GRAB BARS TO THE TOP OF THE GRIPPING SURFACE AT |
| | 36 INCHES, AND MIRROR 40 INCHES TO THE BOTTOM OF THE |
| | REFLECTIVE. |
| | |
| | M. WOULD YOU PLEASE SHOW OR MENTION THAT THE LAVATORY |
| | WATER SUPPLY AND DRAINPIPES UNDER THE SIDE SHALL BE |
| | INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST |
| | CONTACT PER THE 2020 FBC ACC SEC. 606.5. |
| | |
| | N. ON DETAIL 20, PLEASE PROVIDE THE 60 INCHES OF THE |
| | TURNING RADIUS IN BOTH ACCESSIBLE RESTROOMS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | O. ON THAT SAME DETAIL, THE 30 INCHES BY 48 INCHES ON |
| | THE LAV IN THE TWO-STALL IS MISSING, AND THE URINAL |
| | CLEAR FLOOR SPACE AND DIMENSION IN THE MEN'S DOES IS |
| | NOT SHOWN. THE TWO LAVS IN THE OPEN AREA REQUIRE |
| | DIMENSION AND THE CLEAR FLOOR SPACE. |
| | |
| | P. DOOR HANDLE FOR STALLS HARDWARE SHOULD BE NOTED ON |
| | BOTH SIDES OF THE DOOR PER THE 2020 FBC ACC SEC. |
| | 404.2.7. |
| | |
| | Q. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL |
| | SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE |
| | 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P |
| | 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET? |
| | |
| | |
| | R. HANDICAP HI AND LO WATER FOUNTAIN MISSING A HEIGHT |
| | DETAIL AND THE CLEAR FLOOR SPACE WITH THE DIMENSIONS |
| | PER WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION |
| | ON CONSTRUCTION DOCUMENTS. |
| | |
| | S. THERE IS A SINK DETAIL MISSING ON THE 12TH-FLOOR |
| | NEST TO THE LOCATION SUITE 1259B. IT IS NOT IN ANY OF |
| | THE DETAILS, AND IF IT'S ACCESSIBLE, PLEASE SHOW IT AS |
| | WELL. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS? |
| | |
| | 5. ON SHEET P-003, UNDER THE ICE MAKER IN FIXTURE |
| | SCHEDULE, THE ICEMAKER AND COFFEE MAKER SHALL BE |
| | EQUIPPED WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES |
| | WITH ASSE 1024 PER THE 2020 FBC SEC. 608.13.10. THE |
| | BACKFLOW PREVENTER MENTION 1022 IS FOR A SODA MACHINE, |
| | AND IF ONE IS PROVIDED, IT WILL REQUIRE A DRAIN AS THEY |
| | SPIT WATER PER MANUFACTURES SPECIFICATIONS. |
| | |
| | 6. ON SHEET P-501 DETAIL 8, THE TEMPERED WATER SHALL BE |
| | DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER FOR |
| | PUBLIC HAND-WASHING FACILITIES. |
| | |
| | |
| | 7. ON SHEET P- 502; |
| | |
| | A. ON DETAIL FOR THE WATER HEATER, PLEASE SHOW A VALVE |
| | DIRECTLY BEHIND AS IT SHOWS IN FRONT OF THE |
| | RECIRCULATING PUMP PER MOST MANUFACTURERS |
| | SPECIFICATIONS. |
| | |
| | B. ON THAT SAME DETAIL, IT SHOWS THE DRAIN VALVE |
| | CONNECTED TO THE DRAIN FOR THE DRAIN PAN. PLEASE |
| | SEPARATE AND HAVE DRAIN DUMP INTO THE PAN PER THE 2020 |
| | FBC P 501.3 |
| | |
| | 8. ON SHEET P-601; |
| | |
| | A. THE ISOMETRIC SANITARY IS HARD TO FOLLOW, THE LINE |
| | PATTERNS MAY BE TOO THICK, AND NO FIXTURES ARE LABELED. |
| | IF POSSIBLE, ENLARGE AND MAKE CLEAR TO READ, SHOW TRAP |
| | PRIMERS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | B. THERE SEEM TO BE A P-TRAP NEXT TO THE FLOOR DRAIN IN |
| | CONF. R, 1252, BUT IT IS AN FD-X, AND IT'S NOT LABELED. |
| | IT LOOKS LIKE IT'S ON THE WRONG LEVEL AND HARD TO |
| | UNDERSTAND. WOULD YOU PLEASE CORRECT OR MOVE FOR |
| | CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS? |
| | |
| | C. IN THE WOMEN'S AND MEN'S ROOMS, THE LAVS FOR THE |
| | ACCESSIBLE STALLS ARE NOT SHOWN TO THE CONNECTION FOR |
| | SANITARY. WOULD YOU PLEASE CLARIFY PER THE WPB |
| | AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS? |
| | |
| | D. ON THAT SAME SHEET FOR THE WATER ISOMETRIC LABEL, |
| | SHUT OFF VALVES, SHOW TRAP PRIMERS, AND AIR ARRESTORS. |
| | IF POSSIBLE, DO THE SAME FOR LINE PATTERNS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | ON THE RECIRCULATING PUMP, PLEASE REFER TO THE MANIFOLD |
| | FOR THE HOT WATER LINES WHICH SHALL BE SUPPLIED TO THE |
| | SOURCE; PLEASE REFER TO THE 2020 FBC ENERGY CODE TABLE |
| | C404.5.1. MAXIMUM ALLOWABLE PIPE LENGTH METHOD. THERE |
| | SEEMS NOT TO BE A LOOP. |
| | |
| | PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON |
| | ANY OF THE COMMENTS BY PHONE OR ZOOM MEETINGS IF YOU |
| | LIKE TO PREVENT FURTHER REVIEWS. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, DESCRIBING THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |