Plan Review Details - Permit 21080362
Plan Review Stops For Permit 21080362
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-08-31 Cont ID  
Sent By cpuell Date 2021-08-31 Time 14:51 Rev Time 0.00
Received By cpuell Date 2021-08-31 Time 14:51 Sent To  
Notes
2021-08-31 14:56:09APPLICANT UPLOADED NEW APPLICATION STATING THAT THE
 WORK IS FOR CONSTRUCTION LEVEL 11 MARKETING LEVEL 12
 SUITE 1200

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-13 Cont ID  
Sent By cpuell Date 2021-08-13 Time 12:39 Rev Time 0.00
Received By cpuell Date 2021-08-13 Time 12:38 Sent To  
Notes
2021-08-13 12:39:55IS THIS FOR CONSTRUCTION FLOOR 12 OR MARKETING FLOOR
 12? A TENANT SPACE DESIGNATOR WILL NEED TO BE ASSIGNED.
 PLEASE CONTACT [email protected] OR CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-10-12 Cont ID  
Sent By rmcphers Date 2021-10-12 Time 09:10 Rev Time 0.00
Received By rmcphers Date 2021-10-12 Time 09:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-09-22 Cont ID  
Sent By rmcphers Date 2021-09-22 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2021-09-22 Time 09:08 Sent To  
Notes
2021-09-22 09:14:14OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING G-001 SHOWS AN 18" GRAB BAR ABOVE THE
 REQUIRED 42 INCH GRAB BAR ON THE SIDE OF THE TOILET -
 PLEASE SHOW THE REQUIRED 12 INCH CLEARANCE ABOVE THE
 REQUIRED 42 INCH TOILET SIDE GRAB BAR AND ANYTHING
 ABOVE THE GRAB BAR - THE 18 INCH GRAB BAR IS NOT A
 REQUIREMENT OF THE 2020 FBC ACCESSIBILITY CODE - FBC
 ACCESSIBILITY 609.3 THE SPACE BETWEEN THE GRAB BAR AND
 PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305 MM)
 MINIMUM.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-08-27 Cont ID  
Sent By rmcphers Date 2021-08-27 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2021-08-27 Time 13:26 Sent To  
Notes
2021-08-27 16:28:18OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) DRAWING A-101 - DOOR 1259 B AND 1259 A - PLEASE SHOW
 THE REQUIRED 48" BETWEEN THE DOORS PER FBC 1010.1.8
 DOOR ARRANGEMENT.
 SPACE BETWEEN TWO DOORS IN A SERIES SHALL BE 48 INCHES
 (1219 MM) MINIMUM PLUS THE WIDTH OF A DOOR SWINGING
 INTO THE SPACE. DOORS IN A SERIES SHALL SWING EITHER IN
 THE SAME DIRECTION OR AWAY FROM THE SPACE BETWEEN THE
 DOORS.
 2) PLEASE ADD MORE WALL DESIGNATION LABELS ON THE FLOOR
 PLANS TO CLARIFY THE WALL TYPES THAT ARE NOT MARKED -
 FBC WPB 107.2.1
 3) DRAWING G-001 - PLEASE SHOW THE MIRROR DIMENSION
 FROM THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" PER
 FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 4) JOB COST SHOWN ON THE BUILDING PERMIT APPLICATION
 APPEARS TO BE LOW - FBC WPB 109.3 BUILDING PERMIT
 VALUATIONS. IF, IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION
 OF BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW
 DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL
 BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By shill Date 2021-08-20 Time 14:27 Rev Time 0.00
Received By shill Date 2021-08-20 Time 14:27 Sent To  
Notes
2021-08-20 14:30:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEVEN PLANS WERE SUBMITTED FOR A TENANT BUILDOUT,
 TWO FLOORS. FBC 107, PROVIDE ALL PLANS REQUIRED TO SHOW
 CODE COMPLIANCE.
  
 2. FS471, FS481, PLANS ARE REQUIRED TO BE DESIGNED BY A
 LICENSED ARCHITECT AND/OR ENGINEER. FOR EXAMPLE SEE
 SHEET 004, THIS WAS NOT PREPARED BY A DESIGN
 PROFESSIONAL.
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2021-10-12 Cont ID  
Sent By jleahy Date 2021-10-12 Time 10:54 Rev Time 0.00
Received By jleahy Date 2021-10-12 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2021-09-23 Cont ID  
Sent By jleahy Date 2021-09-22 Time 08:55 Rev Time 0.00
Received By jleahy Date 2021-09-22 Time 08:20 Sent To  
Notes
2021-09-23 09:03:38ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 VALUE OF WORK ON PERMIT APPLICATION IS LOW PLEASE
 PROVIDE A SIGNED CONTRACT FOR THE WORK INVOLVED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By jleahy Date 2021-08-31 Time 11:37 Rev Time 0.00
Received By jleahy Date 2021-08-27 Time 13:25 Sent To  
Notes
2021-08-31 11:51:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE EP-211, EP-212
  
 OUTLETS INSTALLED SHALL BE INSTALLED PER 406.12(5)
  
 406.12 TAMPER-RESISTANT RECEPTACLES. ALL 15- AND
 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE
 RECEPTACLES IN THE AREAS
 SPECIFIED IN 406.12(1) THROUGH (7) SHALL BE LISTED
 TAMPERRESISTANT RECEPTACLES.
 (1) DWELLING UNITS IN ALL AREAS SPECIFIED IN 210.52 AND
 550.13
 (2) GUEST ROOMS AND GUEST SUITES OF HOTELS AND MOTELS
 (3) CHILD CARE FACILITIES
 (4) PRESCHOOLS AND ELEMENTARY EDUCATION FACILITIES
 (5) BUSINESS OFFICES, CORRIDORS, WAITING ROOMS AND THE
 LIKE IN CLINICS, MEDICAL AND DENTAL OFFICES AND
 OUTPATIENT FACILITIES
 (6) SUBSET OF ASSEMBLY OCCUPANCIES DESCRIBED IN 518.2
 TO INCLUDE PLACES OF WAITING TRANSPORTATION,
 GYMNASIUMS, SKATING RINKS, AND AUDITORIUMS
 (7) DORMITORIES
  
 PAGE EP-212
  
 CONFERENCE ROOMS 1250,1251,1254, 1255 WALL AND FLOOR
 OUTLETS SHALL BE INSTALLED PER 210.71(A)(B).
  
 210.71 MEETING ROOMS.
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR
 NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71(B)
 (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF
 RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN
 FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED
 IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE
 PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2
 (215 FT2) SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 LOCATED IN THE FLOOR AT A DISTANCE NOT LESS THAN 1.8 M
 (6 FT) FROM ANY FIXED WALL
 FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR
 SPACE.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-08-16 Cont ID  
Sent By jleahy Date 2021-08-16 Time 07:45 Rev Time 0.00
Received By jleahy Date 2021-08-16 Time 07:34 Sent To  
Notes
2021-08-16 07:47:46ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NOT SURE OF THE SCOPE OF WORK, WHICH AREA IS
 ELECTRIC BEING ADDED.
  
 2) PLEASE PROVIDE A SIGNED CONTRACT FOR THE WORK. ALL
 WORK NOT JUST ELECTRIC.
  
 3) LOW VOLTAGE WORK REQUIRES A SEPARATE PERMIT AND
 PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-09-21 Cont ID  
Sent By pleduc Date 2021-09-21 Time   Rev Time 0.00
Received By pleduc Date 2021-09-21 Time 14:00 Sent To  
Notes
2021-09-21 14:02:02FIRE PROVISO:
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM SYSTEM,
 INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-08-31 Cont ID  
Sent By pleduc Date 2021-08-31 Time   Rev Time 0.00
Received By pleduc Date 2021-08-31 Time 12:50 Sent To  
Notes
2021-08-31 12:50:35FIRE PROVISO:
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM SYSTEM,
 INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-13 Cont ID  
Sent By pleduc Date 2021-08-13 Time   Rev Time 0.00
Received By pleduc Date 2021-08-13 Time 13:33 Sent To  
Notes
2021-08-13 13:52:05FIRE PROVISO:
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM SYSTEM,
 INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-10-18 Cont ID  
Sent By rmcphers Date 2021-10-18 Time 13:56 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 12:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-12 Cont ID  
Sent By jleahy Date 2021-10-12 Time 10:54 Rev Time 0.00
Received By jleahy Date 2021-10-04 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-09-23 Cont ID  
Sent By jleahy Date 2021-09-23 Time 09:03 Rev Time 0.00
Received By jleahy Date 2021-09-21 Time 07:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-08-31 Cont ID  
Sent By lcrespo Date 2021-08-31 Time 14:41 Rev Time 0.00
Received By lcrespo Date 2021-08-27 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-08-20 Cont ID  
Sent By shill Date 2021-08-20 Time 14:32 Rev Time 0.00
Received By shill Date 2021-08-11 Time 13:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2021-10-07 Cont ID  
Sent By medwards Date 2021-10-07 Time 06:49 Rev Time 0.00
Received By medwards Date 2021-10-07 Time 06:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-09-22 Cont ID  
Sent By medwards Date 2021-09-22 Time 14:01 Rev Time 0.00
Received By medwards Date 2021-09-22 Time 14:01 Sent To  
Notes
2021-09-22 14:02:113RD REVIEW FBC-2020 MECHANICAL
 PERMIT
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SEE COMMENT (1) OF PREVIOUS REVIEW CYCLE
 COMMENT: SHEET M-003: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON EACH USE OF SPACE ACCORDING TO
 FBC M 403.3.1.1 AND TABLE 403.3.1.1
 403.3.1.1.1 ZONE OUTDOOR AIRFLOW. THE MINIMUM OUTDOOR
 AIRFLOW REQUIRED TO BE SUPPLIED TO EACH ZONE SHALL BE
 DETERMINED AS A FUNCTION OF OCCUPANCY CLASSIFICATION
 AND SPACE AIR DISTRIBUTION EFFECTIVENESS IN ACCORDANCE
 WITH SECTIONS 403.3.1.1.1.1 THROUGH 403.3.1.1.1.3.
  
 VBZ = RPPZ + RAAZ (EQUATION 4-1)
  
 WHERE:
 AZ = ZONE FLOOR AREA: THE NET OCCUPIABLE FLOOR
 AREA OF THE SPACE OR SPACES IN THE ZONE.
 PZ = ZONE POPULATION: THE NUMBER OF PEOPLE IN
 THE SPACE OR SPACES IN THE ZONE.
 RP = PEOPLE OUTDOOR AIR RATE: THE OUTDOOR
 AIRFLOW RATE REQUIRED PER PERSON FROM
 TABLE 403.3.1.1.
 RA = AREA OUTDOOR AIR RATE: THE OUTDOOR AIRFLOW
 RATE REQUIRED PER UNIT AREA FROM TABLE
 403.3.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-08-27 Cont ID  
Sent By medwards Date 2021-08-27 Time 16:44 Rev Time 0.00
Received By medwards Date 2021-08-27 Time 13:15 Sent To  
Notes
2021-08-27 16:44:441ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080362
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-003: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON EACH USE OF SPACE ACCORDING TO
 FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 2) PLEASE SHOW THE REQUIRED PROTECTION WHERE THE DUCT
 SYSTEM PENETRATES THE RATED WALLS ON BOTH FLOORS. FBC
 M607
  
 3) PLEASE SHOW A DETAIL OF THE RETURN AIR PATH FROM
 TENANT SPACE BACK TO THE RETURN AIR DUCT FROM THE CORE
 MECHANICAL SYSTEM ON EACH FLOOR. FBC M 601.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By shill Date 2021-08-20 Time 14:30 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2021-08-20 14:30:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEVEN PLANS WERE SUBMITTED FOR A TENANT BUILDOUT,
 TWO FLOORS. FBC 107, PROVIDE ALL PLANS REQUIRED TO SHOW
 CODE COMPLIANCE.
  
 2. FS471, FS481, PLANS ARE REQUIRED TO BE DESIGNED BY A
 LICENSED ARCHITECT AND/OR ENGINEER. FOR EXAMPLE SEE
 SHEET 004, THIS WAS NOT PREPARED BY A DESIGN
 PROFESSIONAL.
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-09-21 Cont ID  
Sent By lcrespo Date 2021-09-21 Time 18:14 Rev Time 0.00
Received By lcrespo Date 2021-09-21 Time 18:14 Sent To  
Notes
2021-09-21 18:14:4609/21/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-08-31 Cont ID  
Sent By lcrespo Date 2021-08-31 Time 14:32 Rev Time 0.00
Received By lcrespo Date 2021-08-27 Time 12:05 Sent To  
Notes
2021-08-31 14:32:3708/31/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET G-001, SOME HEIGHTS FOR ACCESSIBILITY NEED
 TO BE ADJUSTED FOR THE TYPICAL MOUNTING HEIGHTS;
  
 A. THE GRAB BAR ON THE BACK THE SIX INCHES, NOT
 REQUIRED AS THE TOILET MAY BE ONE FOOT FOUR INCHES TO
 ONE FOOT SIX INCHES PER THE 20230 FBC SEC. 604.2
 LOCATION.
  
 B. THE GRAB BAR FROM THE SIDE FROM THE BACK CALLS FOR
 12 INCHES PER THE 2020 FBC SEC. 604.5.1 SIDE WALL.
  
 C. GRAB BAR FOR THE SIDEWALL IS INSTALLED IN A VERTICAL
 POSITION AND SHALL BE INSTALLED IN A HORIZONTAL
 POSITION PER THE 2020 FBC ACC SEC. 609.4.
  
 D. THE REFLECTIVE PART OF THE MIRROR NEEDS TO BE 40
 INCHES TO THE REFLECTIVE SIDE PER THE 2020 FBC ACC SEC.
 603.3.
  
 2. ON SHEET A100, THERE SEEMS TO BE A SINK; IS IT A
 BREAK ROOM? IF SO, CAN YOU PLEASE LABEL IT AND SHOW THE
 DETAIL AND LABEL IT AS WELL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 3. ON SHEET A101, THERE SEEMS TO BE A SINK; IS IT A
 BREAK ROOM? IF SO, CAN YOU PLEASE LABEL IT AND SHOW THE
 DETAIL AND LABEL IT AS WELL PER THE WPB AMENDMENTS TO
 THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. ON SHEET A400;
  
 A. ON DETAIL 1, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE AND DIMENSIONS IN FROM OF THE SINK PER THE 2020
 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 B. ON DETAIL 2, WOULD YOU PLEASE SHOW THE CLEAR FLOOR
 SPACE AND DIMENSIONS OF THE SINK PER THE 2020 FBC ACC
 SEC. 606.2. 2 CLEAR FLOOR SPACE.
  
 C. ON DETAIL 4, IT LOOKS LIKE THIS RESTROOM IS AN
 ACCESSIBLE RESTROOM. IF SO WOULD YOU, PLEASE LABEL AND
 SHOW THE CLEAR FLOOR SPACE FOR THE LABORATORY PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 D. ON DETAIL 10, THE GRAB BAR SHALL BE A MINIMUM OF 42
 INCHES AND NOT SHOWN. WOULD YOU PLEASE SHOW PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 E. ON THAT SAME DETAIL, IT SHOWS THE CENTER GRAB BARS,
 AND THEY SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE PER THE 2017 FBC ACC SEC. 609.4.
  
 F. ON DETAIL 14, THE CENTER OF THE TOILET IS NOT SHOWN.
 WOULD YOU PLEASE PROVIDE PER THE 2020 FBC SEC. 604.2
 LOCATION. THE CENTERLINE OF THE WATER CLOSET SHALL BE
 16 INCHES MINIMUM TO 18 INCHES MAXIMUM FROM THE
 SIDEWALL OR PARTITION.
  
 G. ON THAT SAME DETAIL, IT DOES NOT SHOW THE DIMENSION
 HEIGHT OF THE MIRROR 40 INCHES TO THE BOTTOM OF THE
 REFLECTIVE, BOTTOM OF LAV 27 INCHES, GRAB BARS TO THE
 TOP OF THE GRIPPING SURFACE AT 36 INCHES. THE GRAB BAR
 FROM THE WALL, THE SIX INCHES IS NOT ACCURATE DUE TO
 THE DEVIANCE OF THE TOILET; IT SHOULD BE PER FIGURE
 604.5.2 REAR WALL GRAB BAR WATER CLOSETS.
  
 I. ON DETAIL 15 AND 21, THE GRAB BAR ON THE REAR SHOW
 BE AS FIGURE 604.5.2 REAR WALL GRAB BAR WATER CLOSETS.
 SHOW THE DIMENSION HEIGHT OF THE MIRROR 40 INCHES TO
 THE BOTTOM OF THE REFLECTIVE. THE BOTTOM OF THE LAV
 NEEDS TO SHOW 27 INCHES.
  
 J. ON THAT SAME DETAIL, THE PARTITION HEIGHT IS NOT
 GREATER THAN 12 INCHES FROM THE FINISHED FLOOR SURFACE
 PER THE 2020 FBC P 405.3.5 URINAL PARTITIONS.
  
 K. ON DETAIL 16, THE GRAB BAR NEEDS TO BE A MIN OF 42
 INCHES WHICH IS NOT SHOWN PER THE 2020 FBC ACC SEC.
 604.5.1 SIDE WALL. THE BOTTOM OF THE LAV MUST BE 27
 INCHES, GRAB BARS TO THE TOP OF THE GRIPPING SURFACE AT
 36 INCHES, AND MIRROR 40 INCHES TO THE BOTTOM OF THE
 REFLECTIVE.
  
 M. WOULD YOU PLEASE SHOW OR MENTION THAT THE LAVATORY
 WATER SUPPLY AND DRAINPIPES UNDER THE SIDE SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 N. ON DETAIL 20, PLEASE PROVIDE THE 60 INCHES OF THE
 TURNING RADIUS IN BOTH ACCESSIBLE RESTROOMS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 O. ON THAT SAME DETAIL, THE 30 INCHES BY 48 INCHES ON
 THE LAV IN THE TWO-STALL IS MISSING, AND THE URINAL
 CLEAR FLOOR SPACE AND DIMENSION IN THE MEN'S DOES IS
 NOT SHOWN. THE TWO LAVS IN THE OPEN AREA REQUIRE
 DIMENSION AND THE CLEAR FLOOR SPACE.
  
 P. DOOR HANDLE FOR STALLS HARDWARE SHOULD BE NOTED ON
 BOTH SIDES OF THE DOOR PER THE 2020 FBC ACC SEC.
 404.2.7.
  
 Q. THE SERVICE SINK (MOP SINK) SURROUNDING THE WALL
 SHALL BE A NON-ABSORBENT SURFACE IN ACCORDANCE WITH THE
 2020 FBC BUILDING SEC. 1210.2.2 AND 2020 FBC SEC. P
 310.3. WOULD YOU PLEASE MAKE A NOTE ON THIS SHEET?
  
  
 R. HANDICAP HI AND LO WATER FOUNTAIN MISSING A HEIGHT
 DETAIL AND THE CLEAR FLOOR SPACE WITH THE DIMENSIONS
 PER WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 S. THERE IS A SINK DETAIL MISSING ON THE 12TH-FLOOR
 NEST TO THE LOCATION SUITE 1259B. IT IS NOT IN ANY OF
 THE DETAILS, AND IF IT'S ACCESSIBLE, PLEASE SHOW IT AS
 WELL. WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 5. ON SHEET P-003, UNDER THE ICE MAKER IN FIXTURE
 SCHEDULE, THE ICEMAKER AND COFFEE MAKER SHALL BE
 EQUIPPED WITH AN IN-LINE VACUUM BREAKER THAT COMPLIES
 WITH ASSE 1024 PER THE 2020 FBC SEC. 608.13.10. THE
 BACKFLOW PREVENTER MENTION 1022 IS FOR A SODA MACHINE,
 AND IF ONE IS PROVIDED, IT WILL REQUIRE A DRAIN AS THEY
 SPIT WATER PER MANUFACTURES SPECIFICATIONS.
  
 6. ON SHEET P-501 DETAIL 8, THE TEMPERED WATER SHALL BE
 DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3 PER THE 2017 FBC SEC. 416.5 TEMPERED WATER FOR
 PUBLIC HAND-WASHING FACILITIES.
  
  
 7. ON SHEET P- 502;
  
 A. ON DETAIL FOR THE WATER HEATER, PLEASE SHOW A VALVE
 DIRECTLY BEHIND AS IT SHOWS IN FRONT OF THE
 RECIRCULATING PUMP PER MOST MANUFACTURERS
 SPECIFICATIONS.
  
 B. ON THAT SAME DETAIL, IT SHOWS THE DRAIN VALVE
 CONNECTED TO THE DRAIN FOR THE DRAIN PAN. PLEASE
 SEPARATE AND HAVE DRAIN DUMP INTO THE PAN PER THE 2020
 FBC P 501.3
  
 8. ON SHEET P-601;
  
 A. THE ISOMETRIC SANITARY IS HARD TO FOLLOW, THE LINE
 PATTERNS MAY BE TOO THICK, AND NO FIXTURES ARE LABELED.
 IF POSSIBLE, ENLARGE AND MAKE CLEAR TO READ, SHOW TRAP
 PRIMERS PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THERE SEEM TO BE A P-TRAP NEXT TO THE FLOOR DRAIN IN
 CONF. R, 1252, BUT IT IS AN FD-X, AND IT'S NOT LABELED.
 IT LOOKS LIKE IT'S ON THE WRONG LEVEL AND HARD TO
 UNDERSTAND. WOULD YOU PLEASE CORRECT OR MOVE FOR
 CLARITY PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS?
  
 C. IN THE WOMEN'S AND MEN'S ROOMS, THE LAVS FOR THE
 ACCESSIBLE STALLS ARE NOT SHOWN TO THE CONNECTION FOR
 SANITARY. WOULD YOU PLEASE CLARIFY PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS?
  
 D. ON THAT SAME SHEET FOR THE WATER ISOMETRIC LABEL,
 SHUT OFF VALVES, SHOW TRAP PRIMERS, AND AIR ARRESTORS.
 IF POSSIBLE, DO THE SAME FOR LINE PATTERNS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 ON THE RECIRCULATING PUMP, PLEASE REFER TO THE MANIFOLD
 FOR THE HOT WATER LINES WHICH SHALL BE SUPPLIED TO THE
 SOURCE; PLEASE REFER TO THE 2020 FBC ENERGY CODE TABLE
 C404.5.1. MAXIMUM ALLOWABLE PIPE LENGTH METHOD. THERE
 SEEMS NOT TO BE A LOOP.
  
 PLEASE FEEL FREE TO SET UP A MEETING OR CONTACT ME ON
 ANY OF THE COMMENTS BY PHONE OR ZOOM MEETINGS IF YOU
 LIKE TO PREVENT FURTHER REVIEWS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, DESCRIBING THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By shill Date 2021-08-20 Time 14:31 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2021-08-20 14:31:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEVEN PLANS WERE SUBMITTED FOR A TENANT BUILDOUT,
 TWO FLOORS. FBC 107, PROVIDE ALL PLANS REQUIRED TO SHOW
 CODE COMPLIANCE.
  
 2. FS471, FS481, PLANS ARE REQUIRED TO BE DESIGNED BY A
 LICENSED ARCHITECT AND/OR ENGINEER. FOR EXAMPLE SEE
 SHEET 004, THIS WAS NOT PREPARED BY A DESIGN
 PROFESSIONAL.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-10-18 Cont ID  
Sent By rmcphers Date 2021-10-18 Time 13:45 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 13:45 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-10-12 Cont ID  
Sent By rmcphers Date 2021-10-12 Time 09:12 Rev Time 0.00
Received By rmcphers Date 2021-10-12 Time 09:12 Sent To  
Notes
2021-10-12 09:14:32SIGNATURE REVIEW
  
 DRAWINGS LABELED -
 003 G-001 - ABBREV, SYMBOLS & TYPICAL MOUNTING HGTS.PDF
 V3
 063 M-003 - MECHANICAL SCHEDULES.PDF V3
 071 M-806 - RMS FLOOR PLAN - LEVEL 12.PDF
 40 E-508 - ELECTRICAL DETAILS.PDF
 001 T-000 - TITLESHEET.PDF V2
 030 D-100 - DEMOLITION PLAN - 11TH FLOOR.PDF V2
 IN PROJECT AND ALL OF THE "G" AND "A" DRAWINGS - DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-09-22 Cont ID  
Sent By rmcphers Date 2021-09-22 Time 10:05 Rev Time 0.00
Received By rmcphers Date 2021-09-22 Time 09:29 Sent To  
Notes
2021-09-22 10:04:58SIGNATURE REVIEW
  
 DRAWINGS LABELED -
 071 M-806 - RMS FLOOR PLAN - LEVEL 12.PDF
 40 E-508 - ELECTRICAL DETAILS.PDF
 001 T-000 - TITLESHEET.PDF V2
 030 D-100 - DEMOLITION PLAN - 11TH FLOOR.PDF V2
 IN PROJECT AND ALL OF THE "G" AND "A" DRAWINGS - DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED AND
 SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-08-27 Cont ID  
Sent By rmcphers Date 2021-08-27 Time 16:42 Rev Time 0.00
Received By rmcphers Date 2021-08-27 Time 16:42 Sent To  
Notes
2021-08-27 16:43:24SIGNATURE REVIEW
 ALL OF THE DRAWINGS DO NOT SHOW AS ELECTRONICALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 BY THE ENGINEER OR ARCHITECT TO BE USED IN ELECTRONIC
 PLAN REVIEW. - OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-08-20 Cont ID  
Sent By shill Date 2021-08-20 Time 14:31 Rev Time  
Received By shill Date   Time   Sent To  
Notes
2021-08-20 14:32:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FS471, FS481, DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED DATED ORIGINALS. THE PLANS PREPARED BY
 THE ARCHITECT ARE NOT DIGITALLY SIGNED. CONTACT ME FOR
 ASSISTANCE IF NEEDED.
  