Plan Review Details - Permit 21080338
Plan Review Stops For Permit 21080338
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2021-10-04 Cont ID  
Sent By cpuell Date 2021-10-04 Time 14:50 Rev Time 0.00
Received By cpuell Date 2021-10-04 Time 14:50 Sent To  
Notes
2021-10-04 14:52:09UNITS 721 VILLAGE BLVD A AND B AND UNIT 731 VILLAGE
 BLVD 112 ARE AREAS OF WORK BEING WORKED ON.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-09-17 Cont ID  
Sent By cpuell Date 2021-09-17 Time 13:14 Rev Time 0.00
Received By cpuell Date 2021-09-17 Time 13:14 Sent To  
Notes
2021-09-17 13:14:43PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-08-19 Cont ID  
Sent By cpuell Date 2021-08-19 Time 14:16 Rev Time 0.00
Received By cpuell Date 2021-08-19 Time 14:16 Sent To  
Notes
2021-08-19 14:19:41PLANS INDICATE THAT YOU WILL BE CREATING A TOTAL OF
 THREE SUITE. WHILE WE DO HAVE THE ADDRESS OF 711
 VILLAGE BLVD 107A (PLEASE UPDATE YOUR DOCUMENTS WITH
 THE CORRECT ADDRESS OF 711 VILLAGE BLVD NOT 831 VILLAGE
 BLVD). PLEASE CONTACT [email protected] OR CALL
 561-805-6659 TO DISCUSS ADDRESSING OPTIONS FOR PROPOSED
 SUITES 107 B & C.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-10-15 Cont ID  
Sent By rmcphers Date 2021-10-15 Time 13:14 Rev Time 0.00
Received By rmcphers Date 2021-10-15 Time 13:14 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-09-23 Cont ID  
Sent By rmcphers Date 2021-09-23 Time 16:23 Rev Time 0.00
Received By rmcphers Date 2021-09-23 Time 16:23 Sent To  
Notes
2021-09-23 16:24:23WE DON'T NEED THE ASBESTOS SURVEY JUST A LETTER FROM
 THE CONTRACTOR -
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 15:38 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 15:02 Sent To  
Notes
2021-08-30 15:38:51PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-09-23 Cont ID  
Sent By rmcphers Date 2021-09-23 Time 16:22 Rev Time 0.00
Received By rmcphers Date 2021-09-23 Time 16:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-08-30 Cont ID  
Sent By rmcphers Date 2021-08-30 Time 15:58 Rev Time 0.00
Received By rmcphers Date 2021-08-30 Time 15:02 Sent To  
Notes
2021-08-30 15:58:07UNIT ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) ACCESSIBLE RESTROOM - PLEASE SHOW MIRROR HEIGHT FROM
 THE FINISHED FLOOR TO THE "REFLECTIVE SURFACE" PER FBC
 A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 2) ACCESSIBLE RESTROOM - PLEASE SHOW THE TOILET PAPER
 DISPENSER DIMENSION FROM THE FACE OF THE TOILET PER FBC
 A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
 3) ACCESSIBLE RESTROOM - PLEASE SHOW THE PAPER TOWEL
 DISPENSERS FROM THE OUTLET TO COMPLY WITH THE REACH
 RANGES PER FBC 308
 4) DRAWING S-201 SHOWS A SLAB IN FILL - PLEASE SHOW IF
 TERMITE PROTECTION IS REQUIRED PER FBC 1816.1.2

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-08-30 Cont ID  
Sent By jleahy Date 2021-08-30 Time 14:58 Rev Time 0.00
Received By jleahy Date 2021-08-30 Time 14:51 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-08-24 Cont ID  
Sent By pleduc Date 2021-08-24 Time   Rev Time 0.00
Received By pleduc Date 2021-08-24 Time 11:23 Sent To  
Notes
2021-08-24 11:29:27FIRE PROVISO:
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL
 BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-10-18 Cont ID  
Sent By rmcphers Date 2021-10-18 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 12:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-10-15 Cont ID  
Sent By rmcphers Date 2021-10-15 Time 13:17 Rev Time 0.00
Received By rmcphers Date 2021-10-15 Time 07:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-09-27 Cont ID  
Sent By lcrespo Date 2021-09-27 Time 16:13 Rev Time 0.00
Received By lcrespo Date 2021-09-17 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-07 Cont ID  
Sent By lcrespo Date 2021-09-07 Time 16:34 Rev Time 0.00
Received By lcrespo Date 2021-08-19 Time 10:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-09-23 Cont ID  
Sent By medwards Date 2021-09-23 Time 06:19 Rev Time 0.00
Received By medwards Date 2021-09-23 Time 06:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-08-21 Cont ID  
Sent By medwards Date 2021-08-21 Time 09:28 Rev Time 0.00
Received By medwards Date 2021-08-21 Time 09:28 Sent To  
Notes
2021-08-21 09:28:211ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21080338
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS PROJECT IS TAKING ONE LARGE TENANT SPACE AND
 CONVERTING IT INTO 3 NEW TENANT SPACES. THIS INCLUDES
 ADDING SOME NEW RTU?S AND AN AHU. PLEASE PROVIDE THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS.
  
 2) PLEASE SHOW THE CONDENSATE PIPING AND TERMINATION
 LOCATIONS. FBC M 307
  
 3) SHEET M-2: THE EXHAUST FANS (EF-1) SHOULD BE 80 CFM
 EACH. PLEASE ADJUST THE AIR BALANCE SCHEDULE. THERE IS
 NOT AN EF-2 IN THE EXHAUST FAN SCHEDULE. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-09-27 Cont ID  
Sent By lcrespo Date 2021-09-27 Time 16:10 Rev Time 0.00
Received By lcrespo Date 2021-09-27 Time 15:50 Sent To  
Notes
2021-09-27 16:13:1209/27/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-07 Cont ID  
Sent By lcrespo Date 2021-09-07 Time 16:33 Rev Time 0.00
Received By lcrespo Date 2021-09-07 Time 14:24 Sent To  
Notes
2021-09-07 17:20:2309/07/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET A-001;
 A. UNDER APPLICABLE CODE, IT REFERS TO THE 6TH EDITION,
 AND THE CURRENT IS THE 7TH EDITION. WOULD YOU PLEASE
 CORRECT PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. THE ACCESSIBILITY CODE IS NOT MOTIONED UNDER THE
 APPLICABLE CODES. WOULD YOU PLEASE ADD IT PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 C. UNDER PROJECT DESCRIPTION/SCOPE OF WORK, IT REFERS
 TO THE 2017 6TH EDITION FOR EXISTING AND BUILDING.
 WOULD YOU PLEASE CORRECT THE CURRENT 2020 7TH EDITION
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET A-003;
  
 A. IF POSSIBLE, WOULD YOU PLEASE DELETE OR
 STRIKETHROUGH ANY ADA DETAILS NOT PERTAINING TO THIS
 PROJECT TO MINIMIZE CONFUSION IN THE FIELD INSTALLATION
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. ON THE BOTTOM OF THE PAGE, LETTER B HAS THE GRAB BAR
 6 INCHES FROM THE WALL, WHICH IS INCORRECT AS THE
 TOILET MAYBE 16 INCHES TO 18 INCHES FROM THE WALL PER
 THE 2020 FBC ACC. SEC. 604.2 LOCATION. WOULD YOU PLEASE
 REFER TO THE 2020 FBC ACC 604.5.2 REAR WALL?
  
 C. ON A AND B, THE GRAB BAR IS MEASURED TO CENTER AND
 SHALL BE MEASURED TO THE TOP OF THE GRIPPING SURFACE
 PER THE 2020 FBC ACC SEC. 609.4.
  
 D. ON THE ADA GUIDELINES FOR THE RESTROOM, THE TOILET,
 AND GRAB BAR SIZES ARE INCORRECT. THE TOILET PAPER IS
 WRONG TO SEE 2020 FBC ACC SEC. 604.7, THE BACK GRAB BAR
 IS INCORRECT TO SEE 2020 FBC ACC SEC. 604.5.2 REAR
 WALL, THE DISTANCE FROM THE SIDE ALL VARIES SEE 2020
 FBC ACC. SEC. 604.2 LOCATION, THE TOP OF THE LAV IS NOT
 SHOWN SEE AND THE HIGHT OF THE GRAB BARS ARE INCORRECT,
 SEE 2020 FBC ACC SEC. 609.4.
  
 E. WOULD YOU PLEASE SHOW THE HANDLE OF THE WATER CLOSET
 TO THE OPEN SIDE PER THE 2020 FBC ACC SEC. 604.9.5.
  
 F. SEAT NEEDS TO BE OPEN FRONT, 2020 FBC P 420.3 WATER
 CLOSET SEATS.
  
 G. THE TOILET PAPER DISPENSERS SHALL BE 7? INCHES
 MINIMUM AND 9? INCHES MAXIMUM IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER PER
 THE 2020 FBC ACC SEC. 604.7.
  
 H. LAVATORY WATER SUPPLY AND DRAINPIPES UNDER THE SIDE
 SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT
 AGAINST CONTACT PER THE 2020 FBC ACC SEC. 606.5.
  
 I. WOULD YOU PLEASE SHOW THE RESTROOM WITH THE LAV AND
 TOILET ALONG WITH THE CLEAR FLOOR SPACE IN DIMENSIONS
 PER THE 2020 FBC ACC SEC. 606.2. 2 CLEAR FLOOR SPACE
 AND 2020 FBC ACC. SEC. 604.3.1.
  
 3. ON SHEET A-601;
 A. ON DETAIL 5, THE GRAB BARS SHALL BE MEASURED TO THE
 TOP OF THE GRIPPING SURFACE PER THE 2020 FBC ACC SEC.
 609.4.
  
 B. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE PER THE 2020 FBC ACC SEC. 609.4.
  
 C. WOULD YOU PLEASE SHOW REINFORCING FOR GRAB BARS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 D. ON DETAIL 6, IT DOESN?T SHOW THE HANDLE ON THE OPEN
 SIDE PER THE 2020 FBC ACC SEC. 604.9.5. THE 6 INCHES
 FROM THE WALL FOR THE GRAB BAR IS NOT CORRECT AS THE
 TOILET MAY BE 16 INCHES TO 18 INCHES FROM THE WALL PER
 THE 2020 FBC ACC. SEC. 604.2 LOCATION. WOULD YOU PLEASE
 REFER TO THE 2020 FBC ACC 604.5.2 REAR WALL? WOULD YOU
 PLEASE ADD THAT THE MIRROR IS MEASURED TO THE
 REFLECTIVE SIDE PER THE 2020 FBC ACC SEC. 603.3.
  
 4. ON SHEET P-2, WHERE TEMP VALVES ARE INSTALLED, THEY
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3 PER THE 2020 FBC SEC. 416.5 TEMPERED
 WATER FOR PUBLIC HAND-WASHING FACILITIES.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-10-18 Cont ID  
Sent By rmcphers Date 2021-10-18 Time 14:06 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 14:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-10-15 Cont ID  
Sent By rmcphers Date 2021-10-15 Time 13:16 Rev Time 0.00
Received By rmcphers Date 2021-10-15 Time 13:16 Sent To  
Notes
2021-10-15 13:17:20SIGNATURE REVIEW
  
 DRAWINGS BELOW LABELED IN PROJECTDOX AS -
 001 A 001 COVER SHEET.PDF V2
 003 A 003 ADA STANDARDS.PDF V2
 007 A 601 SCHEDULES.PDF V2
 012 M-2.PDF V2
 015 P-2.PDF V2
 - DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-09-23 Cont ID  
Sent By rmcphers Date 2021-09-23 Time 16:26 Rev Time 0.00
Received By rmcphers Date 2021-09-23 Time 16:26 Sent To  
Notes
2021-09-23 16:36:10SIGNATURE REVIEW
  
 DRAWINGS BELOW LABELED IN PROJECTDOX AS -
 001 A 001 COVER SHEET.PDF V2
 003 A 003 ADA STANDARDS.PDF V2
 007 A 601 SCHEDULES.PDF V2
 012 M-2.PDF V2
 015 P-2.PDF V2
 - DO NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER -
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-08-21 Cont ID  
Sent By medwards Date 2021-08-21 Time 09:30 Rev Time 0.00
Received By medwards Date 2021-08-21 Time 09:29 Sent To  
Notes
***NONE***